Language object for explicit exchange. Schneider Electric PL7 Micro/Junior/Pro - Communication applications, volume 2
Реклама
Реклама
Standard profiles
Language object for explicit exchange
Introduction
Word objects common to all the profiles
This page describes all the language objects for explicit exchange associated with the standard profiles for FIPIO communication that can be displayed or modified by the application program. (PL7 Micro/Junior/Pro ; Communication applications ;
Volume 1)
The table below shows the different word objects for explicit exchange.
Object (1) Function Meaning
%MW\p.2.c\0.MO
D.2
%MW\p.2.c\0.i.2
Module status
Standard module channel status l l l l l l l l
Least significant byte: corresponds to standard.
l l l l l l l l x0 = 1: internal error x1 = 1: functional error x2 = 1: terminal block fault x3 = 1: standard module self-testing x4 = 1: reserved (= 0) x5 = 1: configuration error x6 = 1: missing module x7 = 1: extension module error
Most significant byte: corresponds to extension x8 = 1: internal error x9 = 1: functional error x10 = 1: terminal block fault x11 = 1: extension module self-testing x12 = 1: reserved (= 0) x13 = 1: configuration error x14 = 1: missing module x15 = 1: reserved (= 0)
Least significant byte: corresponding to standard l l l l l l l l x0 = 1: external error 4 x1 = 1: external error 3 x2 = 1: external error 2 x3 = 1: external error 1 x4 = 1: internal error x5 = 1: hardware configuration error x6 = 1: communication error x7 = 1: application error
%MW\p.2.c\0.i.3
Validity of inputs For FRD, FSD and FED profiles the least significant byte is specific to the connected device.
Refer to the documentation for the device.
Key
338
TLX DS COM PL7 xxE
Standard profiles
Object (1)
(1)
Function Meaning p.2.c\m.i.r Address l l l l p: corresponds to the processor’s slot c: corresponds to the connection point number m: corresponds to the module position number i: corresponds to the channel number
Note: For each connected device, refer to the corresponding documentation for details of task status words.
Internal words for FRD and FSD profiles
The following table shows the internal words specific to FRD and FSD profiles:
Object
%MW\p.2.c\0.i.4
to
%MW\p.2.c\0.i.35
Function
Adjustment parameters
Meaning
32 specific adjustment words.
Parameters which can be accessed in read and write format via the WRITE_PARAM , READ_PARAM ,
SAVE_PARAM and RESTORE_PARAM functions.
Key
(1) p.2.c\m.i.r Address l l l l p: corresponds to the processor’s slot c: corresponds to the connection point number m: corresponds to the module position number i: corresponds to the channel number
Internal words for the FED profiles
TLX DS COM PL7 xxE
The following table shows the internal words specific to the FED profiles:
Object
%MW\p.2.c\0.i.4
to
%MW\p.2.c\0.i.11
%MW\p.2.c\0.i.12
to
%MW\p.2.c\0.i.19
%MW\p.2.c\0.i.20
to
%MW\p.2.c\0.i.49
Function Meaning
Specific status 8 specific status words.
Parameters which can be accessed in read format via the READ_STATUS function.
Specific channel level command
8 specific command words.
Parameters which can be accessed in write format by the WRITE_CMD function.
Adjustment parameters
32 specific adjustment words.
Parameters which can be accessed in read and write format via the WRITE_PARAM , READ_PARAM ,
SAVE_PARAM and RESTORE_PARAM functions.
Key
339
Standard profiles
Object
(1)
Function Meaning p.2.c\m.i.r Address l l l l p: corresponds to the processor’s slot c: corresponds to the connection point number m: corresponds to the module position number i: corresponds to the channel number
340
TLX DS COM PL7 xxE