Language objects in implicit exchange. Schneider Electric PL7 Micro/Junior/Pro - Communication applications, volume 2
Реклама
Реклама
Standard profiles
Language objects in implicit exchange
Introduction
Bit objects
This page describes all the language objects for implicit exchange associated with the standard profiles for FIPIO communication that can be displayed or modified by the application program. (PL7 Micro/Junior/Pro ; Communication applications ;
Volume 1)
The table below shows the different bit objects for implicit exchange.
Object (1)
%I\p.2.c\0.MOD
.ERR
%I\p.2.c\m.i.ER
R
%I\p.2.c\0.0 to
%I\p.2.c\0.31
%Q\p.2.c\0.0 to
%Q\p.2.c\0.31
Function
Module error bit
Channel error bit
Bit exchange
Bit exchange
Meaning
This bit set to 1, indicates a module error (at least one of the channels is faulty,…)
This bit set at 1 indicates a faulty channel.
Acquiring input bits for FRD profiles
Acquiring output bits for FRD profiles
Key
(1) p.2.c Address l l p: corresponds to the processor’s slot c: corresponds to the connection point number
336
TLX DS COM PL7 xxE
Word objects
Standard profiles
The table below shows the different word objects for implicit exchange.
Object (1)
%IW\p.2.c\0.0.
0 to
%IW\p.2.c\0.0.
7
Function
FSD word exchange
%QW\p.2.c\0.0.
0 to
%QW\p.2.c\0.0.
7
FSD word exchange
%IW\p.2.c\0.0.
0 to
%IW\p.2.c\0.0.
31
%QW\p.2.c\0.0.
0 to
%QW\p.2.c\0.0.
31
FED word exchange
FED word exchange
Meaning
Acquiring input words for FSD profiles
Acquiring output words for FSD profiles
Acquiring input words for FED profiles
Acquiring output words for FED profiles
Key
(1) p.2.c\m.i.r Address l l l l p: corresponds to the processor’s slot c: corresponds to the connection point number m: corresponds to the module position number i: corresponds to the channel number
TLX DS COM PL7 xxE
337
Изтегляне
Реклама