![Open/close operation. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW | Manualzz Open/close operation. Mitsubishi Electric AE2000-SWA, AE4000-SW, Low-Voltage Air Circuit Breakers series Type AE-SW, AE3200-SW, AE630-SW | Manualzz](http://s1.manualzz.com/store/data/069768442_1-dfcb447f2a4c1f8f93ad1ea64decc196-360x466.png)
Open/close operation
< Conditions for closing operation >
ON operation becomes available when the following conditions are met.
The breaker is OFF condition.
The closing spring is charged.
The charging indicator shows “CHARGED”.
The state without OFF operations.
• Without SHT operation
• Without mechanical lock (Padlock, Cylinder lock, Mechanical interlock etc.)
• UVT controller power is supplied and no operation with trip terminals.
• The manual reset button is being reset
Manual open/close operation
< Closing >
Push the ON button, the breaker will close. The ON/OFF indicator will show “ON”, and the charging indicator will show
“DISCHARGED”. Operating force is less than 50N.
(Caution)
When an OFF locking device (padlock, cylinder lock, etc.) is being used, release the lock, and then perform the closing operation.
When closing or opening a drawout type breaker at the CONNECT or TEST position, do so with the locking plate protruded.
When an undervoltage trip device (UVT) is equipped, wait 1.5 sec. after applying the rated voltage before closing the breaker.
To perform the ON operation, check that the drawout position indicator shows “CHARGED” before pressing the ON button. (Fig. 17-2)
* If undervoltage tripping device ( UVT ) is UVT with a-contact, wait for 1.8 sec. Instead of 1.5 sec.
< Opening >
Push the OFF button, the breaker will be opened and the
ON/OFF indicator will show “OFF”. Operating force is less than 50N.
ON
OFF non-OFF instructions
Manual reset button
OFF
Fig. 17-1
Fig. 17-2
ON
Fig. 17-3
OFF
E-17
Electric open/close operation
< Closing >
Opening operation can be performed electrically by using a closing coil (CC). By applying the rated voltage to A1 and
A2 on the control circuit terminal block, the breaker can be closed.
The pumping preventing relay that performs only one operation with one input command is built in.
To close again, turn OFF the closing coil control supply
(between A1 and A2 ) once, and apply the rated voltage again. For a closing command to CC, wait at least a 0.5 sec. interval after completing charging and turning OFF the breaker.
(Caution)
For a closing command to CC after completing charging, wait at least a 0.5 sec. interval. If a closing command is given within 0.5 sec. after charging completion, the design life of the opening/closing operation may be shortened.
In some cases, the breaker does not close by a closing command given within 0.5 sec. after a manual OFF operation or an OFF operation by SHT.
When an undervoltage trip device (UVT) is equipped, the breaker does not close unless the power supply is applied.
(After applying the control supply to UVT, wait 1.5 sec. for the closing operation to become available.)
If undervoltage tripping device ( UVT ) is UVT with a-contact, wait for 1.8 sec. Instead of 1.5 sec.
< Opening >
Opening operation can be performed electrically by using a shunt trip device (SHT) or undervoltage trip device (UVT).
For SHT, apply a rated voltage to C1 and C2 of the control circuit terminal block.
For UVT, open between the trip terminals DT1 and DT2 of the control circuit terminal block. (A short-circuit bar is equipped when shipped from the factory. Remove this before using.)
Alternatively, turn OFF the voltage applied to D1 and D2 .
UVT circuit diagram (with the 100 to 120 V AC, 200 to 240 V AC, or DC spec. models)
+
D1
UVT controller
D2
DT1
UVT coil
OFF operating
Press button
Min. 0.2 sec.
2 m or less
DT2
Breaker
Note) For the rating of the OFF operation press button switch, use one for 150 V DC and 0.5 A or higher.
Fig. 18-3
CC circuit diagram
+
A1
Control supply
A2
Breaker
One-pulse circuit
CC unit
CC
Note) The 24 V DC to 48 V DC models are not equipped with rectifier circuits.
Fig. 18-1
SHT circuit diagram
+
C1
Control supply
C2
Breaker Cut-off switch
SHT
SHT unit
Note) The 24 V DC to 48 V DC models are not equipped with rectifier circuits.
Fig. 18-2
UVT circuit diagram (with the 380 to 460 V AC models)
IN1 OUT3
IN2
External unit
OUT4
+
D1
D2
UVT controller
UVT coil
DT1
OFF operating
Press button
Min. 0.2 sec.
2 m or less
DT2
Breaker
Note) For the rating of the OFF operation press button switch, use one for 150 V DC and 0.5 A or higher.
The external unit is dedicated to AE-SW. Only one UVT controller can be connected to one external unit.
Fig. 18-4
E-18
advertisement
Related manuals
advertisement
Table of contents
- 3 Table of contents
- 4 External view
- 5 Internal structure/Outline dimensions and product weight
- 6 Unpacking/Storage
- 7 Transportation
- 8 Installation
- 9 Installation of the drawout handle/Installation of the inter-phase barrier (BA)
- 10 Connection
- 12 Insert operation
- 14 Drawout operation
- 16 Charging operation
- 17 Open/close operation
- 19 Door interlock (DI)/Cylinder lock (CYL) and Castell lock (CAL)/OCR alarm (AL) [MRE: manual reset type]
- 20 Shutter lock (SST-LOCK)/Safety shutter nameplate
- 21 Functions of electronic trip relay (ETR) parts
- 23 Characteristics setting for the WS type
- 24 Characteristics setting for the WM type
- 25 Characteristics setting for the WB type
- 26 Characteristics setting for the WF type
- 28 Characteristics setting for the optional setting modules
- 30 Setting procedure for the electronic trip characteristics
- 32 Wiring diagram
- 34 Technical notes
- 35 Warranty
- 36 Inspection and maintenance
- 42 SERVICE NETWORK