Fire or Paging Microphone Connection to VAR4/VAR12/VAR20 Input. ASL INTERCOM SMC02G

Add to My manuals
60 Pages

advertisement

Fire or Paging Microphone Connection to VAR4/VAR12/VAR20 Input. ASL INTERCOM SMC02G | Manualzz

SMC02G/SMC02F/Variants - Product Manual

4.2.1 Fire or Paging Microphone Connection to VAR4/VAR12/VAR20 Input 1

The following diagram shows the connection of the SMC02 to the VAR4/VAR12/VAR20’s Mic/Line input 1 as

Zoned Fire Microphone or Paging Microphone, the latter being the only option for the ‘S’ variants.

Figure 5 SMC02 Connection to VAR4/VAR12/VAR20 Input 1

ZONED FIRE MICROPHONE / PAGING MICROPHONE

CONNECTIONS TO VAR4 / VAR12 / VAR20 INPUT 1

SMC02

POWER SUPPLY

+ SUPPLY

0V SUPPLY

FROM V400 AUX

OUTPUT

ALL-CALL-ONLY LED

VAR4 / VAR12 / VAR20

CONTROL PORT-1

ON BASE UNIT

PIN 11: ALL-CALL-ONLY-1

ALL CALL ONLY LED

(a)

SPEAK NOW LED

(a)

PIN 23: SPEAK-NOW-1

SPEAK NOW LED

FAULT LED

470

FAULT LED

PTT+

(a)

(a)

PIN 24: REMOTE FAULT-2 (b)

PIN 8: ALL-CALL-1

PIN 6: 0 V

PRESS-TO-TALK

AUDIO

DATA

LISTEN-IN

PTT-

AUDIO OUT -

AUDIO OUT+

DXN

DXP

AUDIO IN -

AUDIO IN+

INPUT-1

PIN1: AUDIO -

PIN2: AUDIO +

PIN5: DATA-

PIN9: DATA+

A OUTPUTS 1-4

ON BASE BOARD

PIN15: AUX OUT -

PIN17: AUX OUT +

(a) Fire Microphone connections: only on standard SMC02 units.

(b) Remote Fault Output to be programmed as 'Remote Fault Active Indicator' at the

Router.

!

!

For EMC compliance:

1. Cable tails to be < 3 cm.

2. Screen of all cables to be connected to earthing terminals installed on the rack.

Issue: 02 complete, approved

Page 25 of 60

SMC02G/SMC02F/Variants - Product Manual

4.2.2 Fire or Paging Microphone Connection to VAR4/VAR12/VAR20 Input 2

The following diagram shows the connection of the SMC02 to the VAR4/VAR12/VAR20’s Mic/Line input 2 as a Zoned Fire Microphone or Paging Microphone, the latter being the only option for the ‘S’ variants.

Figure 6 SMC02 Connection to VAR4/VAR12/VAR20 Input 2

ZONED FIRE MICROPHONE / PAGING MICROPHONE

CONNECTIONS TO VAR4 / VAR12/ VAR20 INPUT 2

SMC02

POWER SUPPLY

+ SUPPLY

0V SUPPLY

FROM V400 AUX

OUTPUT

VAR4 / VAR12/ VAR20

ALL-CALL-ONLY LED

CONTROL PORT-1

ON BASE UNIT

PIN 25: ALL-CALL-ONLY-2

ALL CALL ONLY LED

(a)

SPEAK NOW LED

(a)

PIN 12: SPEAK-NOW-2

SPEAK NOW LED

FAULT LED

470

FAULT LED

PTT+

(a)

(a)

PIN 24: REMOTE FAULT-2 (b)

PIN 7: ALL-CALL-2

PIN 6: 0 V

PRESS-TO-TALK

AUDIO

DATA

LISTEN-IN

PTT-

AUDIO OUT-

AUDIO OUT+

DXN

DXP

AUDIO IN -

AUDIO IN+

INPUT-2

PIN1 AUDIO -

PIN2 AUDIO +

PIN5 DATA-

PIN9 DATA+

A OUTPUTS 1-4

ON BASE BOARD

PIN15: AUX OUT -

PIN17: AUX OUT +

(a) Fire Microphone connections: only on standard SMC02 units.

(b) Remote Fault Output to be programmed as 'Remote Fault Active Indicator' at the

Router.

For EMC compliance:

1. Cable tails to be < 3 cm.

2. Screen of all cables to be connected to earthing terminals installed on the rack.

Issue: 02 complete, approved

Page 26 of 60

advertisement

Key Features

  • Easy to use: Intuitive user interface makes it easy to operate.
  • Versatile: Can be used for a variety of applications, including paging, intercom, and emergency announcements.
  • Expandable: Can be expanded to support up to 128 zones.
  • Reliable: Built to last with high-quality components.
  • Cost-effective: Affordable solution for businesses of all sizes.
  • Compact design: Takes up minimal space.
  • Wall or desk mountable: Can be installed in a variety of locations.
  • Optional accessories: Can be customized to meet specific needs.
  • Meets all relevant safety standards.
  • Backed by a comprehensive warranty.

Related manuals

Frequently Answers and Questions

What are the dimensions of the SMC02G?
The SMC02G is 220mm wide, 140mm high, and 80mm deep.
What type of power supply does the SMC02G require?
The SMC02G requires a 12V DC power supply.
How many zones can the SMC02G support?
The SMC02G can support up to 128 zones.
What is the maximum distance between the SMC02G and a remote station?
The maximum distance between the SMC02G and a remote station is 1000m.
Can the SMC02G be used with other ASL products?
Yes, the SMC02G can be used with other ASL products, such as the VAR4, VAR12, and VAR20 paging amplifiers.