PMC-5151 User Manual


Add to my manuals
279 Pages

advertisement

PMC-5151 User Manual | Manualzz

ICP DAS PMC-5151 User Manual front of the pre-set Modbus I/O module and then click on

“Copy”, a new Modbus I/O module (in sequence) will be added to the list and the settings of the old Modbus I/O module will be copied to this newly added Modbus I/O module.

 Remove: Click the radio button in front of the Modbus I/O module and click on “Remove” to remove the selected Modbus

I/O module.

After all settings are completed, click “Save” button to save the changes.

7.3.5 M-7000 Module Setting

PMC-5151 support ICP DAS M-7000 module, the following section will give more detailed settings of ICP DAS M-7000 module setting page. (Figure 7-38)

 Nickname:For user to define nicknames for each M-7000 module, this nickname will be displayed on the “I/O

Information ” and “Rule Setting” pages.

 Description: The Description field provides a space for the user to make a brief description of this M-7000 module.

 Address: The address will be the Modbus address of this

M-7000 module, please make sure the address is the same as the settings of the module, if the setting is not accurate, the connection for PMC-5151 to the M-7000 module will be failed.

 Scan Rate: Input the time interval for PMC-5151 to periodically retrieve the I/O channel data of this M-7000 module, the setting range will be 0 ~ 65535 seconds.

 Polling Timeout: The time interval for PMC-5151 to send command to the M-7000 module and wait for the response, the unit will be ms. The setting range will be 1-10000 ms.

 Retry Interval: The time interval to wait for PMC-5151 to repeatedly send command again when PMC-5151 sends command to the M-7000 module and get no response. The unit will be second. the setting range will be 3 ~ 65535 seconds.

The settings interfaces of the DI, DO, AI and AO channels on the

M-7000 Module are as below:

 The DI channel setting for M-7000 module

96

ICP DAS PMC-5151 User Manual

The M-7000 module DI channel setting interface is shown as below (using M-7052 as an example)

Figure7-38 : M-7000 DI Channel Setting Page

The settings are as below:

 Nickname:For user to define nickname for each I/O channel, this nickname will be displayed on the “I/O Information” and

“Rule Setting” pages.

 Reset counter when power on: If the “Reset counter when power on” is selected for the DI channel, the DI channel counter of this M-7000 module will be reset to the default value when the PMC-5151 is powered on or after loading the rules.

After all settings of the DI channels are completed, continue the configuration of other channel, and after all channel settings are completed, click “OK” button to save the changes and return to

Modbus RTU Module List.

Please Note:

1. For M-7000 modules, the counting mode of the DI channel counter is Falling.

2. To set up the default value of the DI channels on M-7000 modules, please use DCON Utility to set the value.

 The DO channel setting for M-7000 module

97

ICP DAS PMC-5151 User Manual

The M-7000 module DO channel setting interface is shown as below (using M-7060 as an example)

Figure7-39 : M-7000 DO Channel Setting Page

The settings are as below:

 Nickname:For user to define nickname for each I/O channel, this nickname will be displayed on the “I/O Information” and

“Rule Setting” pages.

 For M-7000 DO channels, PMC-5151 provides the following options for advanced function:

 Disable: Disable the advanced function

 Auto OFF: When “Auto OFF” is selected, it allows this

DO channel to enable Auto OFF function. It is required to set up a time interval, when this DO channel is set to be “ON” and the duration of the ON status reaches the pre-set time interval , the DO will automatically be set to OFF. The unit is second.

 DI Status Mapping: When “DI Status Mapping” is selected, the status of the DI channel with the same channel number on the M-7000 module will be copied to the DO channel. For example, when the “DI Status Mapping” is enabled on DO0, when the DI0 status is ON, DO0 will set to be ON, and when the DI0 status is OFF, DO0 will set to be OFF as well.

After all settings are completed, click “OK” button to save the

98

ICP DAS PMC-5151 User Manual changes and return to Modbus RTU Module List.

Please Note:

1. To set up the Power On value of the DO channels on M-7000 modules, please use DCON Utility to set the value.

2. The DO channels on M-7000 modules do not offer Pulse

Output function.

 The AI channel setting for M-7000 module

The M-7000 module AI channel setting interface is shown as below (using M-7018 as an example)

Figure7-40 : M-7000 AI Channel Setting Page

The settings are as below:

 Nickname:For user to define nickname for each I/O channel, this nickname will be displayed on the “I/O Information” and

99

ICP DAS PMC-5151 User Manual

“Rule Setting” pages.

 Type: Select the input signal type of the AI channel from the dropdown list.

 Deadband: Please refer to Deadband section in the “

7.2.3

XW-Board AI Channel Settings

” for more detailed information.

 Scale: Please refer to Scale section in the “

7.2.3 XW-Board AI

Channel Settings

” for more detailed information.

After all settings are completed, click “OK” button to save the changes and return to Modbus RTU Module List.

 The AO channel setting for M-7000 module

The M-7000 module AO channel setting interface is shown as below (using M-7024 as an example)

Figure7-41 : M-7000 AO Channel Setting Page

The settings are as below:

 Nickname:For user to define nickname for each I/O channel, this nickname will be displayed on the “I/O Information” and

“Rule Setting” pages.

 Type: Select the output signal type of the AO channel from the dropdown list.

After all settings are completed, click “OK” button to save the

100

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Table of contents