AEZ 801 / 802
Sensor link checking on TSX AEZ 802
At a Glance
Fault bit
This checking is available in the range 4-20 mA. In this range the fault is detected by the TSX AEZ 802 module when the intensity in the loop becomes less than 3.2 mA.
The sensor link fault is signaled by a status word bit for explicit exchange which can be used by the system.
Sensor link fault bit:
Bit name
%MWx.i.2:X0
Meaning (for Xj = 1)
Sensor link fault on channel i of module x
Note: The channels of a TSX AEZ 802 module which have not been hardwired should preferably be set between 0-20 mA. If this is not the case, a "sensor link" fault will be signaled by the module.
TLX DS 37 PL7 xxE
185
/
Downloaden
Even een vriendelijke herinnering. U kunt het document hier bekijken. Maar het belangrijkste is dat onze AI het al heeft gelezen. Het kan complexe dingen in eenvoudige bewoordingen uitleggen, uw vragen in elke taal beantwoorden en u helpen snel te navigeren, zelfs in de langste of meest ingewikkelde documenten.