How to parameterize the alarm output of a discrete module. Schneider Electric Software PLC Application-Specific Functions, Micro/Junior/Pro, 4.5
Advertisement
Advertisement
Discrete application configuration
How to parameterize the RUN/STOP input of a discrete module
At a Glance The discrete input (%I1.8) can be parameterized to control the starting (Run) or stopping (Stop) of the execution of the application program.
Note: The change to Stop via the physical input %11.8 takes priority over a change to Run command from a terminal or network.
Procedure The table below shows the procedure for parameterizing the Run/Stop input.
Step
1
2
Action
Access the hardware configuration screen of the required module.
Double click on the 0 position.
Result : The processor configuration screen appears.
TSX 3722 [RACK 0 POSITION 0]
Configuration
Designation: Processor 3722
Operating Mode
%I1.8 Run/Stop
%Q2.0 Alarm
%I1.9 Save program and first %MWi
Auto. Start in Run
%MWi Reset on cold start
Memory Card
None
Tasks
MAST
Cyclic
Periodic
Watchdog
FAST
Period:
Watchdog
250
0 ms ms
FIPIO mode
Cycle time of network (calculated)
Controlled
Free ms
100
5 ms ms
FIPIO mode
Cycle time of network (calculated)
Controlled
Free ms
3 Check the %I1.8 Run/Stop box in the Operating mode field.
90
TLX DS 37 PL7 xxE
Download