Checking the integrity of the module. Schneider Electric Software PLC Application-Specific Functions, Electronic cam module, Junior/Pro, 4.5, PL7 Junior/Pro - Premium PLCs Electronic cam module TSXCCY1128 - Application implementation
広告
広告
List of track or cam error codes
COD_DESC_FLT: error code for track or cam description fault
12
13
14
15
8
9
10
11
6
7
4
5
1
2
Code Faulty parameters
0 No error
TYP_PROFIL unknown cam code
TYP_PROFIL unknown cam code
Cam: Reserved field is not at 0
Cam: Reserved field is not at 0
TRACK_NUM is greater than 7
COND_ENABLE is not at 0,1,2
BIT_NUM_ENABLE impossible
Cam: Reserved field is not at 0
X1 is greater than RESOL_ANG
X2 is greater than RESOL_ANG
TIME_SWICH_OFF is not at 0
X2 is not at 0
TIME_SWITCH_OFF is greater than 16383
Cam: Reserved field is not at 0
35
36
48
49
16
32
33
34
Cam: Reserved field is not at 0
Track: Reserved field is not at 0
Track: Reserved field is not at 0
ADD_TRACK on track 4 to 7
ANTICIP_FACTOR greater than 32767
ANTICIP_FACTOR is not at 0 – logical track
USED_CAM (adjustment) the cam has not been declared
X1(adjustment) is more than RESOL_ANG
50
51
52
53
X2 (adjustment) is greater than RESOL_ANG
TIME_SWITCH_OFF(adjustment) is not at 0
X2 (adjustment) is not at 0
TIME_SWITCH_OFF (adjustment) is greater than 16383
58
59
USED_TRACK (adjustment) the track has not been declared
ANTICIP_FACTOR (adjustment) greater than 32767
60 ANTICIP_FACTOR (adjustment) is not at 0 – logical track
Code Faulty parameters
TLX DS 57 PL7 xx
Diagnostics
189
ダウンロード
広告