How to modify the Network frequency parameter of a discrete module. Schneider Electric Software PLC Application-Specific Functions, Micro/Junior/Pro, 4.5
Реклама
Реклама
Discrete application configuration
How to modify the Network frequency parameter of a discrete module
At a Glance This parameter is used to adapt alternating inputs to the network frequency (50 or
60 Hz) of the TSX DEZ 08A4 , TSX DEZ 08A5 and TSX DMZ 28AR modules
(inputs).
It applies to all the module’s inputs.
Note: The network frequency can only be modified in local mode.
Procedure The table below shows the procedure for defining the Network frequency assigned to the module.
Step
1
2
Action
Access the hardware configuration screen of the required module.
Click on the 50Hz / 60Hz check box located in the module zone of the
Network field.
Result : the network frequency chosen will therefore be assigned to the module.
Configuration
Network
50 Hz
60 Hz
TSX DMZ 28AR [INPUTS: POSITION 03]
Inputs
Designation: 16E 115VCA+12S REL.BORN
86
TLX DS 37 PL7 xxE
Discrete application configuration
How to modify the Filtering time parameter for 24 DCV inputs of a discrete module
At a Glance This parameter defines the filtering period for the selected channel.
The filtering time is defined for a group of 4 consecutive channels and may vary between 0.1 and 7.5 ms in increments of 0.5 ms.
Note: The filtering time can only be modified in local mode.
Procedure The table below shows the procedure for defining the Filtering time parameter.
Step
1
2
Action
Access the hardware configuration screen of the required module.
In the pull-down menu located in the Filtering column, click on the button for the required group of channels.
Result : a pull-down list appears.
ChannelSymbol
6
7
4
5
2
3
0
1
12
13
14
15
8
9
10
11
Supply fault monitoring Task
Enable MAST
MAST
Filtering
4 ms
3 ms
3.5 ms
4 ms
4.5 ms
5 ms
4 ms
4 ms
Function
3 Select the required filtering period.
TLX DS 37 PL7 xxE
87
Скачать
Реклама