Schneider Electric Software PLC Application-Specific Functions, Electronic cam module, Junior/Pro, 4.5 User Guide
Werbung
Werbung
PL7 Junior/Pro
Premium PLCs
Electronic cam module
TSX CCY 1128
Application implementation manual
eng March 2005
2
Document set
At a glance This manual has 8 volumes: l l
Volume 1 l l
Common application specific functions
Discrete application l AS-i implementation l Dialogue operator application
Volume 2 l l Counting Application
Volume 3 l l l Axis Command application
Volume 4 l Step-by-step axis command application
Volume 5 l l Electronic cam application
Volume 6 l l l SERCOS application
Volume 7 l Analog application l PID Control application l Weighing application
Volume 8 l Regulation application
Document set
TLX DS 57 PL7 xx
3
Document set
4
TLX DS 57 PL7 xx
Table of Contents
About the book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1
Introduction to the electronic cam module . . . . . . . . . . . . . . . 11
General introduction to the Electronic Cam Module . . . . . . . . . . . . . . . . . . . . . . 12
Functions for the module’s software implemention. . . . . . . . . . . . . . . . . . . . . . . 22
Methodology for setting up module software. . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
General ergonomics for the module implementation functions . . . . . . . . . . . . . . 25
Chapter 2
Types of applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Chapter 3
Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.1
3.2
5
6
Chapter 4
Configuration of the electronic cam module. . . . . . . . . . . . . . 63
Accessing the module configuration parameters . . . . . . . . . . . . . . . . . . . . . . . . . 66
Configuring the position recalibration function for incremental encoders . . . . . . 74
Chapter 5 Entering recipe adjustment parameters for the electronic cam
module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Accessing the recipe adjustment parameters for the module . . . . . . . . . . . . . . . 82
Entering acquisition parameters for an incremental encoder. . . . . . . . . . . . . . . . 83
Entering the acquisition parameters for an absolute encoder . . . . . . . . . . . . . . . 85
Parametering the confirmation condition associated with a cam . . . . . . . . . . . . . 98
Confirming the recipe adjustment parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Restoring the recipe adjustment parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Chapter 6
Debugging and adjusting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Description of the debugging zone: "Acquisition" . . . . . . . . . . . . . . . . . . . . . . . 108
Description of the debugging zone: "Parts counter" . . . . . . . . . . . . . . . . . . . . . 110
Description of the debugging zone: "Group x" . . . . . . . . . . . . . . . . . . . . . . . . . 111
Chapter 7
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Module adjustment parameters, explicit command . . . . . . . . . . . . . . . . . . . . . . 134
WRITE_PARAM: Transfer of current recipe parameters . . . . . . . . . . . . . . . . . 144
READ_PARAM: Transfer of current recipe parameters . . . . . . . . . . . . . . . . . . 146
RESTORE_PARAM: Transferring initial parameters . . . . . . . . . . . . . . . . . . . . 147
SAVE_PARAM: Transferring initial parameters . . . . . . . . . . . . . . . . . . . . . . . . 148
TRF_RECIPE: Recipe transfer functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
TRF_RECIPE: Functions for storing recipes. . . . . . . . . . . . . . . . . . . . . . . . . . . 159
TRF_RECIPE: Loading a new recipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
DETAIL_OBJECT: Operator dialog interface . . . . . . . . . . . . . . . . . . . . . . . . . . 164
DETAIL_OBJECT: Transferring cam details . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
DETAIL_OBJECT: Transferring track details . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Chapter 8
Performance and limitations . . . . . . . . . . . . . . . . . . . . . . . . . . 171
General time-division performance characteristics . . . . . . . . . . . . . . . . . . . . . . 179
Chapter 9
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
7
8
Glossary
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
About the Book
At a Glance
Document Scope This manual describes the software implementation for the Electronic Cam application.
Validity Note This updated version includes the functions of the PL7 V4.5. Nevertheless, it can be used to install previous versions of PL7.
Related
Documents
Title of Documentation
Hardware set-up manual
Reference Number
TSX DM 57 xxE
User Comments We welcome your comments about this document. You can reach us by e-mail at [email protected]
9
About the book
10
TLX DS 57 PL7 xx
Introduction to the electronic cam module
1
At a glance
Subject of this chapter
What's in this chapter?
This chapter presents the main characteristics and functions of the TSX CCY 1128 electronic cam module.
This chapter contains the following topics:
Topic
General introduction to the Electronic Cam Module
Operation of the electronic Cam Module
Position reading
Cam processing operation
Structuring the cam processes
Interface with the PLC program
Functions for the module’s software implemention.
Methodology for setting up module software
General ergonomics for the module implementation functions
Page
11
TLX DS 57 PL7 xx
Introduction to the electronic cam module
General introduction to the Electronic Cam Module
Introduction
Areas of
Application
Main characteristics
The TSX CCY 1128 electronic cam module is designed to control 24 discrete physical outputs independently and with a very short response time (<0.2ms).
3.3 or above).
Its software is installed using PL7 Junior or Pro software (software version 3.4 or above) and the PL7 software enhancement patch.
l l l l
The TSX CCY 1128 module can process applications with the following types of motion: single-direction rotary (e.g.: mechanical presses), alternating (e.g.: hydraulic presses, transfer machines), cyclical, with periodic entry of parts to be processed (e.g.: packaging machines) continuous, with random entry of parts to be processed (e.g.: conveyors)
This table summarizes the main functional characteristics of the electronic cam module.
Characteristic
Number of cams
Number of tracks
Position encoder inputs
Outputs controlled
Types of cam
Associated functions
Value
128 maximum
32 (24 directly associated to the 24 physical outputs, 8 logic) incremental or absolute
24 discrete outputs 24V, 0.5A
position, monostable, brake compensating for axis play, readjusting the position, capturing the readings, switching anticipation, parts counter, generating events.
12
TLX DS 57 PL7 xx
Introduction to the electronic cam module
Operation of the electronic Cam Module
Introduction
Illustration
Description
The module calculates the position’s reading from an absolute or incremental encoder connected to its inputs. The module controls its outputs depending on this position and on the transferred cam program (acceptance).
The following diagram illustrates the operation of the cam module.
TSX 57 processor Electronic cam module Application
Tracks
Configuration
Recipe
Actuator
Cam processor Encoder
Sequential program
Position
Axis
Position: the module calculates the position’s reading (angular and number of turns) according to the parameters provided by the position encoder.
Cam processor: defines when the cams switch from 1 to 0 according to the l l l configuration and acceptance parameters transmitted by the PLC processor.
Tracks: control the outputs of the module according to the status of the cams associated with them.
PLC interface: this enables: the transfer of the configuration and acceptance parameters to the module, hardware faults to be recognized in the sequential program: the management of the machine operating modes and the extension of the module functions by acting directly on the outputs.
TLX DS 57 PL7 xx
13
Introduction to the electronic cam module
Position reading
Calculation of the Position
Value
Using an incremental or absolute position encoder, the module calculates: l l the angular position value of the machine, the turn number value (for multi-turn processes).
All the operations performed in the module are based on the angular value. The number of turns may be taken into account in the sequential program.
Position Encoder The module accepts 2 encoder types
Encoder type
Incremental
Absolute
Characteristics l l l l l l
500 kHz bandwidth multiplication by 4 line check
SSi frame, any type of 8..25 bit format transmission frequency determined automatically reduction of resolution by 2, 4, 8, 16 and 32
Associated
Functions
Note: The cam module also takes parallel output absolute encoders (via Telefast
ABE 7CPA11).
In addition to the basic functions, the electronic cam module provides the following functions:
Function
Readjustment (See
Configuring the position recalibration function for
Captures (See Capture
function configuration, p. 75)
Compensation for wear (See
Entering acquisition parameters for an
Role initializes the position reading value take various types of reading, such as: length of parts, number of pulses per turn, incoming angle of parts, slip compensates for play when there is a change of direction of movement
14
TLX DS 57 PL7 xx
Introduction to the electronic cam module
Cam processing operation
Role of the
Tracks and the
Cams
A track is made up of one or more cams. It controls a physical output of the module.
A cam defines an action on the output in a position reading interval.
Example of a cam in active position in both forward and reverse directions: the output associated to the track is activated when the angular reading is between 2 position values, X1 and X2 (when moving in either direction.).
State of the Encoder rotation
Forward
Forward direction
Reverse direction
Analogy with
Mechanical
Cams
The following illustration shows a mechanical equivalent of the electronic cam.
Encoder Track 0 Track 1 Track n
Cams
Position
Output
TLX DS 57 PL7 xx
15
Introduction to the electronic cam module
Operation The following table describes the operation of a track to which 2 cams are associated:
Phase Phase Description
1 The axis turns forward and drives the position encoder.
The module calculates the position reading by evaluating the encoder increments.
Track i is not active, output Qxy.i is at 0.
2 When threshold X1 on cam 0 is reached: l l track i becomes active, output Qxy.i switches to 1.
3 When threshold X2 on cam 0 is reached: l l track i becomes inactive, output Qxy.i switches to 0.
4 When threshold X1 on cam 1 is reached, l l track i becomes active, output Qxy.i switches to 1.
5 When threshold X2 on cam 1 is reached, l l track i becomes inactive, output Qxy.i switches to 0.
6 The axis continues to rotate and the process is repeated (returns to phase no. 1).
16
TLX DS 57 PL7 xx
3 types of cam
Introduction to the electronic cam module
The following table describes the 3 types of cam available. These cams can be active in forward or reverse direction, or forward and reverse simultaneously.
Type of cam
Position (See Cam in
Monostable (See
Braking (See Breaking
Role
A position cam is a cam whose logic state depends on the position of the axis in relation to 2 thresholds.
A monostable cam is one which switches to 1 when a threshold is crossed and returns to 0 after a time delay. This function is suitable for slow shaft detection.
A brake cam is one which switches to 1 when a threshold is crossed and returns to 0 when the same threshold is crossed in the opposite direction. This function is suitable for controlling braking at the top dead center of the machine.
Associated
Functions
In addition to the basic functions, the electronic cam module provides the following functions:
Function
Feedforward (See
Parametering for the
Parallel track (See
Parametering for the
Event (See Parametering
Parts counter (See
Parametering for the
Role
Compensates for the delay caused by the machine’s actuators.
Makes 2 tracks in one group parallel.
Triggers an event each time the track is switched.
Manages the number of parts processed or cycles performed and reacts on the process when the counter has reached the limit value.
TLX DS 57 PL7 xx
17
Introduction to the electronic cam module
Structuring the cam processes
General
Distributing the
Tracks and the
Cams
The cam process is done by a maximum of 128 cams divided between 32 tracks.
The tracks are associated with the outputs of the module.
Processing is organized into 4 groups of 8 tracks, with groups 0 and 1 being associated with connector 0 on the module and groups 2 and 3 associated with connector 1.
The following table describes the complete processing structure and the relationships with the module outputs.
Connector
Group
Maximum
Number of
Cams
Tracks
Outputs
Connector
0
0
32
1
32
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
Q0.
0 1 2 3 4 5 6 7
0
Q1.
0 1 2 3
1
2
32
0 1 2 3 4 5 6 7
Q2.
0 1 2 3 4 5 6 7
1
3
32
0 1 2 3 4 5 6 7
Q3.
0 1 2 3
Up to 32 cams can be assigned to one track, but in this case it is no longer possible to assign cams to the other tracks in the same group.
Tracks 4, 5, 6 and 7 of groups 1 and 3 are not linked to any physical output, and can be paralleled with tracks 0, 1, 2 and 3 of the same groups, or they can be used to control an output of a discrete module via the sequential program.
18
TLX DS 57 PL7 xx
Example
Introduction to the electronic cam module
In the example below, 3 cams have been assigned to track 2 of group 1, which is associated with connector 0. This track controls output Q1.2
Electronic cam
01
Acquisition
Cam processor
Parts counter
Connector0
Group0
Group1
Track0
Track1
Track2
Cam0 P(100, 200, 0)
Cam1 M(50, 0, 20)
Cam2 F(10, 220, 0)
Track3
Track4
Track5
Track6
Track7
Connector1
TLX DS 57 PL7 xx
19
Introduction to the electronic cam module
Interface with the PLC program
General
Illustration of exchanges
Although it is independent, the processing of the electronic cam module is controlled by the sequential program of the PLC processor.
The electronic cam module benefits from: l performances due to the independent module process (independence in relation l to the cycles of PLC tasks) automatic cyclic exchanges with the main program in order to communicate with the other parts of the application.
States are read and commands written via the PLC sequential program using language objects associated with the module: %I, %Q, %M, etc accessible via mnemonics.
The following diagram illustrates the various exchanges between the electronic cam module and the PLC processor.
TSX CCY 1128 PLC processor
Recipe
Events
States
Commands
%MW
%IW
%I / %IW
%Q / %QW
20
TLX DS 57 PL7 xx
Description of the data exchanged
Introduction to the electronic cam module
The following table describes the main data that is exchanged.
Type of data
Recipe
Statuses
Commands
Event
Description
The recipe groups together the data required for the module to control the machine for a series of parts. The recipe can be modified or completely changed by the PLC application. All this information is contained in the %MW PLC words in the memory zone reserved for the module.
l l
It contains the: l data for acquisition: the value of recalibration, play, parameters of the encoder (offset, reduction factor) etc.
descriptors of the tracks: parts counter,anticipation… cam descriptors: cam type, threshold values…
This data is used to control the electronic cam application in order to supervise, diagnose, or perform operations on the other elements of the application. It contains the values: l l l l l l of the states of the physical inputs of the position reading (angle and number of turns) of the parts counter of the registers of capture of the states of the tracks and the outputs of any faults
This data is used to control the electronic cam application from the
PLC processor program to perform operations on the operating modes, enable the functions, force the outputs, etc.
l l l
It contains the commands: l l l for starting or stopping the cam program enabling the functions: recalibration, capture, position counting direct commands on the following functions: recalibration, capture, parts counting enabling cams and tracks forcing outputs masking events
Activates the PLC processor event task. The module transmits data to the PLC processor regarding: l l the source of the event the angle values and number of turns which have been captured
TLX DS 57 PL7 xx
21
Introduction to the electronic cam module
Functions for the module’s software implemention.
General
Description of the Functions
PL7 software is used for the software implementation of the TSX CCY 1128 module.
The following table describes the functions specific to the electronic cam provided by PL7 for implementing a TSX CCY 1128 module.
Functions Description Operating mode of the terminal
Configuration Used for entering the configuration parameters of the module: l acquisition: type of encoder, reading format, type of recalibration, type of l l capture...
cam processor: resetting the tracks, performance with errors...
connector: inversion of the tracks.
Adjusting the recipe
Used for entering the adjustment parameters of the recipe: l acquisition: number of points per cycle, play, recalibration value… l cam processor: association of the cams with the tracks, track parameters, cam parameters, etc l Parts counter: threshold
Adjustment
Local or connected
Local or connected
Used to modify certain adjustment parameters of the module recipe without stopping the cam processor: l l acquisition: play, recalibration value, cam processor: anticipation factor, thresholds and values of cam time delays.
Connected
Operating mode of the cam processor
Stop
Stop
Stop or Run
22
TLX DS 57 PL7 xx
Introduction to the electronic cam module
Functions
Debugging
Description
Used to execute the following commands: l l l enabling cams, enabling, forcing outputs, enabling, activating recalibration functions, capturing.
It can also be used to display the following statuses: position reading, inputs, etc, and to perform module and application diagnostics.
Operating mode of the terminal
Connected
Operating mode of the cam processor
Stop or Run
TLX DS 57 PL7 xx
23
Introduction to the electronic cam module
Methodology for setting up module software
Illustration The following flowchart summarizes the various implementation phases for an electronic cam application.
In local mode
Entering configuration parameters
Configuration Editor:
Configuration mode
Design
Enter recipe adjustment parameters
Configuration Editor:
Recipe/Adjustment mode
Program Editor
Programming.
Transfer application to
PLC memory
In connected mode:
Parameter adjustment
Adjustment and
Debugging
Debugging
Configuration Editor:
Adjustment mode or
Recipe/Adjustment mode
Configuration Editor:
Debugging mode
Documentation Editor
File editing
In connected
Operation
Operation
CCX 17
Note: the variables editor offers the Presymbolization function which automatically generates the symbols for the electronic cam module.
24
TLX DS 57 PL7 xx
Introduction to the electronic cam module
General ergonomics for the module implementation functions
Screen
1
The functions for implementing the module are accessed from the TSX CCY 1128 module’s hardware configuration screen.
TSX CCY 1128 IE 06 [RACK 0 POSITION 4]
Recipe adjustment
Designation: MOD.ELEC CAM. 128 CAMS
2
Symbol:
Function:
Electronic cam
Electronic cam
01
Acquisition
Cam processor
Parts counter
Connector0
Group0
Track0
Track1
Track2
Track3
Track4
Track5
Track6
Track7
Group1
Connector1
Task:
MAST
Adjustment parameters: Acquisition
Axis
No. of pulses/cycle:
Initial value:
256
256
Axis play value:
Initial value:
0
0 pulses
Recalibration
Value of the angle: 0
Initial value: 0 pulses
3
This table defines the different addresses:
Address Role
1 Drop-down list, allowing you to select the function for implementing the module.
2
3
Browser zone, displays and provides access to all the component parts of the cam processing.
Entry zone for entering parameters or commands (debugging screen).
TLX DS 57 PL7 xx
25
Introduction to the electronic cam module
Browser
Parameter entry
The browser for the electronic cam function presents the contents of an electronic cam application in a tree structure.
l l l l l l l
It can be used to navigate within the application, providing direct access to the parameter entry or debugging screens associated with the following functions:
Acquisition
Cam processor
Parts counter
Connectors
Groups
Tracks
Cams l l l l
The colors of the parameters in the entry fields have the following meanings:
Black: parameters which can be modified
Grayed out: parameters which cannot be modified
Blue: parameters which can be modified in adjust mode
Red: incorrect parameter value entered
26
TLX DS 57 PL7 xx
Types of applications
2
At a glance
Subject of this chapter
What's in this chapter?
This chapter describes the various fields and types of application an electronic cam can process.
This chapter contains the following topics:
Topic
Areas of application
Alternating movement
Use in alternating motion
Rotary movements
Use for Rotary Motion
Cyclic movements
Use for cyclic motion
Continuous movement
Use for continuous motion
Page
27
TLX DS 57 PL7 xx
Types of applications
Areas of application
Areas of
Application
The module manages high-speed machines autonomously.
The areas of application are: l l l l l
Mechanical or hydraulic presses,
Revolving transfer machines,
Transfer machines
Packaging machines,
Woodworking machines
The machines in these various areas are characterized according to the type of
movement performed by the machine axis.
28
TLX DS 57 PL7 xx
Types of applications
Alternating movement
Area
Example of an alternating axis
This is for revolving transfer machines and hydraulic presses.
The alternating movement of the axis is "to-and-fro".
The rotation speed can vary greatly during the machine cycle.
Outputs are positioned in both directions. The forward program can differ from the reverse program. There may be a prohibited zone defined as a protective zone
(brake control).
In this application, the encoder resolution is 4000 pulses per cycle. The permitted movement zone is 3992 pulses. Recalibration is performed at 90° of the mechanical origin (0) which is not accessible.
Prohibited zone
Work zone
(re)calibrating function
TLX DS 57 PL7 xx
29
Types of applications
Timing diagram of an output
Timing diagram
Prohibited zone
Outward
Return
Prohibited zone
30
TLX DS 57 PL7 xx
Types of applications
Use in alternating motion
Using the module
Anticipation
In this type of application, the user indicates the angular resolution. The number of counter pulses in 360° (a cycle), are indicated. The angle measurement will be done in the "0" to "resolution -1" interval with: l An incremental encoder, recalibrating the reading at the machine origin (cams reference) can be done with a value other than "0". Each time the machine is started up with an incremental encoder. At each machine cycle if the axis drive slips.
l With an absolute encoder, the module can correct the offset of the encoder on the machine 0. This type of encoder is perfectly suitable for this type of application if the drive does not slip.
The module can correct the error due to the axis play when the direction of movement is reversed.
Brake control can be programmed on an output to generate the protective function of the "prohibited zone".
The parts counter function can be programmed to indicate the number of cycles being run.
For high-speed machines, it is possible to correct the following very precisely: the actuator ascent time and the internal module processing time, if required.
A fine resolution and a large number of pulses per cycle, ensure precise anticipation.
For example: if the user wishes to anticipate the command of an actuator by 1ms, the encoder must be able to provide more than 5 pulses in that time. The speed must be stabilized before switching to the cam. This is particularly important after a reversal of the direction of rotation.
TLX DS 57 PL7 xx
31
Types of applications
Rotary movements
Area
Example of a rotating axis
This is for mechanical presses and packaging machines.
The main movement of the axis is in a single direction of rotation. The positioning of the outputs is the same for each cycle. Outputs can be activated between two cycles.
The linear speed is not necessarily constant during movement. The machine must stop within a precise zone.
Two types of encoders can be used, absolute or incremental. For drives with slip, it is preferable to use an incremental encoder.
A press cycle represents 2000 encoder pulses. Synchronization of the axis
(correction of slip) will start at 800 pulses in relation to the physical origin of the tools.
Recalibration is carried out systematically at each cycle.
Real angle value
Pulses
Encoder synchro
Output timing diagram
1 cycle
32
TLX DS 57 PL7 xx
Types of applications
Use for Rotary Motion
Using the module
Anticipation
For rotary movement, the user will indicate the number of pulses in a machine cycle.
l l
The cams can be declared for all the values of a cycle.
The activity zone of an output can be programmed between two cycles.
l l l
Recalibrating the position reading on the machine origin (cam reference) can be done with a value other than "0":
Each time the machine is started up,
On each machine cycle for drives with slip,
With an absolute encoder, the module can correct the offset on the machine 0. It can also apply an angle of deviation in relation to this same machine 0.
l l l
Module capture functions allow the following to be read:
The number of counter pulses in a cycle,
The axis slip (value of the angle before recalibration),
The angle that parts arrive at, or their dimensions.
The parts counter function can be programmed to indicate the number of presses performed.
For high-speed machines, it is possible to correct the following very precisely: the actuator ascent time and the internal module processing time, if required.
l A fine resolution and a large number of pulses per cycle, ensure precise anticipation. For example: if the user wishes to anticipate the command of an actuator by 1ms, the encoder must be able to provide more than 5 pulses in that time.
Caution: speed variation must be negligible in a period corresponding to the largest anticipation value requested.
TLX DS 57 PL7 xx
33
Types of applications
Cyclic movements
Area
Example of a cyclical axis
This is for packaging and bottling machines.
The main movement of the axis is in a single direction of rotation.
The linear speed is constant during movement, or varies slowly in relation to the machine rate. The positioning of the outputs is the same for each cycle.
Parts arrive periodically: l One part for each cycle. All the parts should enter systematically for the same position angle value in each cycle (mechanical problem).
l l
There can be active cams on several cycles.
Certain grouping operations, for example, may be performed in a single cycle
(one cycle in 4, for example).
In this type of application, recipe means a usage value. The recipe groups together the data required for the module to control the machine for a series of parts. The recipe can be modified or completely changed by the PLC application.
Two types of absolute encoder can be used, single-turn or multi-turn. The number of turns is not necessarily a power of 2.
A cycle is made up of 1024 pulses and corresponds to the distance between two parts. The complete machine cycle is performed over 8 cycles. The start of the cycle
(arrival of the part) is offset by 50 pulses in relation to the machine 0.
34
TLX DS 57 PL7 xx
TLX DS 57 PL7 xx
Reflex operations on parts:
Types of applications
> < 50 pulses
Point 0 of the machine is defined when the tool box and the conveyor are synchronized (indexes facing).
35
Types of applications
Use for cyclic motion
Using the Module For cyclic movement, the user indicates the resolution in a basic cycle and the number of turns per machine cycle.
The number of encoder pulses for a cycle (up to 32767) will be indicated; the position reading will be taken in the range ["0" to "resolution -1"].
The number of cycles per machine cycle (up to 32767) will also be indicated.
The cycle number value will be set in the range ["0" to "No. of cycles -1"].
The angle reading and the reading of the number of cycles can be (re)calibrated, independently or simultaneously, on the machine 0 position: l l l l l
When a machine is debugged (with an absolute encoder).
Each time the machine is started up (with an incremental encoder).
The cams used can be declared for all the values of a cycle.
The activity zone of an output can be programmed between two cycles.
From one series to the next, the parts may arrive at different angles.
It is possible to adjust the angle at which the parts arrive in the periodical process without modifying either (re)calibration on position 0 of the machine or the whole cam program in the absolute encoder.
It is possible to construct a cam profile that reacts with good precision over several cycles.
Option to force the cam output using the application program.
Cycle 0 Cycle 1 Cycle 2 Cycle 3
Cam
Forcing bit
Real status of the output
The use of an event cam is recommended in this case.
The "parts counter" function can be programmed to indicate the number of parts completed or to enable the action of a cam once a certain number of parts is reached.
The module can indicate the linear speed of the axis.
It can also provide the number of counter pulses in a cycle (only when using an incremental encoder).
The "slow shaft detection" function can be obtained on a track associated to a time delay cam.
36
TLX DS 57 PL7 xx
Anticipation
Types of applications
For high-speed machines, it is possible to correct the following very precisely: the actuator ascent time and the internal module processing time, if required.
A fine resolution and a large number of pulses per cycle ensure precise anticipation.
For example: if the use wishes to anticipate the command of an actuator by 1ms, the encoder must be able to provide more than 5 pulses in that time.
TLX DS 57 PL7 xx
37
Types of applications
Continuous movement
Area
Machines that set a reference point on 1 part
Example
Continuous movement is for packaging machines, conveyors, tool boxes
(woodworking machines, for example).
The main movement of the axis is in a single direction of rotation.
The machine operates continuously and drives an incremental encoder.
The linear speed is constant during operation or varies slowly in relation to the machine rate.
Parts arrive on the machine randomly, but they are all processed in the same way.
There must be a sensor that sets a reference point for each part as it arrives.
The process operates on one part at a time (one station).
The reflex functions are finished before the next part arrives. The reference point for each part is set by recalibrating the current value.
The position value is recalibrated to 0.
The dimension of each tool is an absolute valu
Recalibrating the current value
Conveyor
The work area is less than 32767 pulses. The position value remains outside the work zone until adjustment.
Actual recalibration value
Cam program work zone
38
TLX DS 57 PL7 xx
Types of applications
Use for continuous motion
Use
Anticipation
The position reading has a fixed dynamic of 32768. Programming the cams is done in this group of pulses.
Example: a 16 m belt with an encoder resolution of 0.5 mm.
Counter recalibration must be configured on the rising edge on Irec. The recalibration value can be adjusted with a value other than 0.
The length of the part can be measured using the capture functions.
l l
The application of events can be used, for example, to: set the processor cam to Run after recalibration (movement of parts).
set the cam processor to Stop on recalibration if processing of a part has not finished.
For high-speed machines, it is possible to correct the following very precisely: the actuator ascent time and the internal module processing time, if required.
A fine resolution and a large number of pulses per cycle, ensure precise anticipation.
For example: if the user wishes to anticipate the command of an actuator by 1ms, the encoder must be able to provide more than 5 pulses in that time.
TLX DS 57 PL7 xx
39
Types of applications
40
TLX DS 57 PL7 xx
Examples
3
At a glance
Subject of this chapter
What's in this chapter?
This chapter presents two examples of using the TSX CCY 1128 electronic cam module. The simple example shows the elementary programming required to actuate an output on detection of a cam. The advanced example implements several cams with generation of events when switching modulo and full counters with production recipe management. They will enable you to implement a cam module quickly.
This chapter contains the following Sections:
Section
3.1
3.2
Topic
Simple example
Advanced example
Page
41
TLX DS 57 PL7 xx
Examples
42
TLX DS 57 PL7 xx
Examples
3.1
Simple example
At a glance
Subject of this section
What's in this section?
This section deals with the following subjects:
This section contains the following topics:
Topic
Introduction to a simple example
Entering configuration parameters
Programming
Page
TLX DS 57 PL7 xx
43
Examples
Introduction to a simple example
Example This is the implementation of an output on detection of a cam. The axis used is a type 1 rotating axis.
Recalibration
The electronic cam is set between 200 and 500. It activates output 0 on track 0.
44
TLX DS 57 PL7 xx
Examples
Entering configuration parameters
Hardware configuration
The hardware configuration is as follows:
0
0
5
5
P
S
Y
1
T
S
X
2
0
5
7
2
V3.3
2 3
C
C
Y
2
8
1
1
4
Note: This is implemented using PL7 Junior or Pro software (software version > or
= 3.4) and the PL7 software enhancement patch.
Procedure The steps are as follows:
Step
1
Action l l
Select the TSX CCY 1128 module at its position n°3 in rack n°0.
Double-click on the module.
Result: the module hardware configuration screen appears:
TSX CCY 1128 V1.0 IE 22 [RACK 0 POSITION 3]
Configuration
Designation: MOD.ELEC CAM. 128 CAMS
Symbol:
Function:
Electronic cam
Electronic cam
Acquisition
01 Cam processor
Connector0
Connector1
Task:
MAST
2
3
The drop-down list at the top should be in Configuration.
l Double-click with the left button on Acquisition in the browser
Select l l l l
For the Input interface: Incremental encoder.
For the Measurement Format: Type 1.
For the position Recalibration on Irec: Short cam
Enable with the toolbar button.
TLX DS 57 PL7 xx
45
Examples
Step
4
5
6
7
8
Action l l l l l l l l l l l l l l l l l l
Select Adjust Recipe from the drop-down list at the top of the screen.
Double-click with the left button on Acquisition in the Browser.
Enable with the toolbar button.
Configure 1024 for No. of pulses/cycle.
Select Configuration from the drop-down list at the top of the screen.
Confirm with yes.
Click with the right button on Connector 0.
Unlock.
Select Adjust Recipe from the drop-down list at the top of the screen.
Confirm with yes.
Double-click with the left button on Connector 0.
Double-click with the left button on Group 0.
Click with the right button on track 0.
Activate.
Click with the right button on track 0.
Create Cam ...
Select 0.
Confirm with OK.
l Double-click with the left button on cam 0.
Result: the adjustment parameters screen appears
Adjustment parameters: Cam processor . Connector0 . Group0 . Track0 . Cam0
Cam definition
Type: Position
Initial value: Position
Threshold X1:
Initial value:
0
200 pulses pulses Threshold X2:
Initial value:
Closing delay
Initial value:
0
0
0
500
*0.1 ms
Confirmation condition
Cam monitoring:
Initial value:
Confirmation bit number:
Initial value:
Conditioned by a confirmation bit
Activation condition
Forward direction
Reverse direction
Conditioned by a confirmation bit
0
0
Initial value
Initial value
46
TLX DS 57 PL7 xx
Step
9
Action
Configure l l for ThresholdX1:200, and for ThresholdX2: 500
Select l for Cam monitoring (in the Enable conditions): Conditioned by an confirmation bit l for the Activation condition: Forward
Enable the configuration entered with the toolbar button.
Examples
TLX DS 57 PL7 xx
47
Examples
Programming
Introduction
Grafcet
The module calculates the position reading from an incremental encoder connected to its inputs. The module controls its outputs according to this position and on the transferred cam program which describes the recipe.
This program contains the minimum number of steps required to ensure that the cam function starts up correctly. For each step, it is sufficient to set the required commands to 1 to activate the output.
This illustration describes an example of Grafcet.
0
1
2
(* Start cycle *)
(* Initializing the module *)
(* Errors? *)
(* Recalibration request *)
(* Counter recalibrated? *)
(Switch to RUN mode*)
3
4
(* Cam processor running?*)
(* Cam confirmation *)
%X(0)->%X(1) (* start cycle?*)
%M0
48
TLX DS 57 PL7 xx
CHART %X1 P1
%X(1)->%X(2)
CHART %X2 P1
%X(2)->%X(3)
CHART %X3 P1
%X(3)->%X(4)
CHART %X4 P1
(* Initializing enable and assignment parameters *)
(* assigning track 0 to output 0 *)
%QW3.0.1:=16#0001;
(* Enabling group 0 outputs *)
SET %Q3.0.25;
(* Reset faults *)
SET %Q3.0.15;
(* fault? *)
NOT %I3.0.ERR
(* Enabling angle recalibration function *)
SET %Q3.0.0;
(* Counter recalibrated? *)
%I3.0.0
(* setting the cam processor to run *)
SET %Q3.0.5;
(* cam processor in RUN? *)
%I3.0.3
(* enabling cam *)
SET %QW3.0:X0;
Examples
TLX DS 57 PL7 xx
49
Examples
Variables used
Address
%M0
%I3.0.Err
%I3.0.0
%I3.0.3
%Q3.0.0
%Q3.0.5
%Q3.0.15
%Q3.0.25
%QW3.0.1
%QW3.0:X0
Symbol
Dcy
CH_ERROR
ANG_OK
PCAM_ON
PRESET_ANG_EN
ABLE
PCAM_START_ST
OP
ACK_FLT
OUTS_ENABLE
Comments
Start cycle
Channel error bit
Valid Angle reading
Cam processor RUN/STOP
Enables (re)calibration function on angle value only
Set: Cam processor Start / Cam processor
Reset:Stop
Acknowledge present faults command
Global enabling of track outputs
GROUP0_AND_BIT
S
8 bits for assigning tracks to group outputs
GROUP0_OR_BITS enabling cam
50
TLX DS 57 PL7 xx
Examples
3.2
Advanced example
At a glance
Subject of this section
What's in this section?
This section deals with the following subjects:
This section contains the following topics:
Topic
Introduction to a detailed example
Operating mode
The Recipes
Entering configuration parameters
Programming
Special Features
Page
TLX DS 57 PL7 xx
51
Examples
Introduction to a detailed example
General An automatic device controls the filling and storage of boxes of medicine. During filling, each box is wedged into a mechanical stop. Once they have been filled, the boxes are stored in lots of 5. Each lot is then sent to the storage area.
Illustration of automatic device
Note: This example is given for information only and is not an exact representation of an industrial application.
52
TLX DS 57 PL7 xx
Cycle 1
Cycle 2
Cycle 3
Cycle 4
Description of the cycles
Examples
The machine is divided into 6 cycles of 1024 pulses: l l
5 filling cycles consisting of depositing the medicine into the box,
1 storage and grouping cycle.
The parts counter counts the parts to be grouped for entry to the storage area. If the storage area is full, grouping is transferred.
The application program manages the transient machine loading and unloading phases. During loading, the stations are activated one at a time according to the cycle number.
When the machine is fully loaded, all stations work in parallel during each cycle.
Filling the machine track 0 track 1 station 1 station 2 track 2 station 3 track 3 station 4 track 4 station 5 forward motion of the belt
Clearing track 5 station 6 track 6 station 7
Cycle 5
Cycle 6
5 times...
... parts counter increment
Grouping
Stations 1 to 5 are controlled by the outputs of tracks 0 to 4 and only have one output per cycle (1 cam). Track 5 performs operations on the indexer for station 6, track 6 performs operations on the grouping actuator at station 7.
TLX DS 57 PL7 xx
53
Examples
Operating mode
Start-up l l l l
Recalibration is performed before every start-up.
The machine is started gradually according to the arrival of the boxes.
The parts counter is incremented for every full box. When this counter equals 5, l l the collected batch is pushed towards the packaging area.
managing 2 types of stop: a controlled stop to empty the string of boxes in progress.
an immediate stop.
54
TLX DS 57 PL7 xx
Examples
The Recipes
At a glance Two recipes are managed. These recipes are stored in the following %MW words:
Recipe 1 %MW100 to %MW816
Recipe 2 %MW850 to %MW1566
Parameters for recipe 1
This table describes the parameters for recipe 1:
Track
Track 0
Track 1
Track 2
Cam
Cam 0
Cam 1
Cam 2
Positions position X1=800 X2=820 position X1=600 X2=620 position X1=400 X2=420
Direction
Forward
Forward
Forward
Track 3
Track 4
Track 5
Track 6
Cam 3
Cam 4
Cam 5
Cam 6 position X1=200 X2=220 position X1=0 X2=20 position X1=800 X2=900
Forward
Forward
Forward position X1=200 Tempo 100 ms Forward
The parts counter is incremented by track 5.
The parts counter is reset by track 6.
Enabling enable by bit:0 enable by bit:1 enable by bit:2 enable by bit:3 enable by bit:4 enable by bit:5 full counter
Parameters for recipe 2
This table describes the parameters for recipe 2:
Track
Track 0
Track 1
Track 2
Cam
Cam 0
Cam 1
Cam 2
Positions position X1=800 X2=900 position X1=600 X2=700 position X1=400 X2=500
Direction
Forward
Forward
Forward
Track 3
Track 4
Track 5
Track 6
Cam 3
Cam 4
Cam 5
Cam 6 position X1=200 X2=300 position X1=0 X2=100 position X1=800 X2=900
Forward
Forward
Forward position X1=200 Tempo 100 ms Forward
The parts counter is incremented by track 5.
The parts counter is reset by track 6.
Enabling enable by bit:0 enable by bit:1 enable by bit:2 enable by bit:3 enable by bit:4 enable by bit:5 full counter
TLX DS 57 PL7 xx
55
Examples
Entering configuration parameters
Hardware configuration
The hardware configuration is as follows:
0
0
5
5
P
S
Y
1
T
S
X
2
0
5
7
2
V3.3
2 3
C
C
Y
2
8
1
1
4
Note: This is implemented using PL7 Junior or Pro software (software version > or
= 3.4) and the PL7 software enhancement patch.
Procedure Entering the axis configuration and adjustment parameters is the same as for the simple example.
56
TLX DS 57 PL7 xx
Examples
Programming
Introduction
MAST-PRL
The module calculates the position reading from an incremental encoder connected to its inputs. The module controls its outputs according to this position and the transferred cam program which describes the recipe.
(* Initializing Grafcet *)
IF NOT %M0 THEN SET %S21;
END_IF;
(* immediate cycle stop *)
IF %M3 THEN SET %S21;RESET %Q3.0.5;%QW3.0:=0;RESET %M3;RESET
%M0;
END_IF;
(* Power outage management *)
IF %S1 THEN SET %S21;RESET %Q3.0.5;%QW3.0:=0;RESET %Q3.0.25;
END_IF;
(* Recipe management *)
(* saving recipe 1 in words %mw100 onwards *)
IF %M11 THEN TRF_RECIPE %CH3.0(1,100);RESET %M11
END_IF;
(* Saving recipe 2 in words %MW850 onwards *)
IF %M12 THEN TRF_RECIPE %CH3.0(1,850);RESET %M12;
END_IF;
(* Restoring recipe 1 from the %MW100 word *)
IF %M13 THEN TRF_RECIPE %CH3.0(0,100);RESET %M13;RESET
%Q3.0.5;
END_IF;
(* Restoring recipe 2 from the %mw850 word *)
IF %M14 THEN TRF_RECIPE %CH3.0(0,850);RESET %M14;RESET
%Q3.0.5;
END_IF;
(* restoring the recipe switches the Cam processor to STOP and so the command must be reset to zero *)
TLX DS 57 PL7 xx
57
Examples
Grafcet This illustration describes an example of Grafcet.
0
1
2
(* Start cycle *)
(* Initializing the module *)
(* Errors? *)
(* Recalibration request *)
(* Counter recalibrated? *)
(* Switch cam processor to RUN mode *)
3
4
(* Cam processor running*)
(* Machine running *)
%X(0)->%X(1)
CHART %X1 P1
%X(1)->%X(2)
(* start cycle? *)
%M0
(* Initializing enable and assignment parameters *)
(* assigning tracks to GRP outputs '7 tracks / 7 outputs' *)
%QW3.0.1:=16#007F;
(* Reset parts counter *)
SET %Q3.0.23;
(* Authorization to control group 0 outputs *)
SET %Q3.0.25;
(* Event authorization when switching to angle modulo *)
SET %Q3.0.8;
(* Fault acknowledgement during start-up phase *)
SET %Q3.0.15;
(* Fault? *)
NOT %I3.0.ERR;
58
TLX DS 57 PL7 xx
CHART %X2 P1
CHART %X2 P0
%X(2)->%X(3)
CHART %X3 P1
%X(3)->%X(4)
CHART %X4 P1
MAST-POST
(* Type 1 function therefore recalibrate angle *)
SET %Q3.0.0;
(* Reset recalibration *)
RESET %Q3.0.0;
(* Counter recalibrated? *)
%I3.0;
(*Setting the cam processor to run *)
SET %Q3.0.5;
(* Cam processor in RUN? *)
%I3.0.3;
(* Enabling parts counter *)
RESET %Q3.0.23;
SET %Q3.0.7;
(* Managing faults *)
IF %I3.0.ERR THEN SET %S21; END_IF;
(* Fault acknowledgement *)
IF %M1 THEN SET %Q3.0.15;RESET %M1;
ELSE RESET %Q3.0.15;END_IF;
(* Reading fault type *)
IF %M2 THEN READ_STS %CH3.0;RESET %M2;END_IF;
Examples
TLX DS 57 PL7 xx
59
Examples
EVENT-EVT1 (* Managing cycle modulo for starting *)
(* Detecting angle number modulos *)
IF %IW3.0.12:X0 AND %M0 THEN INC %MW0;END_IF;
(* Action on detection of cycle modulos, enabling cams *)
IF(%MW0=1)AND %M0 THEN SET %QW3.0:X1;END_IF;
IF(%MW0=2)AND %M0 THEN SET %QW3.0:X2;END_IF;
IF(%MW0=3)AND %M0 THEN SET %QW3.0:X3;END_IF;
IF(%MW0=4)AND %M0 THEN SET %QW3.0:X4;END_IF;
IF(%MW0=5)AND %M0 THEN SET %QW3.0:X5;END_IF;
IF(%MW0>6)AND %M0 THEN %MW0:=6;END_IF;
(* Managing cycle modulos for stopping *)
(* Detecting angle number modulos *)
IF %IW3.0.12:X0 AND NOT %M0 THEN DEC %MW0;END_IF;
(* Action on detection of cycle modulos, disabling cams *)
IF(%MW0=5)AND NOT %M0 THEN RESET %QW3.0:X0;END_IF;
IF(%MW0=4)AND NOT %M0 THEN RESET %QW3.0:X1;END_IF;
IF(%MW0=3)AND NOT %M0 THEN RESET %QW3.0:X2;END_IF;
IF(%MW0=2)AND NOT %M0 THEN RESET %QW3.0:X3;END_IF;
IF(%MW0=1)AND NOT %M0 THEN RESET %QW3.0:X4;END_IF;
IF(%MW0=0)AND NOT %M0 THEN RESET %QW3.0:X5;END_IF;
IF(%MW0<1)AND NOT %M0 THEN %MW0:=0;END_IF;
(* Managing event stack overflow on cam card *)
(* Detecting overflow *)
IF %IW3.0.12:X15 THEN SET %M15;END_IF;
60
TLX DS 57 PL7 xx
Variables used
Examples
Table
Address
%M0
%M1
%M2
%M3
%M5
%M11
%M12
Symbol
Dcy
ACK_DEF
READ_DEF
STOP_IMM
COMP_PLEIN
SAVE_RECIPE1
SAVE_RECIPE2
%M13
%M14
RESTORE_RECIPE1
RESTORE_RECIPE2
%M15
%MW0
%MW2
%I3.0.Err
%I3.0
%I3.0.3
%IW3.0
COMP_MODULO_ANG
COMP_COMP_PIECES
CH_ERROR
ANG_OK
PCAM_ON
GROUP0_STRACK
%IW3.0.12:X0 EVT_ANG
%IW3.0.12:X6 EVT_PIECES_FULL
Comment
Start cycle
Fault acknowledgement
Reading fault
Immediate stop of the machine
Saving Recipe 1
Saving Recipe 2
Restoring Recipe 1
Restoring Recipe 2
Detecting overflow
Evt. modulo counter
%IW3.0.12:X15
%Q3.0.0
%Q3.0.5
%Q3.0.7
%Q3.0.8
%Q3.0.14
%Q3.0.15
%Q3.0.23
%Q3.0.25
%QW3.0
%QW3.0.1
DIRECTION_EVT
PRESET_ANG_ENABLE
PCAM_START_STOP
Channel error bit
Valid angle reading
Cam processor RUN/STOP
Status of tracks i.0 to i.7
Switch to angle value modulo event
Switching to limit value for the parts counter event
Direction of movement on ANG_EVT or
TURN_EVT
Enables (re)calibration function on angle value only
Set: Cam processor start / Cam processor
Reset:Stop
PIECES_ENABLE
EVT_ANG_ENABLE
Enables the Parts counter function
Enables the ANG_EVT event source
EVT_PIECE_FULL_ENABLE Enables the PIECES_FULL_EVT event source
CAME_ACK_FLT
CAME_PIECES_RESET
Command to acknowledge present faults
Reset parts counter
CAME_ENAB_OUTS Global enabling of track outputs
GROUP0_ENABLE_BITS_0 8 enable bits associated with the group
GROUP0_AND_BITS_0 8 bits for assigning tracks to group outputs
TLX DS 57 PL7 xx
61
Examples
Special Features
Managing the box counter reset
%MW for the recipes
Saving the recipes
When the box counter is full, cam 6 is active.
In the example, the counter full reset is performed on activation of cam 6.
This function can only be used if the cam is a Monostable type.
Note: If the cam is not a monostable type it will set and reset immediately.
The parts counter can also be reset to zero by: l the application, but pay particular attention to any problems between tasks: Do not reset the counter before cam execution.
l by a dummy cam.
The recipes use 716 %MW words.
This zone must not be used by the system.
To be able to save the various recipes, use a paginated PCMCIA.
62
TLX DS 57 PL7 xx
Configuration of the electronic cam module
4
At a glance
Subject of this chapter
What's in this chapter?
This chapter describes the configuration operations for the TSX CCY 1128 electronic cam module.
This chapter contains the following topics:
Topic
Declaring the module in the PLC rack
Accessing the module configuration parameters
Configuring the electronic cam parameters
Configuring acquisition parameters
Configuring an incremental encoder
Configuration of an absolute encoder
Reading format configuration
Configuring the position recalibration function for incremental encoders
Capture function configuration
Cam processor configuration
Connector configuration
Confirmation of the configuration
Reconfiguration in connected mode
Page
TLX DS 57 PL7 xx
63
Configuration of the electronic cam module
Declaring the module in the PLC rack
Procedure This operation is used to declare the software equivalent of the electronic cam module in a TSX 57 PLC rack.
Step
1
Action l l
In the application browser, select and click on the Station and
Configuration folders one after the other.
Double-click on the Hardware configuration icon.
Application Browser
2
3
Structure View
STATION
Configuration
Hardware configuration
Software configuration
Program
MAST task
Events
DFB types
Variables
Animation tables
File
Operating screens
If the application browser is not displayed: l l click on the application browser icon or select the Tools
→
Application Browser command
Double-click on the slot in which the module is to be configured
Select the Counting family from the Family list, then the module reference from the Module list.
Adding a module
Family:
Analog 1.5
Communication 1.5
Counting
Remote BusX
Movement
Weighing
Modeling
All or Nothing
1.5
1.0
1.5
1.7
1.0
1.5
Module:
TSX CCY 1128 MOD.ELEC.CAM 128 CAMS
TSX CTY 2A COUNT.MOD. 2 CHANNELS 40KHZ
TSX CTY 2C COUNT.MEASURE.MOD 2
CHANNELS
TSX CTY 4A COUNT.MOD. 4 CHANNELS 40KHZ
OK
Cancel
64
TLX DS 57 PL7 xx
TLX DS 57 PL7 xx
Step
4
Configuration of the electronic cam module
Action
Click on OK,
Result:
The module is declared in its slot. The slot is grayed out and contains the module reference.
Configuration
TSX 57452 V3.3 … XMWI
XTI..
0
0
0
2
6
P
S
Y
0
4
5
5
7
2
T
S
X
1
2 3 4 5
2
8
1
1
C
C
Y
6
65
Configuration of the electronic cam module
Accessing the module configuration parameters
Role
Procedure
This operation is used to access the configuration parameters of the TSXCCY1128 module.
In connected mode, the parameters: task, event, masking faults, encoder and encoder configuration cannot be modified. Confirming any modification causes the cam function to stop (Cam processor in Stop mode).
The following table describes the operations to be performed:
Step
1
2
Action
Access the hardware configuration screen
Double-click on the slot of the module in the rack.
Result:
TSX CCY 1128 [RACK 0 POSITION 5]
Configuration
Designation: MOD.ELEC CAM. 128 CAMS
Symbol:
Function:
Electronic cam
Electronic cam
Acquisition
01 Cam processor
Connector0
Connector1
Task:
MAST:
3
4
Select the task (MAST or FAST) in which the module language objects are updated in the PLC processor: Task pull-down menu.
In the Browser, double-click on the element to be configured.
l l l l
Electronic cam
Acquisition
Cam processor
Connector 0 or 1 after unlocking
66
TLX DS 57 PL7 xx
Configuration of the electronic cam module
Configuring the electronic cam parameters
Role
Procedure
This operation is used to: l l declare an event task associated to the module mask all or some of the application faults
The following table describes the operations to be performed:
Step
1
Action
In the browser, double-click on Electronic cam.
Result:
Configuration parameters:
Event
EVI 1
Errors
Masking
2
3
If an event task in the PLC processor must be assigned to the module: l l click in the EVT check box, select the number of the associated Event task, from 0 to 63 (0 being the priority task).
Masking a fault prevents the fault indication being taken into account in the general channel fault information. The associated check remains active, however, and affects the operating modes of the module.
To mask the faults: click on the Mask button.
Result:
Errors
Encoder supply fault
Auxiliary inputs supply fault
Track outputs supply fault
Masking
Confirm Cancel
Check the box(es) of the faults which are to be masked and confirm.
TLX DS 57 PL7 xx
67
Configuration of the electronic cam module
Configuring acquisition parameters
Role l l
Configuring acquisition parameters allows you to: select the type of encoder (incremental or absolute) and define its characteristics select the acquisition mode functions l l
Reading format
Recalibration l l
Capture
Unit of speed
Procedure
Step
1
The following table describes the operations to be performed:
Action
In the browser, double-click on Acquisition.
Result:
Configuration parameters: Acquisition
Input interface
Incremental encoder Configuration
Acquisition mode
Measurement format
Type:
Type 1
A cycle:
Synchro type:
Position recalibration on Irec:
Type:
Irec rising edge
8..15 bits
Machine
Application:
Application:
Captures:
Capt0 on the falling edge of Icapt 0 and Capt1 on the falling edge of Icapt 0
Unit of speed: in pulses/ms
Part detection
2 Select the field to be modified
68
TLX DS 57 PL7 xx
Configuration of the electronic cam module
Configuring an incremental encoder
Role
Procedure
Configuring an incremental encoder allows you to: l l declare that the inputs are connected to an incremental encoder, define the processing characteristics of the encoder signals.
The following table describes the operations to be performed:
Step
1
2
Action
Select Incremental encoder in the input Interface field in the Acquisition configuration screen.
Click on Configuration to display the following dialogue box:
Details of input interface
Input interface: INCREMENTAL ENCODER
Filtering:
125 kHz x 1 / 125 kHz x 4
Measurement inversion Line monitoring
Multiplication
By 1 By 4
Confirm Cancel
3
4
5
6
7
Select the counter input filtering according to the maximum frequency supplied by the encoder: l 125 kHz x1 / 125 kHz x4 enables good running for frequencies lower than
125 kHz in input (with or without multiplication by 4), l 500 kHz x1 / 250 kHz x4 corresponds to the module's limit values.
If necessary, check the Reading inversion function box.
This parameter defines the direction in which the measurement changes in relation to the direction of the encoder rotation.
If necessary, enable the Line check function.
This function indicates any electrical faults (line break or short-circuit) on the links with the RS422 encoder.
This function must not be used with an encoder with 10...30V Totem pole outputs.
Select multiplication by 1 or by 4.
Multiplication by 4 gives a resolution 4 times greater than the resolution of the encoder.
Click on OK to confirm the choices made.
TLX DS 57 PL7 xx
69
Configuration of the electronic cam module
Configuration of an absolute encoder
Role
Procedure
Configuring an absolute encoder enables you to: l declare that the inputs are connected to an absolute SSI encoder or to an absolute encoder with parallel outputs.
l define the characteristics of the encoder and the SSI frame
The following table describes the operations to be performed:
Step
1
2
Action
Select SSI absolute encoder or Parallel output absolute encoder in the
Input interface field on the Acquisition configuration screen.
Click on Configuration... to display the following dialogue box:
Details of input interface
Input interface:
Encoder
Binary
SSI frame
Period
Header
50us
No. of header bits:
Absolute SSI encoder
Gray code
SSI frequency
0
Measurement inversion
1 MBaud
Status
Line monitoring
No. of status bits: 0
Error bit Data
No. of encoder data bits: 8
Parity
Parity bits
Frame: x8x
Confirm Cancel
3
4
Select the type of coding used by the encoder: Binary or Gray code.
If necessary, check the Reading inversion function box.
This function modifies the value provided by the encoder in order to reverse the movement direction of the position.
70
TLX DS 57 PL7 xx
TLX DS 57 PL7 xx
Step
5
Configuration of the electronic cam module
Action
Adjust the interrogation interval of the encoder according to the length of the frame and the length of the cable connecting the encoder. The module automatically determines the transmission frequency.
The diagram below can be used to select the optimum period; the value in brackets gives the transmission frequency determined by the module.
Frame length
Cable length
71
Configuration of the electronic cam module
Step
6
7
Action
For an SSI absolute encoder: l l l l l l l
Set the SSI frame characteristics used by the encoder: l number of insignificant bits on the frame header N mini = 0, N maxi = 4 (0 is the default) number of encoder data bits: N min. = 8, N max. = 25, (8 is the default) number of status bits N maxi = 3 (0 is the default), number of bits sent after the last data bit excluding the parity bit, presence or absence of the error bit (if the status field is not zero), setting of the error bit (Rank from 1 to 3) in the status bits zone, logical level of the error bit (active at 0 or active at 1), presence of the parity bit (by default it is absent) and the type of parity:
Even or Odd (odd parity is not checked by the module).
Note: Number of header + data + status bits < or = 32
As the selections are made, the frame zone displays the elements of the frame.
Example: Frame: xxxx x8x xxE P xxxx = 4 header bits (one cross per header bit) x8x = 8 data bits xxE = 3 status bits, one of which is an error bit positioned at rank 1
P = presence of parity bit, parity type: Even.
For a parallel output absolute encoder:
Set the characteristics of the SSI frame used by the encoder bearing in mind that the following values are set as standard: l l l l l number of insignificant frame header bits: 0 number of encoder data bits: 24 number of status bits: 3 rank of error bit: 3 if error bit present presence of the parity bit and type of Even parity
Click on Confirm to confirm the choices made.
72
TLX DS 57 PL7 xx
Configuration of the electronic cam module
Reading format configuration
Role of the parameter
Parameter selection
This parameter defines the format for the axis position reading, calculated by the module.
The format is chosen according to the type of movement.
The following table can be used to select the format type (1, 2 or 3) depending on the type of application.
Type 1 Type 2 Type 3
Type of movement rotary and alternating
Position reading angular cyclic continuous
Format
Synchro
8..15 bits (cycle) for incremental
8..14 bits for absolute machine
Type of encoder incremental or absolute angular
+ number of turns counting the number of pulses
8..15 bits (cycle) for incremental
8..14 bits for absolute
1..15 bits (turn)
15 bits (cycle) ie. 32768 pulses machine incremental or absolute parts detection incremental
The choice is made via a pull-down menu. The other fields are for information only.
TLX DS 57 PL7 xx
73
Configuration of the electronic cam module
Configuring the position recalibration function for incremental encoders
Role of recalibration
Procedure
For a synchro...
Part
This is the module function which is used to calibrate the axis in relation to the machine zero or to synchronize the axis in relation to the entry of a part.
Recalibration forces the position reading to a value which is predefined by the
"recalibration value" parameter (within the pulse field of the cycle).
This function is used to compensate for any possible slip in the reading. It is applied to the incremental encoders. Each time the moving part passes in front of the detector (wired to the Irec recalibration input), the reading is recalibrated.
The configuration operation of the recalibration function consists of defining the type of signal detected on the Irec recalibration input.
The type of recalibration is selected using a pull-down menu:
If you want recalibration on detection… then select...
l of a rising edge on the module Irec input Irec rising edge
Machine without turn pulse marker l l of a rising edge in forward movement of a falling edge in reverse movement on the module Irec input.
Rising edge +direction, falling edge -direction
Machine with turn pulse marker l l of a rising edge in forward movement of a falling edge in reverse movement on the Zero Pulse Marker input when the
Irec input is at 1.
short Cam
Zero
Irec
74
TLX DS 57 PL7 xx
Configuration of the electronic cam module
Capture function configuration
Role of the capture function
This function is used to sample the value of the position of the axis on detection of an event. The capture function has no impact on the axis values, nor on the cam processor.
Implementing this function enables the application to manage the process better, for example control of: the number of pulses sent by the encoder, the size of the parts, the slip of the axis, the entry angle of the parts.
l l
The module has:
2 physical capture inputs Icapt0 and Icapt1,
4 register words that can be accessed via the sequential program: l 0 Registers: always store the actual position value of the angle (CAPT0_ANG) and the number of turns (CAPT0_TURN). The capture function always operates on detection of a rising input front Icapt0.
l 1 Registers: the values captured in these registers (CAPT1_ANG and
CAPT1_TURN) depend on the type of capture requested (see table below).
Procedure The type of capture is chosen via a pull-down menu (only the first 2 choices can be accessed for an absolute encoder):
If you require capture on detection of a rising edge on the Icapt0 input
(for 0 registers) and ...
a falling edge on the Icapt0 input (for 1 registers)
(E.g.: measure the size of the parts, in comparison with 0 registers) a rising edge on the Icapt1 input (for 1 registers)
(E.g.: measure the entry angle of the parts) storage of the number of pulses in the 1 registers on each encoder turn (E.g.: to check the encoder link) capturing the value of the angle before recalibration in the 1 registers
(E.g.: to evaluate the deviation due to the slip and corrected by the recalibration) then select...
Capt1 on falling edge of Icapt0.
Capt1 on rising edge of Icapt1.
Capt1 = Number of pulses per encoder turn.
Capt1 before recalibration.
of a rising edge on zero pulse marker input (for 1 registers)
(E.g.: to evaluate the deviation due to the slip, without recalibrating the axis)
Capt1 on rising edge of zero marker
TLX DS 57 PL7 xx
75
Configuration of the electronic cam module
Cam processor configuration
Role
Procedure
This operation defines the cam processor performance and the module outputs on a fault.
The following table describes the operations to be performed:
Step
1
Action
In the browser, double click on Cam processor.
Result:
Configuration parameters: Cam processor
Reactivation of track outputs
Manual
Automatic
On faults in …
... communication
Stand-alone processor
Retention of direct commands
... short-circuit
Ignored by the processor
2
3
4
Select the type of output reactivation: Manual or Automatic.
When an overcurrent is detected on an output, it is tripped, and it can be reactivated: l l
Manually: it can be done from the debugging screen or via the application.
Automatically: performed automatically, 10 seconds after tripping.
Select the performance of the cam processor module on a communication fault between the PLC processor and the electronic cam module, see table below.
Select the behavior of the cam processor on a short-circuit fault: l box not checked or default selection: the cam processor is stopped if an output becomes faulty.
l ignored by the processor: tripping one of the track outputs does not stop the cam processor.
76
TLX DS 57 PL7 xx
Performance of the module on a communication fault
Configuration of the electronic cam module
The performance of the module on a communication fault between the PLC processor and the electronic cam module is summarized in the following table:
Check boxes selected
Cam processor status
None
Retention of direct commands change to stop
Stand-alone processor normal operation,
(remains in RUN) change to stop
Stand-alone processor and Retention of direct commands normal operation,
(remains in RUN)
State of the logic outputs set to 0 set to 0 equal to the last direct commands transmitted by the PLC processor; or logic between: l the status of the associated tracks (or the reverse if an inversion is l requested in the adjustment parameter) the last direct commands transmitted by the PLC processor
The actual state of a physical output is equal to the logic state of the output, or its reverse if inversion has been requested in the connector configuration.
TLX DS 57 PL7 xx
77
Configuration of the electronic cam module
Connector configuration
Role
Procedure
The logic state of the tracks is assigned to the physical outputs of the module.
l l
The configuration of the connectors enables the inverse state to be electrically applied to an output:
24 V for a 0 state,
0 V for a 1 state.
The following table describes the operations to be performed:
Step
1
2
Action
In the browser, click with the right mouse button on Connector 0 or 1 and select unlock.
Result: the cross above the connector icon disappears.
In the browser, double click on Connector 0 or 1.
Result:
Configuration parameters: Cam processor. Connector0
Inversion of outputs
Group0
0 1 2 3 4 5 6 7
Group1
0 1 2 3
3 Check the boxes of the outputs to be inverted
78
TLX DS 57 PL7 xx
Configuration of the electronic cam module
Confirmation of the configuration
Procedure When all the configuration parameters are entered, confirm the configuration obtained using the Edit/Enable command or click on the confirmation icon.
If one or more parameter values are outside the permitted limits, an error message appears indicating the parameter concerned. Correct the parameter then confirm.
Note: Incorrect parameters are displayed in red.
Important l Recipe adjustment parameters are initialized on the first request to confirm the configuration. It is therefore possible that, following modifications of the configuration values, the recipe adjustment parameters will no longer be correct.
In this case a message specifies the parameter affected:
Confirm
Incremental encoder
The angle recalibration value must be < = no. of pulses /cycle
OK l l l
Access the recipe adjustment parameters screen, correct the parameter, then confirm.
The configuration parameters are actually acknowledged: when each of the configuration and adjustment parameters is correct, when they are confirmed in the main screen of the configuration editor.
TLX DS 57 PL7 xx
79
Configuration of the electronic cam module
Reconfiguration in connected mode
Procedure When all the configuration parameters are modified, confirm these parameters using the Edit/Confirm command or click on the confirmation icon.
Only the parameters that are not grayed out can be modified in connected, the other parameters, (task, event, masking faults, encoder and encoder configuration) must be modified in local mode.
Confirm
?
Recipe adjustment will lead to the cam processor stopping. Only adjustment allows the confirmation of parameters without the cam processor stopping.
Do you want to continue?
Yes No
Illustration
Any reconfiguration in connected mode causes the cam processor to stop its operations.
The following diagram describes the reconfiguration process.
Configuration screen PLC processor TSX CCY 1128 module
Configuration parameters
Recipe adjustment parameters
(current)
Configuration parameters
Recipe adjustment parameters
(current)
Recipe adjustment parameters
(initial)
Configuration parameters
Recipe adjustment parameters
(current)
80
TLX DS 57 PL7 xx
Entering recipe adjustment parameters for the electronic cam module
5
At a glance
Subject of this chapter
What's in this chapter?
This chapter describes the operations for entering the recipe adjustment parameters for the TSX CCY 1128 electronic cam module.
This chapter contains the following topics:
Topic
Accessing the recipe adjustment parameters for the module
Entering acquisition parameters for an incremental encoder
Entering the acquisition parameters for an absolute encoder
Parametering for the parts counter
Activating/deactivating the tracks
Parametering for the tracks
Creating cams
Parametering the cams
Cam in position
Monostable cam
Breaking cam
Parametering the confirmation condition associated with a cam
Confirming the recipe adjustment parameters
Saving the recipe adjustment parameters
Restoring the recipe adjustment parameters
Page
81
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Accessing the recipe adjustment parameters for the module
Role This operation is used to access the recipe adjustment parameters for the TSX CCY
1128 module.
The Adjust Recipe mode provides access to all the recipe parameters.
Confirming modifications in connected mode causes the cam function to stop (Cam processor in Stop). Adjust mode can be used to access certain parameters (values in blue in the associated fields) without stopping the cam processor.
Note: The values are refreshed only when the window is opened.
Preliminary conditions
Procedure
The TSX CCY 1128 module must already be configured.
The following table describes the operations to be performed:
Step
1
2
Action
Access the module configuration screen.
Select Recipe Adjustment from the drop-down list at the top left of the configuration screen.
TSX CCY 1128 [RACK 0 POSITION 3]
Adjusting the Recipe
Configuration
Adjusting the Recipe
EC. 128 CAMS
3
4
Confirm the configuration entered if the confirmation request dialog box is displayed.
In the browser, click on the recipe element to be entered: l l l
Acquisition
Parts counter
Connector 0 or 1
82
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Entering acquisition parameters for an incremental encoder
Role
Preliminary conditions
Procedure
This operation defines the recipe adjustment parameters linked with the incremental encoder.
This operation requires an incremental encoder to have been defined during configuration.
The following table describes the operations to be performed:
Step
1
Action
In the browser, double-click on Acquisition.
Result:
Adjustment parameters: Acquisition
Axis
No. of pulses/cycle:
Initial value
No. of cycle:
Initial value 1
256
256
1
Axis play value:
Initial value 0
0 pulses
Recalibration
Value of the angle:
Initial value: 0
0
Value of no. of cycles: 0
Initial value: 0 pulses
2 Enter the Axis parameters. The parameters that are displayed depend on the reading format chosen in the configuration: l Type 1: number of pulses per cycle (minimum value 256 and maximum value 32767).
l Type 2: number of pulses per cycle (minimum value 256 and maximum value 32767) and number of cycles (minimum value 1 and maximum value l
32767)
Type 3: number of pulses per cycle = 32 767. The value that is displayed cannot be modified. It indicates the counting capacity.
TLX DS 57 PL7 xx
83
Entering recipe adjustment parameters
Step
3
4
Action
Enter the axis play value.
This value is used to compensate for the position error caused by changing the direction of rotation, if there is mechanical play between the drive and the axis
(encoder).
If recalibration of the axis is done in the direction of rotation: l forward, declare a negative correction value. The correction will be made on reverse movements, l reverse, declare a positive correction value. The correction will be made on forward movements.
A value of 0 corresponds to no correction.
The values are between -(No. of pulses/cycle) /2 and +(No. of pulses/cycle) /2.
The correction value cannot exceed 1023 pulses.
Note: this correction modifies the switching position of all the cams according to the declared value. Whatever the value of the play entered, the position and captures values sent to the PLC are current values (no corrections).
Enter the recalibration value: l l value of the angle, value of the number of cycles (for type 2 reading format only).
The recalibration value is loaded in the position counter on the recalibration command.
The values are between 0 and + No. of pulses/cycle
84
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Entering the acquisition parameters for an absolute encoder
Role This operation allows you to define an absolute encoder’s recipe adjustment parameters .
This operation requires that an absolute encoder has already been configured.
Preliminary conditions
Procedure
TLX DS 57 PL7 xx
The following table describes the operations to be performed:
Step
1
Action
In the browser, double-click on Acquisition.
Result:
Adjustment parameters: Acquisition
Axis
No. of pulses/cycle:
Initial value
No. of cycle:
Initial value
256
256
1
1
Axis play value:
Initial value 0
0 pulses
Absolute encoder
Offset encoder on angle value:
Initial value:
Offset encoder on value of number of cycles:
Initial value:
Reduction factor:
Initial value: 1
1
0
0
0
0
Recalibration
Value of the angle:
Initial value: 0
0
Value of no. of cycles: 0
Initial value: 0 pulses
2
3 pulses
Enter the Axis parameters. The parameters that are displayed depend on the reading format chosen in the configuration: l l
Type 1: number of pulses per cycle.
Type 2: number of pulses per cycle and number of cycles.
Note:
Choose a value to the power of 2, for the number of pulses per cycle.
Min. value: number of pulses per cycle = 256 and number of cycles = 1
Max. value: 2
14
(see the formula in step 5 of the table).
Enter the encoder offset value (angle and cycle) to obtain a position value equal to 0 when the axis arrives at the machine 0.
This value is the gross value provided by the encoder when the axis is on the machine 0.
The values consist of: l l
0 to No of pulses/cycle for the encoder offset on the angle,
0 to No of cycles for the encoder offset on number of cycles.
85
Entering recipe adjustment parameters
Step
4
5
6
Action
Enter the axis play value.
This value is used to compensate for the position error caused by changing the direction of rotation, if there is mechanical play between the drive and the
(encoder) axis.
l forward, declare a negative correction value. The correction will be made on reverse movements, l reverse, declare a positive correction value. The correction will be made on forward movements.
A value of 0 corresponds to no correction.
The values are between -(No of pulses/cycle) /2 and +(No of pulses/cycle) /2.
The correction value cannot exceed 1023 pulses.
Note: this correction modifies the switching position of all the cams according to the declared value. Whatever the value of the backlash entered, the position and captures values sent to the PLC are current values (no corrections).
Enter the reduction factor.
This factor reduces the encoder resolution. The position given by the encoder is divided by the reduction factor.
This enables the cam program to be effective over a narrower range of pulses than that given by the machine.
Possible reduction factor values:
1 (the cam program reacts in relation to the actual position of the encoder, no reduction),
2 (the position given by the encoder is divided by 2
4, 8, 16 or 32.
In addition the following relationship must be checked:
2 no of data bits > no of pulses/cycles x no of cycles x reduction factor (number of pulses less than or equal to 2
14
)
Enter the recalibration value (angle and cycle).
This recalibration value is systematically added to the position value after correction of the encoder offset. It moves the axis in relation to the machine reference point.
The values consist of: l l
0 to No of pulses/cycles for the recalibration on the angle,
0 to No of cycles for recalibration on the number of cycles.
Note:
The position value (angle and cycle) after offset correction and recalibration application is:
Position value = Gross encoder value - Offset + Recalibration
86
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Parametering for the parts counter
Role
Procedure l l
The parts counter is used to: indicate the number of parts processed, confirm the action of a cam when a certain number of parts (limit value) has been completed.
This operation is used to set the limit value of the parts counter.
The parts counter is incremented, decremented or reset to 0 when changing to 1 on a track according to the cam program.
The following table describes the operations to be performed:
Step
1
Action
In the browser, double-click on Parts counter.
Result
Adjustment parameters: Cam processor. Parts counter
Parts counter
Threshold:
Initial value:
1
1
2 Enter the limit value for the parts counter (value from 1 to 32767)
TLX DS 57 PL7 xx
87
Entering recipe adjustment parameters
Activating/deactivating the tracks
Role
Preliminary conditions
Procedure
The activation operation defines the tracks to be used.
Deactivation frees the unused tracks. The cams associated with these tracks are then destroyed and can be reused for the other tracks in the same group.
The connectors that these tracks are associated to must first be unlocked (in
Configuration mode).
The following table describes the operations to be performed:
Step
1
2
Action
In the browser double click on Connector 0 or 1 then double click in the browser on Group 0, 1, 2 or 3 to access the track(s) to be activated.
Result:
The browser displays all the tracks that are associated with this connector and this group. Tracks that are crossed out are inactive.
Click with the right mouse button on the track to be activated and select the
Activate command (Deactivate for the reverse operation).
The cross disappears from the activated track.
Example: track 0 of connector 0 group 0 is active and tracks 1 to 7 are inactive.
Electronic cam
01
Acquisition
Cam processor
Parts counter
Connector0
Group0
Track0
Track1
Track2
Track3
Track4
Track5
Track6
Track7
Group1
Connector1
88
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Parametering for the tracks
Role
Preliminary conditions
Procedure
This operation is used to define the tracks parameters.
These tracks must first be activated.
The following table describes the operations to be performed:
Step
1
Action
Double-click on the track to be parameterized.
Result:
Adjustment parameters: Cam processor. Connector0. Group1. Track1
The virtual track number 5 can be attached to this track.
Auxiliary functions
Anticipation factor: 0 * 50µ s
Action on the parts counter
Initial value: 0
Forward: N.S
EVT Track
Initial value
Initial value: N.S
Application inverts on output
Initial value
Reverse:
Initial value:
N.S
N.S
Parallel track
Initial value
2 Enter the value of the anticipation factor from 0 to 32767 x 50 micro s.
This factor makes it possible to anticipate all switches of track in order to compensate for the delay caused by the actuators of the machine.
Example: anticipation with a factor of 200
3
Without anticipation
With anticpation
Select EVT Track to trigger an event at each change of track.
TLX DS 57 PL7 xx
89
Entering recipe adjustment parameters
Step
4
5
6
Action
Check Invert application on output to invert the status of the track when the cam processor is in "Run" mode.
This inversion has no effect when the processor is in "Stop". The track remains at 0.
If the track does not have a cam, this function does not apply.
If the track is to perform operations on the parts counter, select the following types of action: l l l
No action
Inc: increments the parts counter each time a cam on the track changes to 1
Dec: decrements the parts counter each time a cam on the track changes to 1 l Reset: resets the parts counter to zero each time a cam on the track changes to 1 in Forward and/or Reverse direction.
Check Parallel track to put a second predefined track (track n+4) from the same group in parallel on the output of track n.
This option allows you to: l l associate tracks 4 to 7 with the outputs of tracks 0 to 3 in the same group.
have 2 tracks with different characteristics (different anticipation factor depending on the direction of movement) on a single output.
If the track does not have a cam, this function does not apply.
Example: if the option is selected on track 1, the value of output 1 will be the
"OR logic" of tracks 1 and 5.
Track 1
Output 1
Track 5
Note: This choice only appears on tracks 0 to 3 of each group.
Output 5
90
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Creating cams
Role
Preliminary conditions
Procedure
This operation associates one (or more) cams to one track.
It is possible to associate up to 32 cams with one track.
The tracks that you wish to associate the cams to must first be activated (in
Configuration mode).
The following table describes the operations to be performed:
Step
1
2
Action
In the browser, click with the right mouse button on the track concerned, and select the Create cam command…
In the dialog box select the number of the cam (0 to 31) and confirm.
The number of a cam already being used in the group cannot be entered.
Result:
The browser displays the cam that has been created under the track to which it belongs.
Example: creation of cam 5 under track 3 of group 1 of connector 0
Connector0
Group0
Group1
Track0
Track1
Track2
Track3
Cam5 P(0, 0, 0)
Track4
Track5
Track6
Track7
TLX DS 57 PL7 xx
91
Entering recipe adjustment parameters
Parametering the cams
Role
Preliminary conditions
Procedure
This operation allows you to define the cam adjustment parameters.
These cams must first be created.
The following table describes the operations to be performed:
Step
1
Action
Double-click on the cam to be parameterized.
Result
Adjustment parameters: Cam processor. Connector0. Group0. Track0. Cam0
Confirmation condition Cam definition
Type: Position
Initial value: Position
ThresholdX1:
Initial value:
0
0 pulses
Cam monitoring:
Initial value:
Cam still operative
Cam still operative
Confirmation bit number:
Initial value:
0
0
ThresholdX2:
Initial value:
Closing delay
Initial value:
0
0
0
0 pulses
*0.1 ms
Activation condition
Forward direction
Reverse direction
Initial value
Initial value
2 Enter the value of each parameter: l l l l type of came: Position, Monostable or Braking, values of associated thresholds, and time delay (for the Monostable cam), cam confirmation condition with the confirmation bit number, direction for which the cam is active.
92
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Cam in position
Role A Position type cam is at state 1 when the position of the axis is between the 2 thresholds. The 2 thresholds, low threshold X1 and high threshold X2 must be defined (X1 and X2 both between 0 and the number of pulses/cycles). X1 can be greater than the value of X2. The cam is then active between two cycles.
One type of activation from the 3 suggested: forward/reverse, forward and reverse, must be selected.
Note: The confirmation condition must be at state 1 for the cam to be able to change to state 1.
Operation of a cam which is active in forward and reverse directions
This table describes the performance of a cam that is active in forward and reverse directions.
Description
If the movement is forward, the cam changes to
1 when threshold X1 is crossed and returns to 0 when threshold X2 is crossed.
Illustration
Avant
If the movement is reversed, the cam changes to
1 when threshold X2 is crossed and returns to 0 when threshold X1 is crossed.
If the movement is: l forward (without crossing threshold X2), the cam changes to 1 when threshold X1 is l crossed.
then reverse, the cam returns to 0 when threshold X1 is crossed
If the movement is: l reverse (without crossing threshold X1), the cam changes to 1 when threshold X2 is crossed l then forward, the cam returns to 0 when threshold X2 is crossed
Arrière
TLX DS 57 PL7 xx
93
Entering recipe adjustment parameters
Operation of a cam which is active in the forward direction
This table describes the performance of a cam that is active in the forward direction.
Description
If the movement is forward, the cam changes to
1 when threshold X1 is crossed and returns to 0 when threshold X2 is crossed
If the movement is reverse, the cam remains at 0.
Illustration
Arrière
Avant
If the movement is: l forward (without crossing threshold X2), the cam changes to 1 when threshold X1 is crossed l then reverse, the cam returns to 0 as soon as the direction of movement changes.
If the movement is: l l reverse, the cam remains at 0 then forward, the cam returns to 1 when threshold X2 is crossed.
94
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Operation of a cam that is active in the reverse direction
This table describes the performance of a cam that is active in the reverse directions.
Illustration Description
If the movement is forward, the cam remains at 0.
Avant
If the movement is reverse, the cam changes to
1 when threshold X2 is crossed and returns to 0 when threshold X1 is crossed
If the movement is: l l forward, the cam remains at 0 then reverse, the cam returns to 1 until threshold X1 is crossed.
Arrière
If the movement is: l reverse, the cam changes to 1 when threshold X2 is crossed l then forward, the cam returns to 0 as soon as the direction of movement changes.
Conditions for angle 0
Threshold X1 can have a value greater than X2 if the cam is active either side of l l value 0, between:
X1 and 0
0 and X2
TLX DS 57 PL7 xx
95
Entering recipe adjustment parameters
Monostable cam
Definition l l
A Monostable type cam is one that changes to 1 when a threshold is crossed and returns to 0 after a time delay.
It is characterized by: l a value of threshold X1 expressed in a number of pulses (X1 is between 0 and the number of pulses/cycles)
An M1 time delay expressed in 1/10 ms (0 to 16383, i.e. 1.6383 s max.)
An activation type: forward/reverse, forward or reverse.
Note: l The confirmation condition must be at state 1 for the time delay to be set when l the threshold is crossed. If the confirmation condition changes to 0, the time delay in progress ends normally.
If the time delay is in progress at a new crossing of threshold X1, the time delay is reset with the setpoint value. The output remains at 1.
Operation
Activation type
Forward and reverse
Description
The monostable is set or reset in both directions.
Illustration
Forward The monostable is only set in forward movement.
Reverse The monostable is only set in reverse.
96
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Breaking cam
Definition A Braking type cam is one that changes to 1 when a threshold is crossed and returns to 0 when the same threshold is crossed in the opposite direction.
It is characterized by: l a forward threshold value X1 (value of the angle which sets the brake when the threshold is crossed in the forward direction) l a reverse threshold value X2 (value of the angle which sets the brake when the threshold is crossed in the reverse direction) l an activation type: forward/reverse, forward or reverse activation type.
Threshold X1 can be greater than X2 (it is thus possible to set the brake cam either in the cycle or between 2 cycles).
Note: The confirmation condition must be at state 1 so that the cam changes to 1 when the threshold is crossed. If the confirmation condition changes to 0, the brake is engaged.
Operation
Activation type
Forward
This table describes the performance of a braking cam.
Illustration Description
The brake is activated when threshold X1 is crossed in the forward direction.
The brake is deactivated when threshold X1 is crossed in the reverse direction.
Reverse
Forward and reverse
The brake is activated when threshold X2 is crossed in the reverse direction.
The brake is deactivated when threshold X2 is crossed in the forward direction.
The brake is activated when: l Threshold X1 is crossed in the forward direction.
l Threshold X2 is crossed in the reverse direction.
The brake is deactivated when these thresholds are crossed in the opposite direction
TLX DS 57 PL7 xx
97
Entering recipe adjustment parameters
Parametering the confirmation condition associated with a cam
Role This is used to associate a confirmation condition with a cam, using a confirmation bit or via the parts counter.
Confirmation bit A group has 8 control bits that are contained in the words GROUPI_ENABLE_BITS
(where i = group no. 0 to 3) and can be accessed by the PLC program. When a l l confirmation bit is associated with a cam, if this bit is at:
1, the cam is enabled,
0, the logic state of the cam remains at 0 whatever the angular position.
l l
Examples of use: integrating the cams in one group by assigning them the same confirmation bit.
managing the operating modes
Parts counter The cam can also be controlled by the state of the parts counter. The cam is only enabled when the parts counter reaches the limit value.
Procedure The following table describes the operations to be performed:
Step
1
2
Action
Access the recipe screen for the cam that is to be parameterized.
Select the confirmation type in the Confirmation condition box: l l
Cam still enabled: no condition is assigned, and the cam is still enabled.
Conditioned by an confirmation bit: a bit is associated with the cam: choose the bit number (from 0 to 7) in the Confirm bit number field, l
Example: if bit 5 is chosen for a cam in group 0, it is the
GROUP0_ENABLE_BITS:X5 bit which enables the cam when it is at 1.
When the parts counter is full.
98
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Confirming the recipe adjustment parameters
Procedure When recipe adjustment parameters are entered, confirm these parameters using the Edit/Confirm command or click on the confirmation icon.
If one or more parameter values are outside the permitted limits, an error message appears indicating the parameter concerned.
Correct the faulty parameter or parameters then confirm.
In connected mode:
The modified parameters are the current parameters (the initial parameters remain unchanged).
PLC processor TSX CCY 1128
Configuration screen recipe adjustment mode
Current adjustment parameters
Current adjustment parameters
Initial adjustment parameters
WARNING
On a cold restart the current parameters are replaced by the initial parameters.
Failure to observe this precaution can result in severe injury or equipment damage.
The initial parameters can be updated by the save command or via a reconfiguration operation.
TLX DS 57 PL7 xx
99
Entering recipe adjustment parameters
Saving the recipe adjustment parameters
Procedure To save the current parameters (updating the initial parameters) select the
Services/Save Parameters command.
PLC processor TSX CCY 1128
Save parameters
Configuration screen recipe adjustment mode
Current adjustment parameters
Current adjustment parameters
Initial adjustment parameters
Note: The SAVE_PARAM%CHXY.0 instruction enables the application to perform this save operation.
100
TLX DS 57 PL7 xx
Entering recipe adjustment parameters
Restoring the recipe adjustment parameters
Procedure The Services/Restore parameters command replaces the current parameters with the initial values.
This operation causes the cam processor to stop.
PLC processor TSX CCY 1128
Configuration screen recipe adjustment mode
Current adjustment parameters
Restore the parameters
Actual adjustment parameters
Initial adjustment parameters
Note: l The RESTORE_PARAM %CHXY.0 instruction enables the application to perform this restoration operation.
l This operation is also performed automatically on a cold restart.
TLX DS 57 PL7 xx
101
Entering recipe adjustment parameters
102
TLX DS 57 PL7 xx
Debugging and adjusting
6
At a glance
Subject of this chapter
What's in this chapter?
This chapter describes the electronic cam module various adjust and debug screens.
This chapter contains the following topics:
Topic
Description of the debugging screen
Description of the status zones
Description of the main debugging zone
Description of the debugging zone: "Acquisition"
Description of the debugging zone: "Parts counter"
Description of the debugging zone: "Group x"
Description of the adjustment screen
Description of the adjustment zone
Page
TLX DS 57 PL7 xx
103
Debugging and adjusting
Description of the debugging screen
Accessing the debugging screen
On the screen corresponding to the module, the pull-down menu can be used to select the debugging mode when the PLC is connected.
TSX CCY 1128 [RACK 0 POSITION 3]
Adjusting the Recipe
Configuration
Adjusting the Recipe
Adjustment
Debugging
EC. 128 CAMS
Debugging screen
This screen is used to find out: l l l the module status, by displaying the various errors which may have arisen the present status of the application-specific function, forcing the track commands, performing recalibrations, setting the module to
RUN or to STOP, and confirming or locking the track action on the outputs.
l the status of the cam processors, locking the outputs,
It can be used to reactivate protected outputs and acknowledge errors.
104
TLX DS 57 PL7 xx
Debugging and adjusting
4
Description This screen is made up of 5 parts:
TSX CCY 1128 V1.0 IE 15 [RACK 0 POSITION 5]
Debugging
Designation: 2 CH.COUNTER.MEASUREMENT Version: 1.0
RUN ERR IO
Symbol:
Function:
Electronic cam
Task:
MAST
CH0
Electronic cam
01
Acquisition
Cam processor
Parts counter
Connector0
Connector1
Debugging: Cam processor Parts counter
Counter
Reset counter:
Confirmation:
Maximum value:
Current value:
1
0
DIAG...
DIAG...
Axis:
Angle: 0
Movement direction: pulses No. of cycles: 0
Reset connector 0:
Speed:
Reset connector 1:
0
Recalib pulses/
Parts counter
Full:
Cam processor
ON: Run cam pgm: Confirm track outputs: Fault acknowledgement:
3
1
2
5
This table describes the different parts:
4
5
2
3
Address Description
1 Module status zone.
Channel status zone.
Debugging zone for the selected function.
Browser zone: used to select a function.
Main debugging zone: used to access the main objects
TLX DS 57 PL7 xx
105
Debugging and adjusting
Description of the status zones
Module status zone
Channel status zone
This section is a reminder of the type of module corresponding to the screen. The three lights are the same as those on the front panel of the module. In normal operation, the DIAG button is grayed out. If there is an error, it turns red.
Clicking on the button opens a window where a message indicates the type of error detected.
Designation: 2 CH.COUNTER.MEASUREMENT Version: 1.0
RUN ERR IO DIAG...
The errors detected can be: faulty self-tests, module missing, module different from the one configured, or communication error…
This section indicates the module application-specific function, the task in which exchanges between the PLC processor and the module are processed, as well as the channel number. In normal operation, the DIAG button is grayed out. If there is an error, it turns red.
Clicking on the button opens a window where a message indicates the type of fault detected.
Symbol:
Function:
Electronic cam
Task:
MAST
CH0 DIAG...
Faults can be one of four types: l Configuration error: axis consistency error. This is indicated by the error codes.
track consistency error. The number of the track concerned and the error code l are indicated, cam consistency error. The number of the cam concerned and the error code are indicated,
Input/output error: l error on the encoder: supply error, line error, SSI transmission error, encoder alarm error, auxiliary I/O error: on supply
Error on track outputs: l supply or trip error. The location of the connector is indicated.
Processing error: modification command refused.
106
TLX DS 57 PL7 xx
Debugging and adjusting
Description of the main debugging zone
At a glance This zone is permanent in the debugging screen. It is used to display the main functions of the axis, and the current status of the cam processor.
Axis:
Angle: 0 pulses
Movement direction:
No. of cycles: 0
Reset connector 0:
Speed: 0
Recalibrated
Reset connector 1: pulses/
Parts counter
Full:
Cam processor
ON: Run cam pgm: Confirm track outputs: Fault acknowledgement:
Description The current values of the axis parameters are provided in the axis section, and cannot be modified. Only two buttons are accessible. These are used to reset shortcircuit faults occurring on each of the module connectors.
In the cam processor section, it is possible to set the processor to RUN or STOP, to enable/lock track outputs, or to acknowledge faults occurring on these outputs.
TLX DS 57 PL7 xx
107
Debugging and adjusting
Description of the debugging zone: "Acquisition"
Accessing the screen
At a glance
This zone is variable and depends on the selection made in the browser.
Selection of acquisition in the browser:
Electronic cam
Acquisition
01 Cam processor
Parts counter
Connector0
Connector1
This acquisition zone is used to display the state and activity of the encoder inputs and the recalibration and capture sensors.
Debugging: Acquisition
State of the physical inputs
Encoder: IA IB
PD: Irec Icapt0
IZ
Icapt1
Confirmation/Recalibration/Captures
Register of capture 0 Register of capture 1
Angle:
No. of cycles:
0
0 pulses Angle:
No. of cycles:
0
0 pulses
Recalibration
Angle: 0
No. of cycles: 0
Recalibration of no. of cycles CAPT0 Recalibration of angle
Confirmation
Direct pulses
CAPT1
The Enable/Recalibrate/Captures zone indicates the current status of the capture and recalibration registers. The buttons are used to confirm the angle and cycle recalibration conditions. The direct recalibration buttons are used to recalibrate the angle and the number of cycles on the rising edge of the action on the button. The capture confirmation buttons are used to confirm the angle and number of cycles capture conditions.
108
TLX DS 57 PL7 xx
Debugging and adjusting
Operation of the
Buttons
"Left click", the action is a push/pull type of operation on the %Q object unless it is controlled by the application program.
"Right click", opens a pull-down menu which is used to force the function to 0 or 1.
The Unforce option is used to remove the forcing in progress. The status of the button indicates forcing in progress.
Status of button
F
Force to 0
Force to 1
Unforce
F
TLX DS 57 PL7 xx
109
Debugging and adjusting
Description of the debugging zone: "Parts counter"
Accessing the screen
At a glance
The "Parts counter" function is selected in the browser.
Electronic cam
Acquisition
01 Cam processor
Parts counter
Connector0
Connector1
"Parts counter" screen zone
Debugging: Cam processor. Parts counter
Counter
Reset counter:
Confirmation:
Maximum value: 1
Current value: 0
The current value of the parts counter is displayed, together with the maximum value given in the recipe.
An enabling button: Reset counter enables the counter to be reset to 0 on the rising edge. An enabling button: Confirmation is used to confirm the conditions for parts counting. This button confirms conditions permanently when it is pressed (black).
110
TLX DS 57 PL7 xx
Debugging and adjusting
Description of the debugging zone: "Group x"
Accessing the screen
At a glance
The Group x function is selected in the browser.
Electronic cam
01
Acquisition
Cam processor
Parts counter
Connector0
Group0
Group1
Connector1
Group2
Group3
This screen zone is divided into two sections.
Cam processor. Connector0. Group0 Debugging:
Confirming cams bit 0: bit 1: bit 2: bit 3: bit 4: bit 5: bit 6: bit 7:
Tracks/Outputs
0 1 2 3 4 5 6 7
Status of tracks
Confirming the output
Forcing the output
State of the outputs
TLX DS 57 PL7 xx
111
Debugging and adjusting
Confirming the cams
Confirming tracks and outputs
Confirming the cams:
Confirming cams bit 0: bit 1: bit 2: bit 3: bit 4: bit 5: bit 6: bit 7:
Each cam in a group can be conditioned on the status of one of the group’s 8 cam confirmation bits. Periodic command objects can be accessed from this screen. (It is possible to set them to 1 as long as the application program is not controlling them). There is no forcing.
Confirming tracks and outputs:
Tracks/Outputs
0 1 2 3 4 5 6 7
Status of tracks
Confirming the output
Forcing the output
State of the outputs
112
4 3 2 1
Correspondence between the status of the tracks and the status of the outputs
2
3
Address Description
1 As long as output confirmation is not set to 1 the output remains at 0.
4
If output confirmation is set to 1, the output takes the status of the track.
As long as the forcing bit is set to 1 the output is set to 1.
Effect of output inversion linked to configuration.
This zone shows the current status of the tracks. Two rows of buttons are used either to confirm each output individually, or to force each output individually (the button turns black).
The lower row is used to display the actual state of the outputs.
TLX DS 57 PL7 xx
Debugging and adjusting
Description of the adjustment screen
At a glance This screen is used to enter and/or modify the parameters of the axis without stopping the processor cam treatment. This mode is used to access a certain number of recipe adjustment parameters.
The layout of this recipe adjustment zone is identical to the "adjust recipe" screen.
Only one function can be modified at a time.
The debugging zone remains simultaneously in these modes.
Description Adjustment Screen
TSX CCY 1128 V1.0 IE 15 [RACK 0 POSITION 5]
Adjustment
Designation: 2 CH.COUNTER.MEASUREMENT Version: 1.0
RUN ERR IO
Symbol:
Function:
Electronic cam
Task:
MAST
CH0
Electronic cam
Acquisition
01 Cam processor
Parts counter
Connector0
Connector1
Adjustment parameters: Acquisition
Axis
No. of pulses/cycle:
Initial value:
256
256
Recalibration
Value of the angle: 132
Initial value: 0 pulses 3
1
Axis play value:
Initial value:
25
0 pulses
Axis:
Angle: 0 pulses
Movement direction:
No. of
Reset connector 0:
Cam processor
ON: Run cam pgm:
0 Speed: 0
Recalibrated pulses/ms
Reset connector 1:
Parts counter
Full:
Confirm track outputs: Fault acknowledgement:
2
TLX DS 57 PL7 xx
113
Debugging and adjusting
This table describes the different zones:
2
3
Address Description
1 Selection zone
Main debugging zone
Adjustment zone (e.g.: acquisition)
Confirming new parameters
After modifying parameter values during debugging, the user should press the confirm button. A request is then sent to the module. The module acknowledges the modification without stopping the cam processor. The modification is in the current module parameters. Switch to Adjust Recipe mode to save them as initial
parameters.
114
TLX DS 57 PL7 xx
Debugging and adjusting
Description of the adjustment zone
Adjustment zone:
"Acquisition"
The "Acquisition" function is selected in the browser.
Electronic cam
01
Acquisition
Cam processor
Parts counter
Connector0
Group0
Group1
Connector1
The only values that can be modified are the values for the play of the axis, the value of the angle of recalibration and the number of cycles. In these screens: whatever is displayed in blue can be modified.
Adjustment parameters: Acquisition
Axis
No. of pulses/cycle:
Initial value
Number of the cycle:
Initial value
Axis play value:
Initial value
256
256
1
1
25
25 pulses
Recalibration
Value of the angle:
Initial value:
Value of no. of cycles: 0
Initial value: 0
132
0 pulses
Adjustment zone: "parts counter"
Opening via the browser:
Electronic cam
01
Acquisition
Cam processor
Parts counter
Connector0
Group0
Group1
Connector1
In this screen the maximum value of the parts counter can be modified.
Adjustment parameters: Cam processor. Parts counter
Parts counter
Threshold:
Initial value:
20
1
TLX DS 57 PL7 xx
115
Debugging and adjusting
Adjustment zone: "track"
Opening via the browser:
Electronic cam
01
Acquisition
Cam processor
Parts counter
Connector0
Group0
Group1
Track0
Track1
Track2
For each selected track, it is possible to assign to it, (modify), a factor of anticipation.
The value will be a number of steps of 50 micro seconds.
Adjustment parameters: Cam processor. Connector0. Group0. Track0
Auxiliary functions
Anticipation factor:
Initial value:
EVT track
Initial value
0
0
Application inverts on output
Initial value
Parallel track
Initial value
* 50µ s
Action on the parts counter
Forward:
Initial value:
Reverse:
Initial value:
No action
No action
No action
No action
116
TLX DS 57 PL7 xx
Adjustment zone: " cam"
Debugging and adjusting
Opening via the browser:
Connector0
Group0
Track0
Cam0 P(0, 0, 0)
Cam1 M(100, 0, 1)
Cam2 F(150, 200, 0)
It is only possible to open configured cams.
Thresholds X1, X2 and the time delay value can be modified. The initial value is given for information and allows you to return easily to the previous conditions.
Adjustment parameters: Cam processor. Connector0. Group0. Track0. Cam3
Confirmation condition Cam definition
Type: Position
Initial value: Position
ThresholdX1:
Initial value:
110
0 pulses
ThresholdX2:
Initial value: 0 pulses
Cam monitoring:
Initial value:
Initial value:
Cam still operative
Cam still operative
Confirmation bit number: 0
0
Closing delay
Initial value:
0
0
*0.1 ms
Activation condition
Forward direction
Reverse direction
Initial value
Initial value
Confirming new parameters
After modifying parameter values during debugging, the user should press the confirm button. A request is then sent to the module. The module acknowledges the modification without stopping the cam processor. The modification is in the current module parameters. Switch to "Adjust Recipe" mode to save them as initial parameters.
TLX DS 57 PL7 xx
117
Debugging and adjusting
118
TLX DS 57 PL7 xx
Programming
7
At a glance
Subject of this chapter
What's in this chapter?
This chapter describes the different programming steps and functions of an electronic cam module
This chapter contains the following topics:
Topic
Circuit diagram of the module functions
Confirmation of the axis functions
Confirming the cam processor functions
Confirming the events
Overview of event management
Language interface
Module level status
Configuration constants
Module adjustment parameters, explicit command
Implicit commands
Processor and module exchanges
System exchanges
WRITE_PARAM: Transfer of current recipe parameters
READ_PARAM: Transfer of current recipe parameters
RESTORE_PARAM: Transferring initial parameters
SAVE_PARAM: Transferring initial parameters
MOD_PARAM: Axis adjustment
MOD_TRACK: Adjusting a track
MOD_CAM: Adjusting a cam
TRF_RECIPE: Recipe transfer functions
Page
TLX DS 57 PL7 xx
119
Programming
Topic
TRF_RECIPE: Functions for storing recipes
TRF_RECIPE: Loading a new recipe
TRF_RECIPE: Saving a new recipe
DETAIL_OBJECT: Operator dialog interface
DETAIL_OBJECT: Transferring cam details
DETAIL_OBJECT: Transferring track details
Page
120
TLX DS 57 PL7 xx
Programming
Circuit diagram of the module functions
General overview
This circuit diagram describes a general overview of the functions of the module: zoom on next page
Group 0
Recipe tracks
TSX 57
Combinational
Module
Physical adaptation of the outputs
32 cams
Assigning the cams to the tracks
Assigning the tracks to the outputs,
Forcing the outputs,
Confirmation
Inverting the outputs outputs of the
TSX CCY
1128 on connector 0
32 cams
Group 1
Assigning the cams to the tracks tracks
Paralleling the tracks
Assigning the tracks to the outputs,
Forcing the outputs
Inverting the outputs
TSX 57 outputs connector 1
Group 2 same as Group 0
Group 3 same as Group 1
TLX DS 57 PL7 xx
121
Programming
Detail for output
0 and track 0 of group 0
This circuit diagram describes the zoom from the previous page:
Recipe
(*)GROUP0_ENABLE_BITS:X0
(Confirmation bit assigned to the cam) %QW INVERT_TRACK
(Inverting the track’s logic state)
%MW
TSX 57 Combinational Module
GROUPE0_AND_BIT:X0
(assigning tracks to the output)
OUTS_ENABLE
%QW
(Confirmation of the output) %Q
Physical adaptation of the outputs
GROUP0_OR_BITS)
(forcing the output to 1)
%QW
INVERT_OUT_0
(Inverting the output) %KW
Cam n
Output 0
Cam n+1
ADD_TRACK possibility of paralleling track 4
%MW on track 0
%MW
122
Note: The cams assigned to one track cannot be assigned to another.
(*) There are two other possibilities: l l still valid parts counter full
TLX DS 57 PL7 xx
Confirmation of the axis functions
Capture The module is able to capture the following: l l the current angle value, the current value of the number for the cycle, (for type 2)
AND FOR THE INCREMENTAL ENCODER ONLY l l l the number of points per turn of the encoder, the current value before recalibration, and the current value on detection of the zero pulse marker
Example: Capture Angle and number of cycles in CAPT0 register
CAPT0_ENABLE AND ICAPT0
ANG_VALUE
TURN_VALUE
CAPT0_ANG
CAPT0_TURN
Programming
Recalibration With an incremental encoder, the counter using the position value must have been recalibrated at least once for the processor to switch to RUN on a
PCAM_START_STOP command.
The implicit commands: l l
PRESET_ANG_ENABLE or PRESET_ANG_FORCE (for Type 1 and Type 3)
PRESET_ALL_ENABLE or PRESET_ALL_FORCE (for Type 2) must be positioned at 1 for the recalibration to be carried out.
Information ANG_OK changes to 1 when the counter is stalled.
TLX DS 57 PL7 xx
123
Programming
Type 1 and Type 3
RESET_ANG_ENABLE
Physical input or zero
PRESET_ANG_FORC
PRESET_ANG_VALUE
ANG_OK set to 1
ANG_VALUE
Type 2
RESET_ANG_ENABLE
Physical input or zero marker
PRESET_ANG_FORC
PRESET_ANG_VALU
E and
ANG_OK set to 1
ANG_VALUE and
TURN_VALUE
124
TLX DS 57 PL7 xx
Programming
Confirming the cam processor functions
RUN The PCAM_START_STOP command object is used to set the cam processing to
RUN.
This will be effective on the rising edge of the command bit: l l
If the axis is recalibrated, if there is no external or application fault detected
If the cam processor is at STOP all the tracks are at 0.
Note: The forcing command and physical inversion of the outputs remain active.
TLX DS 57 PL7 xx
125
Programming
Confirming the events
Event sources
Confirming events
Processing
Conditions
The TSX CCY 1128 module includes 7 sources of events. Each of these can produce a maximum of one event per ms.
For a source to be able to produce its events, its validation bit must be set to 1. (for example: EVT_CAPT0_ENABLE for the capture event 0).
All the events sent by the module, regardless of the source, call up the same single event task in the PLC system.
There is normally only one type of event signaled per call. The switch to angle modulo information is signaled when the switch to Cycle modulo occurs. The source producing the call is determined in the event task via the Events input variable
(%IWxy.0.12). This variable is updated at the beginning of event task processing.
The number of the event task must be declared on the module configuration screen.
The module cannot send out more than one event per ms. This flow can be stopped if several modules send out events simultaneously on bus X.
The module has a buffer with 7 spaces that can be used to store several events awaiting transmission.
If the module cannot send all the internally produced events, the OVERRUN_EVT bit of the Events variable switches to 1.
For the "Modulo crossing" event, the configured current value format must be either type 2 (cyclic) or type 3 (infinite).
126
TLX DS 57 PL7 xx
Programming
Overview of event management
At a glance
Process
Event source
Recalibrating the angle and number of cycles
This synopsis describes event management:
Confirmation of events
EVT_PRESET_ENABLE
%Qxy.0.10
TSX CCY 1128 module event buffer memory
1evt/ms
TSX 57 processor
In the EVT task
1evt/x (1) ms
(* Recalibration *)
! IF EVT_PRESET...
%IWxy.0.12:x2
Switch to Angle modulo
EVT_ANG_ENABLE
%Qxy.0.8
Switch to Cycle modulo
EVT_TURN_ENABLE
%Qxy.0.9
Detection of cam EVT_CAM_ENABLE
%Qxy.0.13
Capture 0 EVT_CAPT0_ENABLE
%Qxy.0.11
(* ANGLE modulo *)
! IF EVT_ANG...
%IWxy.0.12:x0
(* Cycle Modulo *)
! IF EVT_TURN ...
%IWxy.0.12:x1
Note: Saturation of the buffer memory is signaled by the OVERRUN_EVT bit. This bit must be read in the event task.
(1) x ms for 1 ms, normally if system event management is not saturated.
(*CAMS*)
! IF EVT_CAM ...
%IWxy.0.12:x5
(* Capture 0*)
! IF EVT_CAPT0 ...
%IWxy.0.12:x3
Capture1 EVT_CAPT1_ENABLE
%Qxy.0.12
Parts counter full EVT_PIECES_FULL_ENAB
LE
%Qxy.0.14
(* Capture 1*)
! IF EVT_CAPT1 ...
%IWxy.0.12:x4
(* Parts counter full*)
! IF EVT_PIECES_FULL
...
%IWxy.0.12:x6
TLX DS 57 PL7 xx
127
Programming
Language interface
At a glance The language interface defines all the data that can be read or modified by the application program. The data is implicit and periodic (%Q, %QW, %I, %IW) when it is updated automatically by the PLC task. It is explicit and not periodic (%MW) when it is updated by the program after execution of the READ_STS or READ /
WRITE_PARAM functions.
It is possible to associate with each word or bit a symbol that can be used by the application program (see PL7 reference manual). A table of symbols has been predefined. They can be assigned to the module data (see PL7 Reference Manual).
128
TLX DS 57 PL7 xx
Programming
Module level status
Module status objects
These objects are common to all the modules in the range.
Object
%Ixy.MOD.ERR
%MWxy.MOD.2
Symbol
MOD_FAULT
FAULTY_MOD
FAULTY_CH
MOD_CNF_FLT
MISSING_MOD
Meaning module error bit x0 = 1 internal error: module failure x1 = 1 channel operating fault (see channel status) x2 to x4 reserved x5 = 1 fault in configuration: difference between the value configured and that read x6 = 1 module missing or off x7 = reserved
They give information about the module status.
The value of these objects is updated by an explicit command:
READ_STS %CH xy .MOD
TLX DS 57 PL7 xx
129
Programming
Configuration constants
Module level constants
Object
%KWxy.0.0
%KWxy.0.1
%KWxy.0.2
%KW common to the module:
Symbol
EVT_CONF
EVT_ENABLE
EVT_NUM reserved
INPUT_CONF
INPUT_MOD
LINE_FILT
DIRECTION_INV
MULT4_RESOL
LINE_CTRL
FORMAT_MEAS_0
FORMAT_MEAS_1
PRESET_MOD_0
PRESET_MOD_1
CAPTS_MOD_0
CAPTS_MOD_1
CAPTS_MOD_2
Meaning
Event configuration
Bit 0: masking the event
16#FF no event task
16#00 event task priority 0
16#01 event task priority 1
Bit 1: event task number
16#FF no event task
Configuration of the axis x0, x1: Type of encoder
= 16#00: incremental encoder
= 16#01: SSI link absolute encoder
= 16#02: parallel absolute encoder and TSX ABE7CPA11 x2: reserved x3 =1 filtering of inputs (disconnection frequency125KHz) x4 =1 the axis rotates in the opposite direction to the encoder x5: reserved x6 =1 multiplication by 4 of the encoder resolution x7 =1 encoder line check x8, x9 measurement type
=16#00 Type 1 (angle)
=16#01 Type 2 (angle + cycles)
=16#02 Type 3 (linear) x10, x11 type of recalibration
=16#00 no recalibration
=16#01 recalibration on rising edge of Irec
=16#02 recalibration on rising edge of Irec on FWD recalibration on falling edge of Irec in REV
=16#03 recalibration on rising edge of Z FORWARD and
Irec=1 recalibration on falling edge of Z in REV and Irec =1 x12, x13, x14 types of capture capture 0: on the rising edge Icapt0 in every case capture 1:
=16#00 on falling edge Icapt0
=16#01 on rising edge Icapt1
=16#02 number of pulses per cycle
=16#03 angle value before recalibration
=16#04 angle value on rising edge of Z x15: reserved
130
TLX DS 57 PL7 xx
Object
%KWxy.0.3
%KWxy.0.4
%KWxy.0.5
%KWxy.0.6
%KWxy.0.7
%KWxy.0.8
%KWxy.0.9
to
%KWxy.0.14
Programming
Symbol
ABS_ENC_CONF_0
GRAY
WITH_PAR
EVEN_PAR
WITH_ERR
ERROR_LEV
ABS_ENC_ERROR_RANGE
ABS_ENC_READ_PERIOD
ABS_ENC_EXTRA_NB
BEGIN_NB
STAT_NB
ABS_ENC_DATA_NB
Meaning reserved absolute SSI encoder configuration
Choice of binary/Gray code x0 =0 binary x0 =1 Gray x1 =1 parity bit present in the frame x2 =1 even parity x3, x4 reserved x5 =1 parity bit present in the frame x6 = 1 logic level of error bit (default for logic1 ) x7 to x15 reserved rank of error bit in the status bits value: 16#00, 16#01, 16#02, 16#03, or 16#04 encoder read period:
16#00 = 50 microseconds
16#01 = 100 microseconds
16#02 = 200 microseconds number of additional bits supplied by the encoder:
Bit 0: number of header bits length of header field before MSB = 4 max
Bit 1: number of status bits length of status field before LSB = 4 max
Total number of encoder bits length of data field = 25 max reserved
TLX DS 57 PL7 xx
131
Programming
Object
%KWxy.0.15
Symbol
CONTROLES_CONF
C0_LOCK
C0_LOCK
PCAM_STAND_ALONE
%KWxy.0.16
%KWxy.0.17
PCAM_IGN_SC
OUTS_MAINT
SUPPLY_AUX_MSK
SUPPLY_ENC_MSK
SUPPLY_C0C1_MSK
REARM_MOD
SPEED_FORMAT
Meaning
Fault configuration x0: locking connector 0 x0 =1 no power supply monitoring on connector 0 x1: locking connector 0 x1 =1 no power supply monitoring on connector 1 x2 to x7 reserved x8: Option on switching to PLC communication fault: x8 = 0 the cam processor switches to STOP x8 = 1 cam processor remains in RUN mode x9: Option to switch to short-circuit fault x9 = 0 the cam processor goes to STOP x9 = 1 cam processor remains in RUN x10: Option on switching to PLC communication fault: x10 =0 outputs are set to 0V x10 =1 direct commands on maintained outputs x11: Option on auxiliary input power supply fault x11 =0 sets bit: %Ixy.0.ERR
x11 =1 no effect on %Ixy.0.ERR
x12: Option on encoder power supply fault x12 =0 sets bit: %Ixy.0.ERR
x12 =1 no effect on %Ixy.0.ERR
x13: Option on CNX0 and CNX1 connectors power supply fault x13 =0 sets bit: %Ixy.0.ERR
x13 =1 no effect on %Ixy.0.ERR
x14: Reactivation of outputs option x14 =0 reactivation on explicit command x14 =1 reactivation 10 seconds after tripping x15: reserved expression of speed
16#00: speed expressed in pulses/ms
16#04: speed expressed in pulses/s reserved
132
TLX DS 57 PL7 xx
Group level constants
Object
%KWxy.i.18
%KWxy
Symbol
INVERT_OUTi
INVERT_OUTi_0
INVERT_OUTi_1
INVERT_OUTi_7
Meaning electrical level of tracks output of group "i"
Inversion of track output i.0: x0 = 0 output i.0 = 24V for logic state 1 x0 = 1 output i.0 = 24V for logic state 0
Inversion of track output i.1: x1 = 0 output i.0 = 24V for a logic state 1 x1 = 1 output i.0 = 24V for a logic state 0 the same right up to:
Inversion of track output i.7: x7 = 0 output i.0 = 24V for a logic state 1 x7 = 1 output i.0 = 24V for a logic state 0
Programming
TLX DS 57 PL7 xx
133
Programming
Module adjustment parameters, explicit command
Adjustment parameters
Object
%MWxy.0.20
%MWxy.0.21
%MWxy.0.22
%MWxy.0.23
%MWxy.0.24
%MWxy.0.25
%MWxy.0.26
%MWxy.0.27
%MWxy.0.28
%MWxy.0.29
to
%MWxy.0.31
Adjusting the measurement function:
Symbol
PRESET_ANG_VALUE
PRESET_TURN_VALUE
SLACK_VALUE
MAX_PIECES
ABS_OFFSET_ANG
ABS_OFFSET_TURN
ABS_REDUC
RESOL_ANG
RESOL_TURN
Meaning value of angle recalibration value of number of recalibration cycles value of axis play adjustment inverted: hysteresis between -
1023 and + 1023 maximum value of number of parts value of the offset angle absolute encoder in relation to the machine 0 value of the offset of the absolute encoder cycle number in relation to the machine 0 absolute encoder resolution reduction factor:
16#01: no reduction
16#02, 16#04, 16#08, 16#10, 16#20: division by 2, 4, 8, 16, or 32 of the value supplied by the encoder machine resolution in number of pulses per cycle machine resolution in number of cycles reserved
134
TLX DS 57 PL7 xx
Programming
Adjustment of tracks
Object
%MWxy.i.(j)
%MWxy.i.(j+1)
Description of tracks
The description of the tracks is contained in words:
%MWxy.i.(j) and %MWxy.i.(j+1)
"i": represents the group to which track 0, 1, 2, or 3 is attached
"j": represents the value of the track number (0 to 7) multiplied by 2 plus 32
This table describes the track adjustment
Meaning Symbol
SPECIF_TRACK
PIECES_FORW
PIECES_BACK
ADD_TRACK
INVERT_TRACK
EVT_TRACK x0, x1: action on the parts counter in forward direction
16#00: No action
16#01: incremented every time the track changes to 1
16#02: decremented every time the track changes to 1
16#03: reset to zero every time the track changes to 1 x2, x3: action on the parts counter in reverse direction
16#00: no action
16#01: incremented every time the track changes to 1
16#02: decremented every time the track changes to 1
16#03: reset to zero every time the track changes to 1 x4 to x10 reserved x11 =1 paralleling of tracks on an output if the object represents: track 0 then: OUT 0 = track 0 + track 4 track 1 then: OUT 1 = track 1 + track 5 track 2 then: OUT 2 = track 2 + track 6 track 3 then: OUT 3 = track 3 + track 7 x12 =1 inversion of the track logic state x13 =1 event track x14: reserved x15 =0 the track does not participate in processing x15 =1 the track participates in processing
USE_TRACK
ANTICIP_FACTOR anticipation factor in steps of 50 microseconds value between 0 and 32767
TLX DS 57 PL7 xx
135
Programming
Adjusting the cams
Object
%MWxy.i.(j)
%MWxy.i.(j+1)
%MWxy.i.(j+2)
%MWxy.i.(j+3)
%MWxy.i.(j+4)
Description of cams
The description of the cams is contained in words:
%MWxy.i.(j) and %MWxy.i.(j+4)
"i": represents the group to which cam 0, 1, 2, or 3 is attached
"j": represents the value of the cam number (0 to 31) multiplied by 5 plus 48
This table describes the cam adjustment
Symbol
SPECIF_CAM_0
TYP_PROFIL
FORW_ENABLE
BACK_ENABLE
TRACK_NUM
USE_CAM
SPECIF_CAM_1
COND_ENABLE
BIT_NUM_ENABLE
X1
X2
TIME_SWITCH_OFF
Meaning specification of the profile of a cam x0 to x2: cam profile:
16#00: position cam
16#03: monostable cam
16#06: brake cam x3 =1 cam enabled in forward direction x4 =1 cam enabled in reverse direction x5 to x8: reserved x9 to x11: assigning to a track number (0 to 7) x12 to x14: reserved cam declared: x15 =0 the cam is not processed by the program x15 =1 the cam is declared and processed by the program
Cam confirmation conditions x0, x1: cam confirmation condition
16#00: cam still active
16#01: cam conditioned by a confirmation bit
16#02: the cam is confirmed when the parts counter reaches the programmed value x2 to x4: confirmation bit number x5 to x15: reserved value of cam threshold X1 value of cam threshold X2 value of time delay at opening in steps of 100 microseconds from 0 to 16383
136
TLX DS 57 PL7 xx
Programming
Implicit commands
Object
%Qxy.0.0
%Qxy.0.1
%Qxy.0.2
%Qxy.0.3
%Qxy.0.4
%Qxy.0.5
%Qxy.0.6
%Qxy.0.7
%Qxy.0.8
%Qxy.0.9
%Qxy.0.10
%Qxy.0.11
%Qxy.0.12
%Qxy.0.13
%Qxy.0.14
%Qxy.0.15
%Qxy.0.16
to
%Qxy.0.20
%Qxy.0.21
%Qxy.0.22
%Qxy.0.23
%Qxy.0.24
%Qxy.0.25
Global %Q commands
These are all the variables that are used to configure a channel command. The variables are exchanged implicitly by the module. Commands are performed by positioning %Q bits.
This table describes the global %Q commands
Symbol
PRESET_ANG_ENABLE
PRESET_ALL_ENABLE
CAPT0_ENABLE
CAPT1_ENABLE
PCAM_START_STOP
PIECES_ENABLE
EVT_ANG_ENABLE
EVT_TURN_ENABLE
EVT_PRESET_ENABLE
EVT_CAPT0_ENABLE
EVT_CAPT1_ENABLE
EVT_CAM_ENABLE
EVT_PIECES_FULL_ENABL
E
ACK_FLT
Meaning
= 1: confirmation of the recalibration function only on the angle value
= 1: enables the recalibration function on the angle and cycle value
= 1: enables capture 0
= 1: enables capture 1 reserved start command for the cam processor active on rising edge stop command for the cam processor active on falling edge reserved
= 1: enables the parts counter function
= 1: event source when switching to enabled angle modulo
= 1: event source when switching to enabled cycle modulo
= 1: event source for enabled preset
= 1: capture 0 enabled event source
= 1: capture 1 enabled event source
= 1: event source for enabled cam program
= 1: event source for enabled parts counter threshold reached
= 1: acknowledgement of faults present reserved
PRESET_ANG_FORCE
PRESET_ALL_FORCE
PIECES_RESET
OUTS_ENABLE
= 1: (re)calibrates the angle value
=1: (re)calibrates the angle and cycle values
= 1: parts counter reset to zero reserved
= 0: the outputs are kept idle (according to the outputs configuration) x25 = 1 global enabling of outputs
TLX DS 57 PL7 xx
137
Programming
Object
%Qxy.0.16
to
%Qxy.0.20
%Qxy.0.32
%Qxy.0.33
%Qxy.0.34
to
%Qxy.0.39
Symbol
C0_REARM
C1_REARM
Meaning reserved resetting of connector 0 of groups 0 and 1 active on rising edge resetting of connector 1 of groups 2 and 3 active on rising edge reserved
Object
%QWxy.0.0
%QWxy.0.1
%QWxy.0.2
%QWxy.1.0
%QWxy.1.1
%QWxy.1.2
%QWxy.2.0
%QWxy.2.1
%QWxy.2.2
%QWxy.3.0
%QWxy.3.1
%QWxy.3.2
Commands on
%QW groups
%QWxy.i.j words, exchanged implicitly, are used to control groups of cams for each module channel. i is the number of the channel group.
This table describes the commands on %QW groups
Symbol
GROUP0_ENABLE_BITs
GROUP0_AND_BITs
GROUP0_OR_BITs
GROUP1_ENABLE_BITs
GROUP1_AND_BITs
GROUP1_OR_BITs
GROUP2_ENABLE_BITs
GROUP2_AND_BITs
GROUP2_OR_BITs
GROUP3_ENABLE_BITs
GROUP3_AND_BITs
GROUP3_OR_BITs
Meaning x0 to x7 = 1: enables cams by track from 0 to 7, group 0 x0 to x7 = 1: assigns tracks to group 0 outputs x0 to x7 = 1: forces group 0 outputs (to 1) x0 to x7 = 1: enables cams by track from 0 to 7, group 1 x0 to x7 = 1: assigns tracks to group 1 outputs x0 to x7 = 1: forces group 1 outputs (to 1) x0 to x7 = 1: enables cams by track from 0 to 7, group 2 x0 to x7 = 1: assigns tracks to group 2 outputs x0 to x7 = 1: forces group 2 outputs (to 1) x0 to x7 = 1: enables group 3 cams x0 to x7 = 1: assigns tracks to group 3 outputs x0 to x7 = 1: forces group 3 outputs (to 1)
138
TLX DS 57 PL7 xx
Programming
%Ixy.0.4
%Ixy.0.5
%Ixy.0.6
%Ixy.0.7
%Ixy.0.8
%Ixy.0.9
%Ixy.0.10
%Ixy.0.11
%Ixy.0.12
%Ixy.0.13
%Ixy.0.14
%Ixy.0.15
Periodic inputs:
%I
Object
%Ixy.0.0
%Ixy.0.1
%Ixy.0.2
%Ixy.0.3
Input bits or words are exchanged periodically (implicit exchange). There is no synchronization with the cam module cycle. They are used to find out the status of the module functions.
This table describes periodic inputs: %I
Symbol
ANG_OK
DIRECTION
PCAM_ON
PIECES_FULL
IREC_STAT
ICAPT0_STAT
ICAPT1_STAT
IA_STAT
IB_STAT
IZ_STAT
Meaning
=1: enable angle reading reserved
= 0: reverse direction (-)
= 1: forward direction (+)
= 0: cam processor in STOP mode
= 1: cam processor in RUN mode
= 1: parts counter at the threshold reserved reserved reserved status of IREC physical input reserved status of ICAPT0 physical input status of ICAPT1 physical input status of IA encoder input status of IB encoder input status of IZ encoder input reserved
TLX DS 57 PL7 xx
139
Programming
Periodic inputs:
%IW
Object
%IWxy.0.0
%IWxy.1.0
%IWxy.2.0
%IWxy.3.0
%IWxy.0.1
%IWxy.0.2
%IWxy.0.3
%IWxy.0.4
%IWxy.0.5
%IWxy.0.6
%IWxy.0.7
%IWxy.0.8
%IWxy.0.9
%IWxy.0.10
%IWxy.0.12
Words %IWxy.0.0 to %IWxy.0.10 are exchanged periodically (implicit exchanges).
This table describes %IW periodic inputs
Symbol
GROUP0_TRACKS
GROUP1_TRACKS
GROUP2_TRACKS
GROUP3_TRACKS
ANG_VALUE
TURN_VALUE
SPEED
PIECES_VALUE
CAPT0_ANG
CAPT0_TURN
CAPT1_ANG
CAPT1_TURN
OUTS_C0
OUTS_C1
EVENTS
EVT_ANG
EVT_TURN
EVT_PRESET
EVT_CAPT0
EVT_CAPT1
EVT_CAM
EVT_PIECES_FULL
DIRECTION_EVT
Meaning x0 to x7: status of group 0 tracks x0 to x7: status of group 1 tracks x0 to x7: status of group 2 tracks x0 to x7: status of group 3 tracks x0 to x15: current value of the position angle x0 to x15: current value of number of cycles x0 to x15: speed value x0 to x15: value of the parts counter x0 to x15: value of capture 0 register (angle) x0 to x15: value of capture 0 register (cycle) x0 to x15: value of capture 1 register (angle) x0 to x15: value of capture 1 register (cycle) x0 to x15: status of connector 0 outputs x0 to x15: status of connector 1 outputs event register x0 =1: event transmitted at each rollover of the angle value x1 = 1: event transmitted at each rollover of the cycle value x2 = 1: event transmitted on recalibration x3 = 1: event transmitted on capture 0 x4 = 1: event transmitted on capture 1 x5 = 1: event transmitted by the cam program x6 = 1: event transmitted when the parts counter reaches the threshold x7 to x13 reserved x14 = 1: forward direction of rotation on event: EVT_TURN or
EVT_ANG x14 = 0: reverse direction of rotation on event: x15 = 1: events overrun
%IWxy.0.13
%IWxy.0.14
%IWxy.0.15
OVERRUN_EVT
CAME_EVT
CAPT_ANG_EVT
CAPT_TURN_EVT x0 to x4 = cam number x5 to x6 = group number x7 to x15 reserved x0 to x15 captured angle value x0 to x15 captured value of number of cycles
Words %Iwxy.012.to %IWxy.015 are refreshed in the event task.
140
TLX DS 57 PL7 xx
Programming
Processor and module exchanges
At a Glance The module is used to modify parameters using the following exchanges:
Special Features Role
Transferring initial configuration and adjustment data
Transferring current parameters
Name system exchanges
WRITE_PARAM
READ_PARAM
Transferring initial parameters RESTORE_PARAM
SAVE_PARAM
Adjusting the axis
Adjusting a track
Adjusting a cam
MOD_PARAM
MOD_TRACK
MOD_CAM
These exchanges are specific to the cam module
TLX DS 57 PL7 xx
141
Programming
System exchanges
Reminder on exchanges
Transferring initial configuration and adjustment data
Exchanges comply with the Premium range exchange standard (see PL7 implementation manual).
Transfer is performed at the time of a warm restart, a cold restart or on request for reconfiguration from a programming terminal in connected mode.
The module switches to stop mode before each transfer.
Processor memory
%KWxy.
Axis configuration
Cam processor configuration
Group configuration
%MWxy.0.0
RECONF_IN_PROG
%MWxy.0.1
RECONF_IN_ERR
Module
TSX
CCY 1128
Save initial adjustments
Recipe
%MWxy.
Axis adjustment
Cam program
Channel status
%MWxy.
APPLI_FIT
COD_PARAM_FIT
COD_DESC_FIT
NUM_DESC_FLT
NUM_GROUP_FLT READ_STS %CHxy.0
142
TLX DS 57 PL7 xx
Transfer report
Programming l l
During the transfer, %MWxy.0.0:15 RECONF_IN_ PROG is set to 1.
At the end of the exchange, the bit RECNF_ERR is set to 1 if the exchange was not carried out correctly. The READ_STS %CHxy.0 function is used to refresh the channel status.
It contains the following data: l l
APPLI_FLT: the module does not have the configuration and adjustment data necessary for its operation.
COD_PARAM_FLT: error code found by the module in the axis. part of a l configuration or adjustment data item.
COD_DESC_FLT: error code found by the module in the track or cam descriptor part of a configuration or adjustment data item.
NUM_DESC_FLT: codes the track or cam number containing a description error.
NUM_GROUP_FLT: codes the group number which contains the track or cam containing a description error.
TLX DS 57 PL7 xx
143
Programming
WRITE_PARAM: Transfer of current recipe parameters
Reloading a modified recipe in the module
The WRITE_PARAM %CHxy.0 instruction is used to load the parameters of a modified recipe
%KWxy.
Axis configuration
Cam processor configuration
Group configuration
%MWxy.0.0
ADJ_IN_PROGR
%MWxy.0.1
ADJUST_ERR
WRITE_PARAM %CHxy.0
Module
TSX
CCY 1128
(Cam processor in STOP mode)
Save initial adjustments
Modifications
Recipe
%MWxy.
Axis adjustment
Cam program
Channel status
%MWxy.
APPLI_FIT
COD_PARAM_FIT
COD_DESC_FIT
NUM_DESC_FLT
NUM_GROUP_FLT
READ_STS %CHxy.0
All the recipe adjustment data is transmitted to the module using the
WRITE_PARAM %CHxy.0 function. The cam processor is switched to STOP mode.
If the exchange is faulty, the module remains in STOP mode.
144
TLX DS 57 PL7 xx
Transfer report
Programming
During the transfer, the bit %MWxy.0.0:x2 ADJ_IN_ PROG is set to 1.
At the end of the exchange, the bit ADJUST_ERR (bit %MWxy.0.1:x2) is set to 1 if l l the exchange has not been carried out correctly. The READ_STS %CHxy.0 function is used to refresh the channel status.
It contains the following data: l APPLI_FLT: the module refused the new recipe. The cam function cannot be activated. However, the old parameters contained in the module can be saved using the function READ_PARAM %CHxy.0.
l l
COD_PARAM_FLT: error code found by the module in the axis part of a configuration or adjustment data item.
COD_DESC_FLT: error code found by the modulein the track or cam descriptor part of a configuration or adjustment data item.
NUM_DESC_FLT: codes the track or cam number containing a description error.
NUM_GROUP_FLT: codes the group number which contains the track or cam containing a description error.
TLX DS 57 PL7 xx
145
Programming
READ_PARAM: Transfer of current recipe parameters
Retrieving current recipe parameters
The READ_PARAM %CHxy.0 instruction is used to retrieve the parameters of the current recipe contained in this module.
%KWxy.
Axis configuration
Cam processor configuration
Group configuration
%MWxy.0.0
ADJ_IN_PROGR
%MWxy.0.1
ADJUST_ERR
READ_PARAM %CHxy.0
Module
TSX
CCY 1128
(Cam processor at STOP or
RUN mode)
Save initial adjustments
Recipe
%MWxy.
Axis adjustment
Cam program
During the transfer, the bit ADJ_IN_PROGR is set to 1. The READ_PARAM instruction does not force the cam processor into STOP mode.
146
TLX DS 57 PL7 xx
Programming
RESTORE_PARAM: Transferring initial parameters
Loading the original recipe
In an application, it may be necessary to reload the initial parameters of a recipe.
%KWxy.
Axis configuration
Cam processor configuration
Group configuration
Save adjustments
Recipe
%MWxy.
Axis adjustment
Cam program
Module
TSX
CCY 1128
(Cam processor in
RUN mode)
RESTORE_PARAM %CHxy.0
The operating mode is identical to that of WRITE_PARAM.
TLX DS 57 PL7 xx
147
Programming
SAVE_PARAM: Transferring initial parameters
Saving recipe adjustments and modifications
In an application, after the adjustment and debugging phases have been completed, it is necessary to save the new axis parameters.
%KWxy.
Axis configuration
Cam processor configuration
Group configuration
Module
TSX
CCY 1128
RUN or
STOP)
Save adjustments
SAVE_PARAM %CHxy.0
Recipe
%MWxy.
Axis adjustment
Cam program
Saving the parameters can be done with the module and the cam processor in RUN mode.
148
TLX DS 57 PL7 xx
Programming
MOD_PARAM: Axis adjustment
General The MOD_PARAM function is used to adjust an axis dynamically. In this case, transferring modified data does not mean that the cam processor must be switched to STOP mode. If the transfer is successful, then the new parameters are recognized by the module. If the transfer is not successful, then the module uses the l l l l old axis adjustment values.
The MOD_PARAM function assigns to each exchange the parameters:
PRESET_ANG_VALUE: value of angle recalibration
PRESET_TURN_VALUE: value of recalibration for the number of cycles
SLACK_VALUE: axis play value
MAX_PIECES: parts counter threshold
Parameter buffer The exchange zone used by the MOD_PARAM function is a buffer made up of reserved words: %MWxy.0.16 to %MWxy.0.19.
Loading the exchange zone
The exchange zone (buffer) can be preloaded: l l with the initial adjustment values MOD_PARAM %CHxy.0 (0,0,0,0) action {Get} with the current adjustment values MOD_PARAM %CHxy.0 (1.0,0,0) action
{Read}
Sending the new values to the module
After modification in the buffer, the function MOD_PARAM %CHxy.0 (2,0,0,0) action {Send} sends the new values to the module and updates the current parameters zone.
TLX DS 57 PL7 xx
149
Programming
Initializing the parameter buffer action {Get} or action {Read}
%KWxy.
Axis configuration
Cam processor configuration
Group configuration
Save initial adjustments
MOD_PARAM %{Get}
Recipe
%MWxy.
Axis adjustment
Cam program
MOD_PARAM %{Read}
Module
TSX
CCY 1128
(RUN or
STOP)
%MWxy.0.16= PRESET_ANG_VALUE
%MWxy.0.17= PRESET_TURN_VALUE
%MWxy.0.18= SLACK_VALUE
%MWxy.0.19= MAX_PIECES_VALUE
Example {Get} MOD_PARAM %CHxy.0 (0,0,0,0);
{Read} MOD_PARAM %CHxy.0 (1,0,0,0);
150
TLX DS 57 PL7 xx
Programming
Sending new parameters
Action {send}
%KWxy.
Axis configuration
Cam processor configuration
Group configuration
%MWxy.0.0
ADJ_IN_PROG
%MWxy.0.1
ADJ_ERR
Save adjustments
Recipe
%MWxy.
Axis adjustment
Cam program
Modifications
MOD_PARAM {Send}
Axis parameters
%MWxy.0.16= PRESET_ANG_VALUE
%MWxy.0.17= PRESET_TURN_VALUE
%MWxy.0.18= SLACK_VALUE
%MWxy.0.19= MAX_PIECES_VALUE
Parameter buffer
%MWxy.
COD_PARAM_FIT
Module
TSX
CCY 1128
Cam processor in RUN mode
READ_STS %CHxy.0
Example
Monitoring the exchange
{Send} MOD_PARAM %CHxy.0 (2,0,0,0)
During the transfer, the bit (x15) ADJ_IN_PROG is set to 1. At the end of the exchange, the bit ADJUST_ERR is set to 1 if the exchange was not carried out correctly. The READ_STS %CHxy.0 function is used to refresh the channel status.
It contains the following data: l COD_PARAM_FLT: error code found by the module in the axis part of a configuration or adjustment data item.
TLX DS 57 PL7 xx
151
Programming
MOD_TRACK: Adjusting a track
General The MOD_TRACK function is used to adjust a track dynamically. Transferring new data does not require the cam processor to switch to STOP mode. If the transfer is successful, the new parameters are recognized by the module. If the transfer is not successful, the cam processor remains in RUN mode with the old values.
The MOD_TRACK function only affects the anticipation value of a track.
Parameter buffer The exchange zone used by the MOD_TRACK function is a buffer made up of the reserved word: %MWxy.0.16.
Loading the exchange zone
The exchange zone (buffer) can be preloaded: l l with the initial anticipation values:
MOD_TRACK %CHxy.0 (0,Group,Track) with the current anticipation values:
MOD_TRACK %CHxy.0 (1,Group,Track) action {Get}
{action {READ}
Sending the new values to the module
After modification in the buffer: l the function
MOD_TRACK %CHxy.0 (2,Group,Track) action {Send} updates the track anticipation value in the module and in the current parameters zone.
Key Group: identifies the group number
Track: identifies the track number
152
TLX DS 57 PL7 xx
Programming
Initializing the parameter buffer action {Get} or action {Read}
%KWxy.
Axis configuration
Axis processor configuration
Group configuration
Save initial adjustments
MOD_TRACK{Get}
%MWxy.0.16=Anticip
%MWxy.0.0
ADJ_IN_PROGR
%MWxy.0.1
ADJUST_ERR
Recipe
%MWxy.0.0
Axis adjustment
Cam program
MOD_TRACK{Read}
Module
TSX
CCY 1128
Parameter buffer
Example For Group 0 Track 4 l {Read}: MOD_TRACK %CHxy.0 (1,0,4) l {Get}: MOD_TRACK %CHxy.0 (0.0,4)
The execution of the MOD_TRACK function can be monitored via the channel status level.
TLX DS 57 PL7 xx
153
Programming
Sending the new anticipation value
Action {Send}
%KWxy.
Axis configuration
Axis processor configuration
Group configuration
Save initial adjustments
Modifications
%MWxy.0.16
Anticip
%MWxy.0.0
ADJ_IN_PROGR
%MWxy.0.1
ADJUST_ERR
Recipe
%MWxy.0.0
Axis adjustment
Cam program
MOD_TRACK
Parameters
Channel status
Module
TSX
CCY 1128
%MWxy.0
COD_DESC_FIT
NUM_DESC_FLT
NUM_GROUP_FLT
READ_STS %CHxy.0
Example
Monitoring the exchange
For Group 0 Track 4: l {Send}: MOD_TRACK %CHxy.0 (2,0,4) l l
During the transfer, the bit (x15) ADJ_IN_PROG is set to 1.
At the end of the exchange, the bit ADJUST_ERR is set to 1 if the exchange was not carried out correctly. The READ_STS %CHxy.0 function is used to refresh the channel status.
It contains the following data: l COD_DESC_FLT: error code found by the module in a track adjustment data item.
l
NUM_DESC_FLT: codes the track number containing a description error.
NUM_GROUP_FLT: codes the group number which contains the track containing a description error.
COD_LOCAL_FLT: indicates an error in the group or track number.
154
TLX DS 57 PL7 xx
Programming
MOD_CAM: Adjusting a cam
General The MOD_CAM function is used to adjust a cam dynamically. Transferring new data does not require the cam processor to switch to STOP mode. If the transfer is successful, the new parameters are recognized by the module. If the transfer is not l l l successful, the cam processor remains in RUN mode with the old values.
The MOD_CAM function assigns the following parameters:
X1: Low threshold
X2: high threshold
TIME_SWITCH_OFF: time delay
Parameter buffer The exchange zone used by the MOD_CAM function is a buffer made up of reserved words: %MWxy.0.16 to %MW xy.0.18.
Loading the exchange zone
The exchange zone (buffer) can be preloaded: l with the initial adjustment values:
MOD_CAM %CHxy.0 (0,Group,Cam) l with the actual adjustment values:
MOD_CAM %CHxy.0 (1,Group,Cam)
Sending the new values to the module
After modification in the buffer, the function: l MOD_CAM %CHxy.0 (2,Group,Cam) action {Send} sends the new values to the module and updates the current parameters zone.
Key Group: identifies the group number
Cam: identifies the track number action {Get} action {Read}
TLX DS 57 PL7 xx
155
Programming
Initializing the parameter buffer action {Get} or action {Read
%KWxy.
Axis configuration
Axis processor configuration
Group configuration
Save initial adjustments
MOD_TRACK{Get}
Recipe
%MWxy.0.0
Axis adjustment
Cam program
MOD_CAM{Read}
%MWxy.0.16= X1
%MWxy.0.17= X2
%MWxy.0.18= TIME_SWITCH_OFF
Parameter buffer
Module
TSX
CCY 1128
Initializing the parameter buffer
For cam 9 in group 2: l l action {Read}: MOD_CAM %CHxy.0 (1,2,9) action {Get}: MOD_CAM %CHxy.0 (0.2,9)
156
TLX DS 57 PL7 xx
Programming
Sending the new recipe
Action {Send}
%KWxy.
Axis configuration
Axis processor configuration
Group configuration
Save initial adjustments
Modifications
%MWxy.0.0
ADJ_IN_PROGR
%MWxy.0.1
ADJUST_ERR
Recipe
%MWxy.0.0
Axis adjustment
Cam program
MOD_CAM {Send}
%MWxy.0.16= X1
%MWxy.0.17= X2
%MWxy.0.18= TIME_SWITCH_OFF
Parameter buffer
Module
TSX
CCY 1128
Cam processor in RUN mode)
Channel status
%MWxy.
COD_DESC_FIT
NUM_DESC_FLT
NUM_GROUP_FLT
READ_STS %CHxy.0
Example
Monitoring the exchange
For cam 9 in group 2: l action {Send}: MOD_CAM %CHxy.0 (2,2,9)
At the end of the exchange, the bit ADJUST_ERR is set to 1 if the exchange has not been carried out correctly. The READ_STS %CHxy.0 function is used to refresh the channel status.
l l
It contains the following data: l COD_DESC_FLT: error code found by the module in a cam adjustment data item.
NUM_DESC_FLT: codes the cam number containing a description error.
NUM_GROUP_FLT: codes the group number which contains the cam containing a description error.
l COM_LOCAL_FLT: indicates an error in the group or track number.
TLX DS 57 PL7 xx
157
Programming
TRF_RECIPE: Recipe transfer functions
General l l
An application program can use several recipes. These are contained in several memory zones. The TRF_RECIPE instruction is used to: transfer the contents of the current recipe to a memory zone.
transfer a recipe from a memory zone to the %MW zone containing the current recipe and transfer it to the module. In this case the cam processor switches to
STOP mode as for the WRITE_PARAM instruction.
Note: It is possible to save (Restore) one or more recipes to the memory zone in a paged PCMCIA using the WRITE_PCMCIA (READ_PCMCIA) instructions.
158
TLX DS 57 PL7 xx
Programming
TRF_RECIPE: Functions for storing recipes
%MW for the recipe
A recipe is stored in %MW words in this way (n is the value of the "ADR" parameter coded in the instruction TRF_RECIPE):
Details Group Word addresses Content Number of words
%MWn to %MWn+11 Adjusting the axis 12 words
%MWn+12 to
%MWn+27
Descriptor for tracks 0 to 7
16 words Group 0
%MWn+28 to
%MWn+187
Descriptor for cams 0 to 31
160 words
16 words l l l l l
SPECIF-TRACK track 0
ANTICIP-FACTOR track 0
...
SPECIF-TRACK track 7
ANTICIP-FACTOR track 7
Cam 0 l l l
SPECIF-CAM_0
SPECIF_CAM_1
TIME_SWITCH_OFF
Cam...
l ...
Cam 31 l l l
SPECIF-CAM_0
SPECIF_CAM_1
TIME_SWITCH_OFF see Group 0 Group 1 %MWn+188 to
%MWn+203
%MWn+204 to
%MWn+363
%MWn+364 to
%MWn+379
%MWn+380 to
%MWn+539
%MWn+540 to
%MWn+555
%MWn+556 to
%MWn+715
Descriptor for tracks 0 to7
Descriptor for cams 0 to 31
Descriptor for tracks 0 to 7
Descriptor for cams 0 to 31
Descriptor for tracks 0 to 7
Descriptor for cams 0 to 31
160 words
16 words
160 words
16 words
160 words see Group 0 see Group 0 see Group 0 see Group 0 see Group 0
Group 2
Group 3
TLX DS 57 PL7 xx
159
Programming
TRF_RECIPE: Loading a new recipe
Diagram showing loading
Loading is triggered by a call from the application program.
%MW0
%KWxy.
Axis configuration
Cam processor configuration
Group configuration
%MWx0
Recipe 0
%MWx1
Recipe 1
TRF_RECIPE (Load; adr)
Module
TSX
CCY 1128
(in STOP mode)
Current recipe
%MWxy.
Axis adjustment
Cam program
Save initial adjustments
Channel status
%MWxy.0.0
ADJ_IN_PROG
%MWxy.0.1
ADJ_ERR
%MWxy.
APPLI_FIT
COD_PARAM_FIT
COD_DESC_FIT
NUM_DESC_FLT
NUM_GROUP_FLT
READ_STS %CHxy.0
Example Loading defines the word %MW800.
Action {Load} TRF_RECIPE %CHxy.0 (0,800) or
%MW0:= 800; TRF_RECIPE %CHxy.0 (0,800)
160
TLX DS 57 PL7 xx
Exchange monitoring
Programming
During the transfer, the bit (x15) ADJ_IN_PROG is set to 1.
At the end of the exchange, the bit ADJUST_ERR is set to 1 if the exchange was not l l carried out correctly. The READ_STS %CHxy.0 function is used to refresh the channel status.
It contains the following data: l APPLI_FLT: the module has refused the new recipe. The cam function cannot be activated. However, the old parameters contained in the module can be restored by a READ_PARAM %CHxy.0 instruction.
l l
COD_PARAM_FLT: error code found by the module in the axis. part of a configuration or adjustment data item.
COD_DESC_FLT: error code found by the module in the track or cam descriptor part of a configuration or adjustment data item.
NUM_DESC_FLT: codes the track or cam number containing a description error.
NUM_GROUP_FLT: codes the group number which contains the track or cam containing a description error.
TLX DS 57 PL7 xx
161
Programming
TRF_RECIPE: Saving a new recipe
Diagram of a save operation
Saving a recipe:
%KWxy.
Axis configuration
Cam processor configuration
Group configuration
%MW0
%MWx0
Recipe 0
%MWx1
Recipe 1
Application
TRF_RECIPE [Save]
Save initial adjustments
Channel
Recipe
%MWxy.
Axis adjustment
Cam program
%MWxy.0.0
ADJ_IN_PROG
%MWxy.0.1
ADJ_ERR
%MWxy.
APPLI_FIT
COD_PARAM_FIT
COD_DESC_FIT
NUM_DESC_FLT
NUM_GROUP_FLT
READ_STS
Module
TSX
CCY 1128
(RUN or
STOP mode)
Example Transferring the recipe used in the module to the %MW800 table.
(* Action {Save} *) TRF_RECIPE %CHxy.0 (1,800); or
%MW0:= 800; TRF_RECIPE %CHxy.0 (1,%MW0);
162
TLX DS 57 PL7 xx
Exchange monitoring
Programming
During the transfer, the bit (x15) ADJ_IN_PROG is set to 1.
At the end of the exchange, the bit ADJ_ERR is set to 1 if the exchange was not l l carried out correctly. The READ_STS %CHxy.0 function is used to refresh the channel status.
It contains the following data: l APPLI_FLT: the module has refused the new recipe. The cam function cannot be activated. However, the old parameters contained in the module can be restored by a READ_PARAM %CHxy.0 instruction.
l l
COD_PARAM_FLT: error code found by the module in the axis part of a configuration or adjustment data item.
COD_DESC_FLT: error code found by the module in the track or cam descriptor part of a configuration or adjustment data item.
NUM_DESC_FLT: codes the track or cam number containing a description error.
NUM_GROUP_FLT: codes the group number which contains the track or cam containing a description error.
TLX DS 57 PL7 xx
163
Programming
DETAIL_OBJECT: Operator dialog interface
General
Function parameters
The DETAIL_OBJECT function facilitates the management and creation of a recipe using operator dialog. It gives the application program use of all the descriptive information for a track or a cam in a %MW memory zone selected by the programmer.
l l l l l l l l
DETAIL_OBJECT %CHxy.0 (ACTION, TYPE_OBJECT, NUM_GROUP,
NUM_OBJECT, ADR)
ACTION = 1: Ext is used to write the cam or track descriptor to a memory zone
Action = 0: Inc is used to write the cam or track descriptor with data to the memory zone.
type of object = 0: cam.
type of object = 1: track.
NUM_GROUP = number of the group to which the cam or track belongs.
NUM_OBJET = number of the cam or track in the group.
ADR = address of the first object in the memory zone.
164
TLX DS 57 PL7 xx
Programming
DETAIL_OBJECT: Transferring cam details
Diagram This diagram describes transferring cam details
%KWxy.
Axis configuration
Cam processor configuration
Save initial adjustments
Recipe
%MWxy.
Axis adjustment
Cam program
DETAIL_OBJET (1,0,.,.,.,)
Detail of cam descriptors
Module
TSX
CCY 1128
Example Breakdown of parameters for cam 9 in group 2 from address %MW100
DETAIL_OBJECT %CHxy.0 (1,0,2,9,100);
TLX DS 57 PL7 xx
165
Programming
Order in which cam parameters are stored
The parameters are stored in a %MW memory zone:
13
14
15
9
10
11
12
5
6
3
4
7
8
1
2
Position Meaning
0 bit 0 = 1 cam used type of cam bit 0 =1 enable in forward direction, bit 1 =1 enable in reverse direction reserved reserved reserved track number reserved cam monitoring selection code l l l
0 : still enabled
1 : confirmation bit condition
2 : counter full condition cam monitoring bit number reserved reserved
X1: low threshold
X2: high threshold delay value on opening reserved
166
TLX DS 57 PL7 xx
Loading cam details
Programming
The parameters are transferred into the recipe buffer from the memory zone
%KWxy.
Axis configuration
Cam processor configuration
Module
TSX
CCY 1128
Save initial adjustments
Recipe
%MWxy.
Axis adjustment
Cam program
DETAIL_OBJET (0,0,.,.,.,)
Detail of cam descriptors
Example
CAUTION
There is no consistency check at this level of transfer
Failure to observe this precaution can result in injury or equipment damage.
Loading the details of cam 3, group 2, into the current recipe
DETAIL_OBJECT %CHxy.0 (0,0,2,9,100);
TLX DS 57 PL7 xx
167
Programming
DETAIL_OBJECT: Transferring track details
Diagram This diagram describes transferring a track
%KWxy.
Axis configuration
Cam processor configuration
Save initial adjustments
Recipe
%MWxy.
Axis adjustment
Cam program
DETAIL_OBJET (1,1,.,.,.,)
Detail of cam descriptors
Module
TSX
CCY 1128
Example Breakdown of parameters for track 5 group 1 from address %MW200. Loading the details of cam 3, group 2, into the current recipe
DETAIL_OBJECT %CHxy.0 (1,1,1,5,100);
168
TLX DS 57 PL7 xx
Order in which track parameters are stored
The parameters are stored in a %MW memory zone:
3
4
5
1
2
Position Meaning
0 bit 0 = 1 track used
Output, bit 0: INVERT_TRACK, bit 1: ADD_TRACK
Action code for switching to 1 for parts counter in forward direction
Action code for switching to 0 for parts counter in reverse direction
= 1 track declared as event value of anticipation factor
Programming
TLX DS 57 PL7 xx
169
Programming
Loading track details
The parameters are transferred into the recipe buffer from the memory zone.
%KWxy.
Axis configuration
Cam processor configuration
Module
TSX
CCY 1128
Save initial adjustments
Recipe
%MWxy.
Axis adjustment
Cam program
DETAIL_OBJET (0.1,.,.,.,)
Details of track
Example
CAUTION
There is no consistency check at the level of this transfer
Failure to observe this precaution can result in injury or equipment damage.
Changing the details of track 5, group 1, in the current recipe from word %MW100
DETAIL_OBJECT %CHxy.0 (0,1,1,5,100);
170
TLX DS 57 PL7 xx
Performance and limitations
8
At a Glance
Object of this chapter
What's in this chapter?
This chapter describes the performances and limits of the electronic cam module.
This chapter contains the following topics:
Topic
Global precision in controlling the actuators
Actuator commands
General time-division performance characteristics
Functional limitations
Page
171
TLX DS 57 PL7 xx
Performance and limitations
Global precision in controlling the actuators
General Precision in controlling actuators in relation to the target mechanical position is linked to three factors: the resolution of the encoder, the speed and the reaction time of the module.
The resolution of the encoder
For a target precision of 0.1mm, the encoder should produce at least one or two pulses for 0.1mm.
l l
Caution: depending on the configuration selected, the resolution must be taken into account: after multiplying by 4 for an incremental encoder after reducing the resolution for an absolute encoder
Speed For the required position, and depending on the approach speed, the system should have a maximum reaction time.
Example: reaction time required for a target precision of 1mm.
Using the cam module in an application is justified for speeds between 10 and 300m/ min.
Linear speed
Reaction time on output command
10 m/min 300 m/min
PLC architecture
6 ms
CCY 1128 application
0.2 ms
Other
For a movement speed of<10 m/min, the entire application could be handled by a
TSX PLC.
The minimum reaction time of the CCY 1128 module is 0.2ms, the maximum movement speed is therefore 300m/min.
172
TLX DS 57 PL7 xx
Structural diagram of cam processing
Performance and limitations
The TSX CCY 1128 cam module optimizes its reaction time for controlling outputs depending on the parameters configured for the application.
Precision of the machine axis
Encoder Pulse period
1 /
ω x resolution
ω
: rotation speed
In
Acquisition loop 0 µs = counting
50 µs: = SSI
100 µs: = SSI
200 µs: = SSI
Calculation loop
Internal module reaction time
Anticipation
50 µs: < = 16 cams
100 µs: < = 64 cams
200 µs: < = 128 cams
Propagation time:
< 150 µs
Output
Out
Reaction time linked to the machine
Actuators
...ms
TLX DS 57 PL7 xx
173
Performance and limitations
Acquisition loop The duration of the acquisition loop corresponds to the cycle for reading the absolute encoder via its SSI link. It is always synchronous with the calculation loop. The reading period is configurable (50 micro seconds, 100 micro seconds, 200 micro seconds).
The value selected must be dependent on the length of the SSI frame (number of bits), and the distance (l) between the encoder and the module.
Number of bits in the frame length
Calculation loop For an SSI encoder, the calculation period is optimized according to the number of cams configured, but cannot be less than the reading period.
For example: if T1 = 100 micro seconds then T2 = 100 micro seconds for a configuration of between 1 and 32 cams, T2 = 200 micro seconds for a configuration of between 33 and 128 cams.
Anticipation function
The output refresh period is fixed by the calculation loop:
With the incremental encoder, it is automatically fixed by the module depending on the number of cams used by the cam program (50 micro seconds up to 16 cams,
100 micro seconds up to 32 cams, 200 micro seconds up to 128 cams).
This is used to compensate for the fixed delay introduced by the actuator and its associated mechanics. The calculation loop ensures that the anticipation value for switching each output is updated.
174
TLX DS 57 PL7 xx
Performance and limitations
Actuator commands
Estimating precision for controlling actuators
The global communication delay of an output in relation to the crossing of a mechanical threshold depends on the application. It may be divided into two parts: l Minimum delay: is a constant part corresponding to the time necessary to set the outputs.
l Max/min delay: a variable part corresponding to the "jitter" brought by the periodicity of the refreshing of outputs. Internal module synchronization is such that the variable part is reduced to the influence of T0 (period between two encoder pulses) and of T2 (calculation period).
Minimum delay (1) in incremental encoder in absolute encoder
= T2+T3
= T1 + T2 + T3
Maximum / minimum delta (2) without anticipation with anticipation of the SSI with anticipation of the incremental
= T0 + T2
= 2 x (T0 = T2)
= 2 x T0 = T2
TLX DS 57 PL7 xx
175
Performance and limitations
Precision in output control
The switching delay on outputs causes an error in relation to the target threshold.
Illustration of the use of the without anticipation function
Position
4
3
Target threshold
Switching zone
Output
Time
1
2
3
4
1
2
The switching zone deviates from the target threshold proportionally to the speed.
Switching can be reset around the threshold using the anticipation system. To do this, simply add to the anticipation value = minimum delay (1 + 1/2 delta delay (2).
Minimum delay
Maximum / Minimum delay
Fixed deviation
Delta switching
176
TLX DS 57 PL7 xx
TLX DS 57 PL7 xx
Illustration of the use of the with anticipation function
Position
Performance and limitations
Target threshold
Switching zone
Output Time
Anticipation
Caution: To make a valid correction to the delay caused by the module, the encoder resolution should be 2 to 5 times more precise than that which was estimated at the first attempt.
177
Performance and limitations
Calculation chart The tables below show the foreseeable errors depending on the application type and for a reference speed of 120m/min. Values for other speeds can be obtained by a simple rule of three.
Fixed deviation for a speed of 120 m/mn (encoder resolution = 0.1 mm)
Calculation No. of cams
50 (1) up to 16
100 (1)
200 (1) up to 32 up to 128 incremental
0.4 mm
0.5 mm
0.7 mm
SSI 50 (1)
0.5 mm
0.6 mm
0.8 mm
SSI 100 (1)
-
0.7 mm
0.9 mm
SSI 200 (1)
-
-
1.1 mm
Delta switching for a speed of 120 m/min without anticipation (encoder resolution
= 0.1 mm)
Calculation No. of cams
50 (1) up to 16
100 (1)
200 (1) up to 32 up to 128 incremental
0.2 mm
0.3 mm
0.5 mm
SSI 50 (1)
0.2 mm
0.3 mm
0.5 mm
SSI 100 (1)
-
0.3 mm
0.5 mm
SSI 200 (1)
-
-
0.5 mm
1 Values are expressed in micro seconds.
WARNING
The variation in communication (Delta switching) is increased if the anticipation system is used.
Failure to observe this precaution can result in severe injury or equipment damage.
178
TLX DS 57 PL7 xx
Performance and limitations
General time-division performance characteristics
Calling an event task
Diagram of an event task call
Source Event
Module 1 ms 1 ms
System
Application t event transmission
< 1 ms
Event task call
EVT
%I
EVT
%Q
The module includes 7 event sources (capture, cycle switching, cam ....).
The calling of event tasks is limited to a maximum of 1 event per ms.
Only one type of event is sent at a time to the system.
In the case of one event
The start of the event task is executed no more than 3 ms after the real event (e.g.: switch to cycle modulo).
In the case of several simultaneous events
The module integrates a buffer that allows the storing up to 7 events awaiting transmission to the system. The events will be sent in their order of arrival (1 per ms).
This, therefore, increases the reaction time.
TLX DS 57 PL7 xx
179
Performance and limitations
Table Description of the functions
Function
Counter
Recalibration
Cam function
Implicit interface
Explicit interface
Additional cycle time
Comments
Permitted frequency
Activation of the event task on switching of cycle
Recalibration of counter on Z marker pulse
Recalibration of counter on Irec
Event task activation
Refreshing output
Updating the correction values
(anticipation)
Activating the event task (cam, parts counter)
Influence of the module on the processor cycle time
Refreshing %I and %IW
Recognizing %Q and %QW
WRITE_PARAM
SAVE_PARAM
RESTORE
READ_STS
MOD_PARAM
MOD_CAM
MOD_TRACK
TRF_RECIPE
DETAIL_OBJECT
The cycle time has no effect on the output reaction time
Value
500Khz in x1
250Khz in x4
< 3 ms
< 1 micro second
< 50 micro seconds
< 3 ms
50 micro seconds up to 16 cams
100 micro seconds up to 32 cams
200 micro seconds up to 128 cams
< 4ms
< 3 ms
< 1 ms
< 1 ms
300 ms
300 ms
300 ms immediate (1) send: 20 ms (2) send: 20 ms (2) send: 20 ms (2)
300 ms immediate (1)
1 ms
(1) There is no access to the module / Execution time is included in the task execution.
(2) For GET and READ it is immediate as in (1).
180
TLX DS 57 PL7 xx
Performance and limitations
Functional limitations
Correction of axis play
Example
Reverse
IREC
Dmin (Pr+)
Tmin
(Pr-) Dmin
Forward
The application for correcting axis play allows you to to obtain a positioning of the cams on a mechanical position whatever the direction.
In the example, recalibration is done in a backwards direction. The actual mechanical position is the value delivered by the encoder in the backward direction and the corrected value in the forward direction (end).
A safety distance (Dmin) is necessary between the position of the cames and the points of return. (Pr+ and Pr-). This distance corresponds to the value of axis play that is given when the adjusting the track.
In addition, the actual application of the correction (in forward direction in the example) is effective 4 ms after the change in direction. Also the cams must be positioned in such a way that the direction of development is correctly established:
4 ms (Tmin) before the switch to the first cam.
TLX DS 57 PL7 xx
181
Performance and limitations
Anticipation Example with anticipation
Tmin
With anticipation
(Re)Start
Forward
Cam switching is anticipated (in time) in relation to the actual crossing of thresholds.
The value is fixed by the anticipation factor (T anticip = n x 50 microseconds).
Following a (re)start or a change of direction, there is a delay (Tmin) until anticipation is applied. For correct operation, the first cam switch should not be expected before this delay.
T min = 2 x ( T anticip + 4 ms)
The delay required for the axis to reach speed can be added to t min to increase precision.
182
TLX DS 57 PL7 xx
Diagnostics
9
At a Glance
Object of this chapter
What's in this chapter?
This chapter describes the error codes and relevant status words of the electronic cam
This chapter contains the following topics:
Topic
Module level status
Status of channel level
Error codes
Controls
Checking the integrity of the module
Monitoring the encoder
Checking auxiliary inputs
Monitoring track outputs
Questions and Answers
Page
183
TLX DS 57 PL7 xx
Diagnostics
Module level status
Module status objects
Method
These objects are common to all the modules in the range.
Object
%Ixy.MOD.ERR
%MWxy.MOD.2
Symbol
MOD_FAULT
FAULTY_MOD
FAULTY_CH
MOD_CNF_FLT
MISSING_MOD
Meaning module fault bit x0 = 1 internal fault: module failure x1 = 1 channel functional fault (see channel status) x2 to x4 reserved x5 = 1 configuration fault: difference between the value configured and that read x6 = 1 module missing or switched off x7 = reserved
They give information about the module status.
Value %MWxy.MOD.1 is updated again by an explicit command:
READ_STS %CH xy .MOD
If %Ixy.Mod.Err = 1 (default), perform the READ_STS command.
184
TLX DS 57 PL7 xx
Diagnostics
Status of channel level
Aperiodic status This data allows module diagnostics. Faults may be internal or external to the module.
Object
%Ixy.0.ERR
%MWxy.0.0
%MWxy.0.1
%MWxy.0.2
Symbol
Track_FAULT
EX_STS
STS_IN_PROG
ADJ_IN_PROG
RECNF_IN_PROG
EX_RPT
ADJUST_ERR
RECONF_ERR
CH_STS
ENC_FLT
AUXIL_FLT
TRACK_FLT
INTERNAL_FLT
CONF_FLT
COMMUNIC_FLT
APPLI_FLT
CH_LED
ENC_SUPPLY_FLT
ENC_WIRE_FLT
ENC_TRANSMIT_FLT
AUX_SUPPLY_FLT
C0_SUPPLY_FLT
C1_SUPPLY_FLT
Meaning group 0 fault bit exchange status management x0 = 1 channel status reading in progress x1 reserved x2 = 1 function: WRITE_PARAM, MOD_PARAM, MOD_TRACK,
MOD_CAM, TRF_RECEIPT in progress.
x3 to x14 reserved x15 = 1 reconfiguration in progress exchange report status x0 to x1 reserved x2 = 1 error on a communication function: WRITE_PARAM,
MOD_PARAM, MOD_TRACK, MOD_CAM, TRANF_RECEIPT.
x3 to x14 reserved x15 = 1 reconfiguration fault channel status x0 = 1 external fault: encoder supply fault x1 = 1 external fault: auxiliary inputs supply fault x2 reserved x3 = 1 external fault: tracks outputs fault x4 = 1 internal fault: internal module fault or module self-tests running x5 = 1 module hardware configuration fault or software configuration different to that expected x6 = 1 communication fault x7 = 1 error on a piece of data in recipe x8 and x9 state of the LED channel x10 = 1 encoder supply fault x11 = 1 encoder line fault x12 = 1 SSI Frame transmission fault (parity or format) x13 = 1 auxiliary inputs supply fault x14 = 1 connector 0 supply fault x15 = 1 connector 1 supply fault
TLX DS 57 PL7 xx
185
Diagnostics
Object
%MWxy.0.3
%MWxy.0.4
%MWxy.0.5
%MWxy.0.6
%MWxy.0.7
%MWxy.0.8
to
%MWxy.0.11
Symbol
EXTEN0_FLT
COD_PARAM_FLT
COD_DESC_FLT
Meaning channel status (specific) x0 to x5 error code for axis configuration or adjustment fault.
x6 to x11 error code for track or cam description fault x12 = 1 fault delivered by the SSI encoder x13 to x15 reserved
ENC_ALARM
EXTEN1_FLT
NUM_DESC_FLT
NUM_GROUP_FLT
COD_LOCAL_FLT channel status (specific) x0 to x4 order number of the faulty track or cam x5 to x6 group number of the faulty track or cam x7 to x8 reserved x9 to x15 error code for transfer of recipe data:
16#01 = the address specified does not exist
16#02 = the group specified does not exist
16#03 = the track specified does not exist
16#04 = the cam specified does not exist
16#05 = the action code specified does not exist
16#06 = the type of object does not exist reserved
C0_SHORT_CIRCUIT short-circuit fault on connector 0
16#0000 no fault
16#0001 short-circuit on group 0 tracks
16#0100 short-circuit on group 1 tracks
16#0101 short-circuit on group 0 and group 1 tracks
C1_SHORT_CIRCUIT short-circuit fault on connector 1
16#0000 no fault
16#0001 short-circuit on group 2 tracks
16#0100 short-circuit on group 3 tracks
16#0101 short-circuit on group 2 and group 3 tracks reserved
Method
The value of the %MW objects is updated by the READ_STS %CHxy.0 command.
If %Ixy.Mod.Err = 1 (default), perform the READ_STS command.
186
TLX DS 57 PL7 xx
Diagnostics
Error codes
Error codes In the channel periodic status word %MWxy.0.3, bits x0 à x5 are used to code the configuration or adjustment errors for the axis, and bits x6 à x11 code the description errors for a track or a cam. A symbol is associated with each error code.
COD_PARAM_FLT: error code for axis configuration or adjustment error
19
20
21
22
15
16
17
18
23
24
11
12
13
14
7
8
9
10
5
6
3
4
1
2
Code Faulty parameters
0 No error
EVT_ENABLE is not 0,1,or 255
EVT_NUM is not between 0 and 63
INPUT_MOD is not 0 (inc) or 1 (abs)
Reserved field is not at 0
FORMAT_MEAS is not 0,1 or 2
PRESET_MOD is not 0,1,2, or 3
CAPTS_MOD is not 0,1,2, or 4
Conf: Reserved field is not at 0
Conf: Reserved field is not at 0
Conf: Reserved field is not at 0
WITH_ERR is not zero - in incremental encoder
ABS_ENC_ERROR_RANGE is not zero - in incremental encoder
ABS_ENC_READ_PERIOD is not zero - in incremental encoder
CAPTS_MOD is not zero - in absolute encoder
25
26
ABS_ENC_READ_RANGE is greater than or equal to the number of status bits
ABS_ENC_READ_RANGE is at 0
ABS_ENC_READ_PERIOD is not 0,1 or 2 - in absolute encoder
ABS_ENC_READ_PERIOD - 50 micro – incompatible with frame length
ABS_ENC_READ_PERIOD incompatible with frame length
ABS_ENC_READ_EXTRA_NB - number of header bits is too big (0.4 allowed)
ABS_ENC_READ_EXTRA_NB - number of status bits is too big (0.3 allowed)
ABS_ENC_EXTRA_NB is at 0 – incompatible with WITH_ERR
ABS_ENC_DATA_NB - number of data bits is greater than 25
ABS_ENC_DATA_NB + ABS_ENC_READ_EXTRA_NB + WITH_PAR is greater than 32
PRESET_ANG_VALUE is greater than RESOL_ANG
PRESET_TURN_VALUE is greater than RESOL_TURN
TLX DS 57 PL7 xx
187
Diagnostics
46
47
48
49
50
42
43
44
45
38
39
40
41
34
35
36
37
29
30
31
32
33
Code Faulty parameters
27
28
SLACK_VALUE less than -1023
SLACK_VALUE greater than 1023
SLACK_VALUE greater than (RESOL_ANGL * RESOL_TURN)
SLACK_VALUE greater than RESOL_ANG/2
ABS_REDUC is at 0
ABS_REDUC is not 1,2,4,8,16 or 32
(ABS_REDUC*RESOL_ANGL*RESOL_TURN) greater than
ABS_ENC_DATA_NB
ABS_OFFSET_ANG greater than RESOL_ANGL
ABS_OFFSET_TURN greater than RESOL_TURN
RESOL_ANGL is not a power of 2 - in absolute encoder
Param: Reserved field is not at 0
PRESET_ANG_VALUE(adjustment) is greater than RES_ANG
PRESET_TURN_VALUE (adjustment) is greater than RES_TURN
SLACK_VALUE (adjustment) less than -1023
SLACK_VALUE (adjustment) greater than 1023
SLACK_VALUE (adjustment) greater than (RESOL_ANGL * RESOL_TURN)
SLACK_VALUE (adjustment) greater than RESOL_ANG/2
ABS_ENC_DATA_NB less than 8
RESOL_ANGL less than 256
INPUT_MOD (encoder) incompatible with FORMAT_MEAS
MAX_PIECES is less than 1
MAX_PIECES is greater than 32767
MAX_PIECES (adjustment ) is less than 1
MAX_PIECES (adjusted ) is greater than 32767
188
TLX DS 57 PL7 xx
List of track or cam error codes
COD_DESC_FLT: error code for track or cam description fault
12
13
14
15
8
9
10
11
6
7
4
5
1
2
Code Faulty parameters
0 No error
TYP_PROFIL unknown cam code
TYP_PROFIL unknown cam code
Cam: Reserved field is not at 0
Cam: Reserved field is not at 0
TRACK_NUM is greater than 7
COND_ENABLE is not at 0,1,2
BIT_NUM_ENABLE impossible
Cam: Reserved field is not at 0
X1 is greater than RESOL_ANG
X2 is greater than RESOL_ANG
TIME_SWICH_OFF is not at 0
X2 is not at 0
TIME_SWITCH_OFF is greater than 16383
Cam: Reserved field is not at 0
35
36
48
49
16
32
33
34
Cam: Reserved field is not at 0
Track: Reserved field is not at 0
Track: Reserved field is not at 0
ADD_TRACK on track 4 to 7
ANTICIP_FACTOR greater than 32767
ANTICIP_FACTOR is not at 0 – logical track
USED_CAM (adjustment) the cam has not been declared
X1(adjustment) is more than RESOL_ANG
50
51
52
53
X2 (adjustment) is greater than RESOL_ANG
TIME_SWITCH_OFF(adjustment) is not at 0
X2 (adjustment) is not at 0
TIME_SWITCH_OFF (adjustment) is greater than 16383
58
59
USED_TRACK (adjustment) the track has not been declared
ANTICIP_FACTOR (adjustment) greater than 32767
60 ANTICIP_FACTOR (adjustment) is not at 0 – logical track
Code Faulty parameters
TLX DS 57 PL7 xx
Diagnostics
189
Diagnostics
Controls
General
Display on module front panel l l l l l l l
The system checks that a module really is in good working order and is capable of performing the designated function.
The module tests its main components.
Checks correct operation of the internal self-tests performed on cold or warm restart of the internal software.
Checks communication between the cams module and the processing unit.
Checks supply and connection of the encoder.
Checks auxiliary inputs supply.
Checks track outputs.
The display on the module front panel shows the module operating status. The information is laid out in the following arrangement:
CH0 RUN ERR
I/O
On power-up, if CH0 and RUN light up green, the module has not detected any errors and is ready to operate.
The CH0 light is lit (green)
The RUN light is lit (green)
190
TLX DS 57 PL7 xx
Diagnostics
Checking the integrity of the module
Internal error Example
The ERR light is lit (red)
When the bit %Ixy.MOD.ERR = 1, the READ_STS %CHxy.MOD instruction is used to refresh the status, and you will find: FAULTY_MOD = 1
The outputs are guaranteed at 0V.
Communication error towards the module
For example, due to a break in the X bus linking the extension rack in which the module is located.
TLX DS 57 PL7 xx
The ERR light flashes (red)
The RUN light is lit (green)
The CH0 light flashes (green)
When the bit %Ixy.MOD.ERR = 1, the READ_STS %CHxy.MOD instruction is used to refresh the status, and you will find: FAULTY_MOD = 1
When the bit %Ixy.MOD.ERR = 1, the READ_STS %CHxy.MOD instruction is used to refresh the status, and you will find: COMMUNIC_FLT = 1 or INTERNAL_FLT =1.
The status of the outputs depends on the configuration selected (cam processor configuration).
191
Diagnostics
Monitoring the encoder
At a Glance Conitinous monitoring of the configured encoder is performed.
Monitoring the supply to the encoder: the real voltage applied to the encoder is measured.
Line monitoring: if requested during configuration, line breaks and short-circuits are detected by measuring the differential voltage on the encoder connection lines.
Monitoring transmission: two checks are made on the SSI link with the encoder.
A parity check if requested during configuration. An answer present check.
Encoder alarm: some SSI encoders bring up error data in the serial link frame. The module transmits the data, if requested during configuration, to the application software.
Signaling:
The ERR light (red) is off
The RUN light (green) stays lit
The CH0 light (green) flashes
The I/O light (red) is on
192
TLX DS 57 PL7 xx
Consequences of an encoder fault
Diagnostics
If the encoder power supply voltage is too low, if there is a line fault or if a transmission fault is detected: l Position reading is no longer ensured: data ANG_OK = 0 l The cam processor is switched to STOP mode: data PCAM_ON = 0
For an ALARM_CODEUR error, the module proceeds with processing as normal, the processor remains in RUN mode.
Bit %Ixy.MOD.ERR = 1. The READ_STS %CHxy.MOD instruction is used to refresh the status, and you will find: l FAULTY_CH =1
Bit %Ixy.0.ERR = 1. The READ_STS %CHxy.0 instruction is used to refresh the status, and you will find: l l l l
ENC_FLT = 1 and
ENC_ALARM = 1 if data is detected in the SSI frame
ENC_TRANSMIT_FLT = 1 if an SSI frame error is detected
ENC_WIRE_FLT = 1 if a line fault is detected l Enc_Supply_Flt = 1 if the encoder is incorrectly supplied
If encoder supply fault masking has been configured (supply ENC_MSK = 1) then
%IWxy.MOD.ERR, %IWxy.0.ERR and ENC_FLT will not change to 1 on an encoder supply fault.
TLX DS 57 PL7 xx
193
Diagnostics
Checking auxiliary inputs
At a Glance
Consequences of the supply fault
Auxiliary inputs supply fault
The 24 V voltage on the auxiliary I/O connector is monitored. A fault occurs if the voltage is less than 19V.
If the 24V power supply is too low (<19V): l l
Position reading is no longer ensured: data ANG_OK = 0
The cam processor is switched to STOP mode: data PCAM_ON = 0
Signaling: l l l l
The ERR light (red) is off
The RUN light (green) is on
The CH0 light (green) lashes
The I/O light (red) is on
Bit %Ixy.MOD.ERR = 1. The READ_STS %CHxy.MOD instruction is used to refresh the status, and you will find: l FAULTY_CH =1
Bit %Ixy.0.ERR = 1. The READ_STS %CHxy.0 instruction is used to refresh the status, and you will find: l AUX_FLT = 1 and l AUX_SUPPLY = 1 if the encoder is incorrectly supplied
If auxiliary inputs supply fault masking has been configured (SUPPLY_AUX_MSK) then: %IWxy.MOD.ERR, %IWxy.0.ERR and AUX_FLT will not be switched to 1 on an encoder supply fault.
194
TLX DS 57 PL7 xx
Diagnostics
Monitoring track outputs
At a Glance
Consequences of the fault
The 24V voltage is monitored on each of the track output connectors. A fault occurs if the voltage is less than 19V. The check is only made if the connector is unlocked.
Each output has a current limiting system (from 0.7 to 2 A). In the event of prolonged overcurrent, thermal tripping occurs.
For a supply fault to one of the connectors, the cam processor is set to STOP mode.
For a short-circuit fault on one of the track outputs, all the connector outputs are set to 0V.
Depending on the selected configuration of the "cam processor": l If the processor ignores short-circuit faults (CP_IGN_SC= 1) then the processor remains in RUN mode.
l Otherwise the processor is set to STOP mode.
If automatic reset is required (REARM_MOD =1), resetting of the faulty connector is automatic after 10s or else the fault must be acknowledged by the command
C0_REARM or C1_REARM according to the connector.
TLX DS 57 PL7 xx
195
Diagnostics
Track output faults
Signaling: l l l l
The ERR light (red) is off.
The RUN light (green) is on.
The CH0 light (green) flashes.
The I/O light (red) is on.
Bit %Ixy.MOD.ERR = 1. The READ_STS %CHxy.MOD instruction is used to refresh the status, and you will find: l FAULTY_CH =1
Bit %Ixy.0.ERR = 1. The READ_STS %CHxy.0 instruction is used to refresh the status, and you will find: l l l l l l l
TRACK_FLT = 1 and
C0_SUPPLY_FLT = 1 if connector 0 is incorrectly supplied
C1_SUPPLY_FLT = 1 if connector 1 is incorrectly supplied
C0_SHORT_CIRCUIT = 1 if an output in group 0 has short-circuited
= 256 if an output in group 1 has short-circuited
C0_SHORT_CIRCUIT = 1 if an output in group 0 has short-circuited
= 256 if an output in group 1 has short-circuited
If track output supply fault masking has been configured (SUPPLY_TRACK_MSK =
1) then %IWxy.MOD.ERR, %IWxy.0.ERR and TRACK_FLT will not change to 1 on a connector supply fault.
196
TLX DS 57 PL7 xx
Diagnostics
Questions and Answers
List Table of malfunctions
Malfunction
The cam processor does not switch to RUN mode
The cam processor changes to stop mode without modifying bit
%Qxy.0.5
(PCAM_START_STOP)
No action on the outputs
Loss of modifications to the current recipe
Following modification to the configuration, the browser turns red and it is not possible to confirm the configuration l l l
Possible causes l The module has not been recalibrated (bit
%Ixy.0.0.i=0).
There is no encoder supply
Lack of auxiliary input supply
CAUTION: If the faults have been masked, a fault can prevent the switch to RUN mode without appearing!
l l l l
Loading a recipe using the commands l l l
WRITE_PARAM
RESTORE_PARAM
TRF_RECIPE
The outputs are already valid OUTS_ENABLE
Parallelization of a track without configured cam
Forced outputs
Inverted outputs
When switching to local mode, if the save has not been done when adjusting the recipe
A parameter is no longer compatible with the new configuration l l l l
Switch to recipe adjustment
Click on No when requested to confirm
Modify the parameter
Confirm
TLX DS 57 PL7 xx
197
Diagnostics
198
TLX DS 57 PL7 xx
Glossary
A
Absolute encoder
Acquisition
Adjusting the
Recipe
Alternating movement
Angle reading
Anticipation
Axis
This type of encoder directly delivers the numeric value of the axis position. The position reading is kept in case of power outage.
Module functions that are used to calculate the position reading of the machine.
Adjusting the recipe is a PL7 facility that allows modification of the parameters of a recipe element (axis, cam or track) in connected mode. Modifications done under recipe adjustment do not stop the cam processor.
This is a typical movement for hydraulic presses and transfer machines. The axis describes a to and fro movement in a pulses domain equal to or less than the value of the cycle.
The "reading format" is type 1. The arrival of parts is synchronized by the machine
(Machine Synchro).
This is the instant position value of the axis in the cycle. This value is expressed as a number of pulses.
Cam processor function that is used to compensate for the delay caused by the machine’s actuators.
The anticipation value is applied to all changes of track status. It is specified by the
"anticipation factor" defined in the recipe parameters (value between 0 and 32 767 x 50 micro seconds).
These are all the external elements that control the movements of the machine
(reducer, encoder…).
TLX DS 57 PL7 xx
199
Glossary
Axis play This is the position error caused by the axis according to the direction of movement.
The cam processor can compensate for this error. The value of axis play is supplied in a configuration parameter.
C
Cam
Cam descriptor
Cam processor
Cam program
Capture
Cold restart
Communication fault
Configuration
Logic state which switches to 1 when an angular value in the cycle is overshot and which resets to 0 according to the type of cam.
A cam is systematically associated to one and only one track. Several cams can be associated to one track.
Part of the cam program that characterizes a cam (number of associated track, thresholds, type, confirmation condition, etc.).
This is the part of the module that directly controls the outputs according to the angle reading and according to the cam program supplied with the module.
This is all the internal data that defines the activation of the outputs according to the position reading of the axis. The cam program represents the most important part of the recipe.
A module function that is used to sample the position value of the axis on detection of a precise event (input Icapt0 and/or Icapt1). The capture has no impact on the values of the axis nor on the cam processor.
The implementation of this function allows the application to manage the process better, for example: in monitoring the number of pulses sent by the encoder, the size of the parts, the axis slip, the angle of arrival of the parts.
The module is initialized with current configuration and adjustment parameters.
This happens after the PLC supply has been cut or the supply has been reset or the module has been disconnected.
The module will execute the recipe in operation before the Reset.
Fault detected by the module when periodic exchanges with the PLC processor are no longer made.
The configuration gathers together the data which characterizes the machine
(invariant) and which is necessary for the TSX CCY 1128 module to operate.
All this information is stored in the PLC %KW constants zone. The PLC application cannot modify them.
200
TLX DS 57 PL7 xx
Continuous movement
Cycle
Cyclical movement
Glossary
This is the movement typical of conveyor belts. Theoretically the cycle is infinite. In fact, the limit for this module is 32768 pulses. The axis must be recalibrated when each part arrives (Part Synchro).
The "reading format" is type 3.
Area in which the action of the outputs can be programmed.
Caution: A complete cycle of the machine (machine cycle) must be a whole number of cycles.
This is the typical movement for packaging machines. The axis describes several cycles to carry out all the operations on a part. The direction of movement is usually constant.
The "reading format" is type 2. The arrival of parts is synchronized by the machine
(Machine Synchro).
D
Debugging
Deviation angle
Debugging is a PL7 facility that allows direct monitoring of the module in connected mode.
This is the axis position reading, taken each time it passes machine zero. This function for measuring axis slip can be accessed via the capture function.
E
Encoder Position sensor accepted by the module It can be incremental, SSI absolute or parallel (via Telefast ABE 7CPA11).
F
Filtering Filtering allows better environmental handling (for difficult environments). It is a filter that limits the bandwidth of counting signals which come from an incremental encoder.
With filtering the permitted frequency (before multiplying by 4) is 125 KHz, as against
250 KHz without filtering.
TLX DS 57 PL7 xx
201
Glossary
G
Gray code A binary code known as reflected, in which the change from term n to term n+1 is carried out by changing only a single digit, and so the code can be read unambiguously.
I
Incremental encoder
Pulse generator with 2 signals offset by 90°. These are produced according to the movement of the axis and are counted by the module.
L
Line monitoring System of monitoring the connection lines with the encoder. It detects breaks and short circuits between signals in the cable.
M
Machine cycle All of the cycles necessary to effect a complete operation of the machine.
Machine synchro Synchronization is carried out on a physical reference of the machine called
"Machine zero".
In this case the mechanism must control the arrival of the parts in the cycle. Each part will have to arrive for the same angle value, but you will always be able to find several parts on the machine at the same time.
Machine zero This is the mechanical reference position of the machine.
Measurement format
Defines the format for the axis position reading calculated by the module. It depends on the type of machine.
202
TLX DS 57 PL7 xx
Glossary
O
Offset
Operating mode
Output fallback
This is the rough value delivered by an absolute encoder to the machine zero.
By completing the adjustment parameter "Offset encoder", it is possible to set the angle value of the axis to 0 on the machine zero position.
These are all the rules that govern the performance of the module during transitory phases or when an error appears.
This is the behavior of the outputs under different errors: l If an electrical fault is detected on a connector (short circuit or supply under l voltage).
l All faulty connector outputs switch to 0V.
l Direct commands continue to be applied on the outputs of the other connector.
The cam processor can be set to Stop (according to the configuration).
If communication between the module and the central unit is defective.
l l The cam processor can be set to Stop (according to the configuration) l Direct commands continue to be applied or not (according to the configuration)
If the cam processor is in Stop mode.
l l
The tracks are set to logical 0.
The outputs can no longer be conditioned except by direct commands and INV information set at configuration.
l If the module is not configured (RUN light is out), the outputs are at 0V.
P
Part synchro Synchronization is carried out when each part arrives.
In this case parts can arrive at random on the machine, but the tool box can only handle one part at a time.
Pulses per cycle This is the number of pulses delivered by the axis per cycle.
In relation to the encoder resolution, this adjustment parameter must be considered: l l after multiplying by 4 for an incremental encoder after reducing the resolution for an absolute encoder.
TLX DS 57 PL7 xx
203
Glossary
R
Reading inversion
Recalibration
Recipe
Reducing the resolution
Resetting
Resolution
Rotating movement
This function allows the module to adapt itself to the type of mechanical mounting of the encoder on the axis.
This is the module function which is used to adjust the axis in relation to the machine zero or to synchronize the axis in relation to the arrival of a part.
Recalibration forces the position reading to a value which is predefined by the
"recalibration value" parameter (included in the pulse field of the cycle).
The module allows recalibration to be carried out systematically for each cycle or for only one cycle. This recalibration is always conditioned to the IREC input.
The recipe groups together the data required for the module to control the machine for a series of parts. The recipe can be modified or completely changed by the PLC application. All this information is contained in the PLC %MW words in the memory zone reserved for the module.
This function is used to divide the position value delivered by an absolute encoder via the "resolution reduction factor" by 2, 4, 8, 16 or 32.
Module function that allows a return to normal for the outputs after the outputs have been tripped.
The reset mode can be configured as "Manual" or "Automatic": l In "Manual", resetting is conditioned by a command bit controlled by the application.
l In "Automatic", resetting is carried out 10 seconds after the trip.
this is the smallest variation of input information which gives a measurable piece of output information.
This is a typical movement for mechanical presses and punching machines. The axis describes a complete cycle to carry out all the operations on a part. The direction of rotation is constant.
The "reading format" is type 1. The arrival of parts is synchronized by the machine
(Machine Synchro).
S
Short circuit fault The module includes a thermal circuit break system for the module's 24 V outputs.
204
TLX DS 57 PL7 xx
Slipping
SSI encoder
Synchro
Glossary
This system shows up a "short circuit fault".
Before a break, the short circuit current is limited to 1.5 A. The 24 V supply must be able to cope with this overload without a drop in voltage so that the rest of the application is not disrupted if there is an output fault.
This is the error of pulse loss in a cycle. This can be caused by the mechanical transmission of the axis. The module allows measurement of this slip (see:
"deviation angle").
Synchronous Series Interface link This is the standard connection protocol for absolute encoders that is used by the module.
l l
The transmission frequency is set by the module according to the following configuration parameters:
Number of bits making up the frame,
Reading period (50, 100 or 200 micro seconds).
"Part synchro", "Machine synchro": these are the two main modes of synchronization of the axis (which brings the parts in) in relation to the tool box. One or other of them is used according to the type of application.
Synchronization is necessary with an incremental encoder.
T
Top dead center With mechanical presses, you find a zone in the cycle which is called TDC. It is in this zone that the machine can and must be stopped. The "brake" cam is specially designed to deal with this problem.
Track This is the logic state which can be applied to the physical output. The maximum number of tracks is 32.
Track descriptor Part of the cam program that sets the parameters for the functions associated with a track (anticipation factor, generation of an event, evolution of the parts counter).
Turn pulse marker
Type of cam
Type of movement
A pulse supplied by a rotary incremental encoder, detected on each complete turn of the axis.
Essential feature of a cam. Defines the type of cam calculation according to the angle value (position, monostable or brake command).
This is the feature of the machine that sets the speed cycles on the axis.
TLX DS 57 PL7 xx
205
Glossary
W
Warm restart The module is initialized with the initial configuration and adjustment parameters.
This happens after a Reset of the CPU.
The module executes the initial recipe. Modifications done in connected mode, are not recognized if a "Save parameters" has not been carried out before the Reset.
206
TLX DS 57 PL7 xx
Index
A
Absolute encoder
Electronic cam configuration, 70
Acquisition
Electronic cam adjustment, 115
Acquisition parameters
Electronic cam configuration, 68
Adjustment
Areas of application
Auxiliary inputs
B
C
Cam
Cam module
TLX DS 57 PL7 09/2000
A C
Cam processor
Electronic cam configuration, 76
Capture
Circuit diagram
Configuration
Configuration of constants
Confirmation
Electronic cam configuration, 79
D
Debugging
DETAIL_OBJECT
Diagnostics
E
Electronic cam module interface, 20
207
Index
Encoder
Error codes
Errors
Events
Explicit command
F
Filtering
Front panel
G
I
Implementation
Implicit command
Incremental encoder
Electronic cam configuration, 69
Electronic cam module parameters, 83
Initial cam parameters
Interface
L
Lights
line check
208
M
Methodology
MOD_CAM
MOD_PARAM
MOD_TRACK
Module status
Movement
O
Operator dialog
P
Parametering adjustments
Parts counter
Electronic cam adjustment, 115
Parametering for the electronic cam module, 87
Performance
Position
Position reading
R
READ_PARAM
TLX DS 57 PL7 09/2000
Reading format
Electronic cam configuration, 73
Reading inversion
Recalibrating the position
Electronic cam configuration, 74
Recalibration
Recipe
Electronic cam module adjustment, 82
Reconfiguration
RESTORE_PARAM
Restoring
Electronic cam parameters, 101
RUN
S
SAVE_PARAM
Saving
Electronic cam parameters, 100
Sensor
Electronic cam configuration, 75
T
Parametering for the electronic cam module, 88, 89
Track adjustment
Track output
Tracks
TLX DS 57 PL7 09/2000
TRF_RECIPE
U
Unit of speed
W
WRITE_PARAM
Index
209
Index
210
TLX DS 57 PL7 09/2000
Herunterladen