Connection. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW
Add to My manuals43 Pages
advertisement
Connection
Use M12 screws (made of copper), spring washers, and small washers to connect to the conductors.
Clean the contact surface and securely tighten the screws with a appropriate torque.
The connecting area on main circuit terminal of the breaker is different depending on the shape of the breaker’s terminal.
Refer to the outline dimensions in the catalog.
Main circuit
Horizontal connection CAUTION
25mm
CAUTION
Small washer
M12
45±5N·m
Small washer
Spring washer
Small washer
Conductor
Fig. 10-1
Use small washers to connect that the washers do not overlap with each other.
Fig. 10-2
CAUTION
Conductor
Small washer
Spring washer
Breaker terminal
(silver plated)
Fig. 10-3
Appropriate tightening torque for conductor connection
Bolt size Tightening torque (N·m)
M12 45±5
Keep an insulation distance between the conductors to be connected according to the standard of the panel.
Breaker
Bolt
Please tighten screws after checking breaker’s terminal and conductor certainly contact with each other.
Make sure the conductor doesn’t apply the force to breaker’s terminal in any direction.
Fig. 10-4
E-10
Since fault current flowing through the conductors causes large electromagnetic forces, the conductors should be secured firmly, using the values in the below table as a reference. Max. distance between fixing support and breaker bus bar should be less than 200mm.
Breaker
Conductor
200 mm or less
Supporting fixture
Supporting between live parts of different poles and between the power supply and load terminals.
Fig. 11-1
Table 11-1 Electromagnetic force per 1 m of conductor (in the case of three phase short circuit)
Type
AE630-SW ~
AE1600-SW
AE2000-SWA AE2000-SW ~
AE3200-SW
Drawout type
AE4000-SWA
Fixed type
(N/m)
AE4000-SW ~
AE6300-SW
3 poles 4 poles 3 poles 4 poles 3 poles 4 poles
Conductor distance (mm)
Prospective fault current kA (pf)
30(0.2)
42(0.2)
50(0.2)
65(0.2)
75(0.2)
85(0.2)
100(0.2)
130(0.2)
85
-
-
-
-
7700
15100
21400
36100
115
-
-
-
-
5700
11200
15800
26700
105
-
-
-
-
6300
12200
17300
29300
130
5100
9900
14000
23600
31500
40400
-
-
190
3500
6800
9600
16200
21500
27600
-
-
170
3900
7600
10700
18100
24100
30900
-
-
152
4300
8500
12000
20200
26900
34500
-
-
145
4500
8900
12600
21200
28200
36200
-
-
262
2500
5000
7000
11800
15800
20000
27800
47000
When selecting conductors to be connected to the breakers, ensure that they have a sufficient current capacity. Refer to the right table.
Table 11-2 Conductor size
(IEC 60947-1, Ambient Temp. 40 °C, Open air)
Rated current
MAX (A)
630
1000
1250
1600
2000
2500
3200* 1
Conductor to be connected (copper)
Quantity Conductor size (mm) Arrangement
2
2
40 x 5
60 x 5
2
2
3
4
3
2
80 x 5
100 x 5
100 x 5
100 x 5
100 x 10
150 x 10
4000
AE4000-SWA drawout type
4000
AE4000-SWA fixed type
4
3
150 x 10
150 x 10
Vertical
(Note) Table 11-2 shows the conductor size that is indicated in IEC 60947-1 with an ambient temperature of 40 °C and in an open air environment.
Fig. 11-2 shows the testing conditions.
3m
Breaker
2m
4000
(AE4000-SW)
4 100 x 10
5000
6300
4
4
150 x 10
200 x 10 Fig. 11-2
*1 For 3200 A, connect a conductor which is sized for 3150 A.
For 3200 A or higher, there is no specification by IEC (IEC 60947-1). (Specification by the manufacturer)
Control circuit terminal block
Tighteing with excessive torque above the specification may cause damages of terminals and screws.
Be sure to tighten with the specified torque.
After removing screws, make sure not to tighten the screws diagonally.
Be careful not to apply excessive tension to the wirings.
Use a cross-head screwdriver with a diameter that matches the cross-shaped groove.
M3.5 ................................. No. 2
Crossover wiring
M3.5 x 10
Torque: 1.0 ± 0.2N·m
Control circuit terminal block
Applicable crimp-type terminals
A A
A = 7.2 mm or less
Applicable crimp-type terminals for M3.5 screws with an outer diameter of 7.2 mm or less.
(Wire size 1.25 mm 2 ~ 2.0 mm 2 )
Fig. 11-3 Fig. 11-4 Fig. 11-5
E-11
advertisement
Related manuals
advertisement
Table of contents
- 3 Table of contents
- 4 External view
- 5 Internal structure/Outline dimensions and product weight
- 6 Unpacking/Storage
- 7 Transportation
- 8 Installation
- 9 Installation of the drawout handle/Installation of the inter-phase barrier (BA)
- 10 Connection
- 12 Insert operation
- 14 Drawout operation
- 16 Charging operation
- 17 Open/close operation
- 19 Door interlock (DI)/Cylinder lock (CYL) and Castell lock (CAL)/OCR alarm (AL) [MRE: manual reset type]
- 20 Shutter lock (SST-LOCK)/Safety shutter nameplate
- 21 Functions of electronic trip relay (ETR) parts
- 23 Characteristics setting for the WS type
- 24 Characteristics setting for the WM type
- 25 Characteristics setting for the WB type
- 26 Characteristics setting for the WF type
- 28 Characteristics setting for the optional setting modules
- 30 Setting procedure for the electronic trip characteristics
- 32 Wiring diagram
- 34 Technical notes
- 35 Warranty
- 36 Inspection and maintenance
- 42 SERVICE NETWORK