PMC-5151 User Manual


Add to my manuals
279 Pages

advertisement

PMC-5151 User Manual | Manualzz

ICP DAS PMC-5151 User Manual

7.3 I/O Module Setting

PMC-5151 allows connections to ICP DAS M-7000 modules. It also supports standard Modbus RTU or Modbus TCP I/O modules. The I/O

Module Setting page allows user to add Modbus RTU or Modbus TCP I/O modules that are connected to the PMC-5151 to the list. After the module is added, it allows to set up the configuration of the I/O module. The setting page is shown as below:

Figure7-26 : I/O Module Setting Page

The following section will give more information how to add and complete settings of Modbus RTU I/O modules and Modbus TCP I/O modules. After all settings are completed, click “Save” button to save the changes.

Please Note:

1. The COM2 (RS-485) and COM3 (RS-485) interfaces on PMC-5151 allows connections to Modbus RTU I/O modules.

2. The LAN interface on PMC-5151 allows connections to Modbus TCP

I/O modules. For more detailed information of the LAN settings,

please refer to “

6.4 I/O Interface Setting

”.

3. One PMC-5151 allows connections to at most 8 Modbus I/O modules

(including M-7000 modules, Modbus RTU I/O modules and Modbus

TCP I/O modules.)

4. A single I/O interface (COM2, COM3 or LAN) allows connections to at most 16 devices (Power meters and I/O modules); each device requires its own index number. Therefore, if an I/O interface is connecting to both power meters and I/O modules, they will share the same set of the index numbers. For example, if COM2 is connecting to

2 Modbus RTU power meters and already takes the index numbers

No.1 and No.2, the Modbus RTU I/O modules that are going to be connected to COM2 can be only set as No.3 ~ No.16 that are not occupied.

7.3.1 Scan to Add ICP DAS M-7000 Modules

90

ICP DAS PMC-5151 User Manual

The user could use Scan function to add ICP DAS M-7000 Modules to the PMC-5151, the steps are as below: i Click on button to scan the M-7000 modules that are connected to the PMC-5151.

Figure7-27 :

The “Scan” button to search M-7000 module

ii When the Scan page appears (Figure 7-28), input the starting address and the ending address of the Modbus address that are going to perform scan. Click on “Scan”, the system will start to scan the

M-7000 modules that match the settings previously set, to cancel the scan, click on “Cancel”.

Figure7-28 : Set up the Scanning Range for the M-7000 module

iii When the system is performing the scan (Figure 7-29), the address that are performing scan will be dynamically shown on the upper left side, please wait till the scan operation is completed. To stop the scan operation, click on “Cancel” to terminal the scan and leave the page.

91

ICP DAS PMC-5151 User Manual

Figure7-29 : Scaning the M-7000 modules

iv After the Scan operation is completed, an M-7000 module list will appear (Figure 7-30). If the newly scaned module doesn’t match the module previously set on the same address, a window will appear

(Figure 7-31), please select the actual device that are connected to

PMC-5151. After all settings are completed, click “Save” button to save the changes.

Figure7-30 : The M-7000 List after Scan operation

Figure7-31 : Select the actual M-7000 modules connected to PMC-5151

92

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement

Table of contents