Software compatibility: Network transparency. Schneider Electric PL7 Micro/Junior/Pro - Communication applications, volume 2
જાહેરાત
જાહેરાત
General
Software compatibility: Network transparency
Introduction
Transparency restrictions
Exchanges from a remote station to the FIPIO bus or vice versa are possible under certain conditions.
Inter-station communication with FIPIO is only available if the bus arbiter is a TSX
Premium PLC, of at least version V3.3.
Exchanges from a third-party device to a PLC connected as a FIPIO slave are only possible if the PLC is a TSX Premium of V3.3 at least. Communication with a TSX
Micro PLC is not possible.
A FIPIO agent does not communicate with the exterior.
Only one programming terminal can be connected to the FIPIO bus. If it is present in the configuration, it must be connected to the default connection port (63).
This programming terminal cannot be used to load the application onto the FIPIO bus arbiter.
TLX DS COM PL7 xxE
237
General
Illustration The following illustration shows the different exchanges possible between a FIPIO bus and a network or another bus.
FIPAWAY, ETHERNET, Uni-telway, ...
TSX Premium V3.3
Third party device
0
TSX Micro
TSX Premium V3.3
Magelis
63
Programming terminal
238
TLX DS COM PL7 xxE