How to access the channels debug screen of a discrete module. Schneider Electric Software PLC Application-Specific Functions, Micro/Junior/Pro, 4.5
विज्ञापन
विज्ञापन
Debugging discrete modules
Description of the debug screen for a discrete module.
At a Glance
Illustration
The debug screen displays the value and state of each of the selected module's channels in real time. It is also used to access the channel commands (forcing of the input/output value, Set/Reset an output, etc.).
The debug screen looks like this:
1
TSX DMZ 64DTK [OUTPUTS . POSITION 02]
2
Debugging
Designation: 32E 24VCC+32S 0.1A CONN
Reactivation Global unforcing
Outputs
3
4
Channel
6
7
4
5
2
3
0
1
12
13
14
15
8
9
10
11
Symbol State
0
F1
F0
F0
0
0
0
0
0
0
0
0
0
0
0
Error
ERR
ERR
ERR
ERR
ERR
ERR
ERR
ERR
ERR
ERR
ERR
ERR
ERR
ERR
ERR
ERR
Fallback
STOP
STOP
DIAG…
Function
ALARM
Channel 4 commands x
Forcing
F4 Force to 0
F5 Force to 1
F6
Write
F7
Unforce
Set
F8 Reset
Description
Number
1
2
The table below shows the different elements in the debug screen and their functions.
Element
Title bar
Function
Indicates the reference of the selected module and its physical position in the PLC.
Module zone Enables the user to select: l parameter type: l l
Configuration ,
Debugging (diagnostics), can only be accessed in online mode.
l channel type (inputs or outputs) displayed, if the module in question contains both inputs and outputs or the position (even or odd) for 32 channel modules.
Displays the designation of the selected module.
Provides direct access to: l l the Global unforcing function for channels, the module diagnostics, if the module is faulty (shown by the indicator integrated in the diagnostics access button, DIAG , which turns red).
l the Reactivation of outputs function ( for static output modules).
TLX DS 37 PL7 xxE