Wiring diagram. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW
Add to My manuals43 Pages
advertisement
![Wiring diagram. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW | Manualzz Wiring diagram. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW | Manualzz](http://s1.manualzz.com/store/data/069768442_1-dfcb447f2a4c1f8f93ad1ea64decc196-360x466.png)
Wiring diagram
* The wiring diagram below shows a fully equipped model.
L1 L2 L3 N
Terminals for extension RS1
Wiring length
2 m or less
RS2
Control power supply
513 P1
+
P2 97 C1
+
A1
+
See the figure below for wiring.
+ +
D2 D1 413 U1
+
Electronic trip relay
(ETR)
Reset circuit Power supply circuit
Alarm contacts
(Power supply type P3 ~ P5 only)
SHT CC
UVT
M
Breaker
Main circuit
N1 N2 Z1 Z2 P4
(
M8 screw
)
NCT ※ ZCT ※
※ Voltage forbid to be applied.
FG
Dielectric test forbidden
574 564 554 544 534 524 98 C2 A2 DT2 DT1 414 U2
Shorting bar
Push button for tripping
Wiring length
2 m or less
Electronic trip relay
Control power supply circuit/ alarm contact
OCR alarm
Electric operation circuit
E-32
Terminal description
13 14 ~ 53 54
11
U1
12
U2
~ 51 52
413 414
D1 D2
DT1 DT2
A1
C1
97
P1
P4
RS1 RS2
513 524
513 534
513 544
513 554
513 564
513 574
Z1 Z2
N1 N2
A2
C2
98
P2
Extension terminals
Auxiliary switch "a"
Auxiliary switch "b"
Motor charging
Charged signal (Normal open)
Voltage Input terminal of UVT
Trip terminal of UVT (Remote trip)
Closing coil
Shunt trip
OCR alarm
Power supply for ETR
FG of power supply (FG:Frame Ground)
Alarm reset (Trip cause LED, alarm contact)
Alarm contact for LTD Trip
Alarm contact for STD or INST Trips
Alarm contact for Ground fault, Earth leakage trips or 2nd Pre-alarm contact
Pre-alarm contact
Temperature alarm contact
Error alarm contact
For external ZCT
For Neutral CT
For external display DP2
For Interface unit
For VT unit
Fig. 32
CC
M
UVT
AX
AL
CLS
SBC
CL
Accessory Symbols
SHT Shunt tripping device
Closing coil
Motor(Motor charging device)
UVT coil
Auxiliary switch
OCR alarm switch
Charge limit switch
Shorting b-contact
Cell switch
Internal wiring
External wiring (user's wiring)
Control circuit connecter (drawout type)
51
+
41
+
31
+
21
+
11
+
53
+
43
+
33
+
23
+
13
+
341
+
331
+
321
+
311
+
Cell switch
52 42 32 22 12 54 44 34 24 14 344 342 334 332 324 322 314 312
Auxiliary switch (“b” contact) Auxiliary switch (“a” contact)
UVT controller voltage application
For 100-120 V AC
For 200-240 V AC
DC ratings
Apply voltage
D2 D1
For 380-460 V AC
Apply voltage
IN2 IN1
External unit
OUT4 OUT3
D2 D1
Control circuit terminal block
Applicable crimp terminal
A A
A = 7.2 mm or less
Applicable crimp-type terminals for M3.5 screws with an outer diameter of 7.2 mm or less.
(Wire size 1.25 mm 2 to 2.0 mm 2 )
Cell switch
For the drawout type, the cables should have the length which allow the control circuit terminal block to be moved to the left or right by 5mm.
When a coil load is connected in the same control circuit as the ETR, surge absorbers are required to absorb the surge voltage.
OCR alarm (AL)
The contact output of the OCR alarm (Standard type AL) is the one-pulse output and the output time is 30~50ms.
For this reason, this output needs self-holding circuit.
For Power supply type P3 and P4, the high sensitive relay used in contact output may cause the chattering noise (wrong output of 1ms level) during ON and OFF operation, depending on the
Panel placing condition. When it is used in the quick responsive sequence, the filter circuit of a few milli-second (ms) should be provided or the double reading sampling should be implemented.
Closing coil (CC)
As CC is one-pulse driven, it is not necessary to insert AXb for burning prevention purposes.
Inserting AXb will cause anti-pumping function to be ineffective.
Under voltage trip device (UVT)
Use the switch that can open and close 150V DC, 0.5A for remote trip.
Remote trip terminal has short bar at shipment, so remove it before using this function.
Disconnect the voltage input wires during dielectric testing of main circuit.
Since some terminals are polarized, the wiring should be done correctly as the polarity shown in the wiring diagram when the control voltage is DC. Auxiliary switch (AX) Standard type has no polarity.
Alarm reset (Terminal: RS1 and RS2 ) is available only for Power supply type P3, P4 and P5.
For Power supply type P1 and P2, it can not be reset from the Control circuit terminal block ( RS1 and RS2 ).
513 574 P3 P4
FG (Terminal: P4 ) is the protective earth for power supply (Terminal: P1 , P2 ).
It is recommended to use this terminal to reduce surge (M8 screw required).
Shorting b-contact (SBC)
SBC can be provided for all AX b contacts. At the time of shipment from factory, SBC is already connected to control circuit terminal block. Only one more crimp terminal can be added on contact, overlapping with SBC’s contact on Terminal: 11 ~ 51 .
* The wiring diagram below shows a fully equipped model.
L1 L2 L3 N
Terminals for extension RS1
Wiring length
2 m or less
RS2
Control power supply
513 P1
+
P2 97 C1
+
A1
+
See the figure below for wiring.
+ +
D2 D1 413 U1
+
Electronic trip relay
(ETR)
Reset circuit Power supply circuit
Alarm contacts
(Power supply type P3 ~ P5 only)
SHT CC
UVT
M
Breaker
Main circuit
N1 N2 Z1 Z2 P4
(
M8 screw
)
NCT ※ ZCT ※
※ Voltage forbid to be applied.
FG
Dielectric test forbidden
574 564 554 544 534 524 98 C2 A2 DT2 DT1 414 U2
Shorting bar
Push button for tripping
Wiring length
2 m or less
Electronic trip relay
Control power supply circuit/ alarm contact
OCR alarm
Electric operation circuit
Terminal description
13 14 ~ 53 54
11
U1
12
U2
~ 51 52
413 414
D1 D2
DT1 DT2
A1
C1
97
P1
P4
RS1 RS2
513 524
513 534
513 544
513 554
513 564
513 574
Z1 Z2
N1 N2
A2
C2
98
P2
Extension terminals
Auxiliary switch "a"
Auxiliary switch "b"
Motor charging
Charged signal (Normal open)
Voltage Input terminal of UVT
Trip terminal of UVT (Remote trip)
Closing coil
Shunt trip
OCR alarm
Power supply for ETR
FG of power supply (FG:Frame Ground)
Alarm reset (Trip cause LED, alarm contact)
Alarm contact for LTD Trip
Alarm contact for STD or INST Trips
Alarm contact for Ground fault, Earth leakage trips or 2nd Pre-alarm contact
Pre-alarm contact
Temperature alarm contact
Error alarm contact
For external ZCT
For Neutral CT
For external display DP2
For Interface unit
For VT unit
CC
M
UVT
AX
AL
CLS
SBC
CL
Accessory Symbols
SHT Shunt tripping device
Closing coil
Motor(Motor charging device)
UVT coil
Auxiliary switch
OCR alarm switch
Charge limit switch
Shorting b-contact
Cell switch
Internal wiring
External wiring (user's wiring)
Control circuit connecter (drawout type)
51
+
41
+
31
+
21
+
11
+
53
+
43
+
33
+
23
+
13
+
341
+
331
+
321
+
311
+
Cell switch
52 42 32 22 12 54 44 34 24 14 344 342 334 332 324 322 314 312
Auxiliary switch (“b” contact) Auxiliary switch (“a” contact)
UVT controller voltage application
For 100-120 V AC
For 200-240 V AC
DC ratings
Apply voltage
D2 D1
For 380-460 V AC
Apply voltage
IN2 IN1
External unit
OUT4 OUT3
D2 D1
Control circuit terminal block
Applicable crimp terminal
A A
A = 7.2 mm or less
Applicable crimp-type terminals for M3.5 screws with an outer diameter of 7.2 mm or less.
(Wire size 1.25 mm 2 to 2.0 mm 2 )
Cell switch
For the drawout type, the cables should have the length which allow the control circuit terminal block to be moved to the left or right by 5mm.
When a coil load is connected in the same control circuit as the ETR, surge absorbers are required to absorb the surge voltage.
OCR alarm (AL)
The contact output of the OCR alarm (Standard type AL) is the one-pulse output and the output time is 30~50ms.
For this reason, this output needs self-holding circuit.
For Power supply type P3 and P4, the high sensitive relay used in contact output may cause the chattering noise (wrong output of 1ms level) during ON and OFF operation, depending on the
Panel placing condition. When it is used in the quick responsive sequence, the filter circuit of a few milli-second (ms) should be provided or the double reading sampling should be implemented.
Closing coil (CC)
As CC is one-pulse driven, it is not necessary to insert AXb for burning prevention purposes.
Inserting AXb will cause anti-pumping function to be ineffective.
Under voltage trip device (UVT)
Use the switch that can open and close 150V DC, 0.5A for remote trip.
Remote trip terminal has short bar at shipment, so remove it before using this function.
Disconnect the voltage input wires during dielectric testing of main circuit.
Since some terminals are polarized, the wiring should be done correctly as the polarity shown in the wiring diagram when the control voltage is DC. Auxiliary switch (AX) Standard type has no polarity.
Alarm reset (Terminal: RS1 and RS2 ) is available only for Power supply type P3, P4 and P5.
For Power supply type P1 and P2, it can not be reset from the Control circuit terminal block ( RS1 and RS2 ).
513 574 P3 P4
FG (Terminal: P4 ) is the protective earth for power supply (Terminal: P1 , P2 ).
It is recommended to use this terminal to reduce surge (M8 screw required).
Shorting b-contact (SBC)
SBC can be provided for all AX b contacts. At the time of shipment from factory, SBC is already connected to control circuit terminal block. Only one more crimp terminal can be added on contact, overlapping with SBC’s contact on Terminal: 11 ~ 51 .
E-33
advertisement
Related manuals
advertisement
Table of contents
- 3 Table of contents
- 4 External view
- 5 Internal structure/Outline dimensions and product weight
- 6 Unpacking/Storage
- 7 Transportation
- 8 Installation
- 9 Installation of the drawout handle/Installation of the inter-phase barrier (BA)
- 10 Connection
- 12 Insert operation
- 14 Drawout operation
- 16 Charging operation
- 17 Open/close operation
- 19 Door interlock (DI)/Cylinder lock (CYL) and Castell lock (CAL)/OCR alarm (AL) [MRE: manual reset type]
- 20 Shutter lock (SST-LOCK)/Safety shutter nameplate
- 21 Functions of electronic trip relay (ETR) parts
- 23 Characteristics setting for the WS type
- 24 Characteristics setting for the WM type
- 25 Characteristics setting for the WB type
- 26 Characteristics setting for the WF type
- 28 Characteristics setting for the optional setting modules
- 30 Setting procedure for the electronic trip characteristics
- 32 Wiring diagram
- 34 Technical notes
- 35 Warranty
- 36 Inspection and maintenance
- 42 SERVICE NETWORK