Downloading Data by Group. T&D RTR-500DC

Add to My manuals
85 Pages

advertisement

Downloading Data by Group. T&D RTR-500DC | Manualzz

Downloading Data by Group

Wireless Communication:[ Gather Data]

The RTR-500DC Base Unit can download recorded data from up to

128 Remote Units at one time.

1. In the Main Menu, open [WL Gather Data].

2.

Select the Target for downloading.

[All Groups]: Download from all registered groups

[Specify Group]: Download from only the specified group

3. Select the Download Mode in the [Execute] window.

[COM Route] : Select route of communication

[Direct] : Communicate directly without Repeaters

[As Set]: Communicate according to Wireless Route Settings.

As the RTR-500DC is a hand held portable Base Unit, it is recommended to set to

[Direct] so as to shorten communication time.

The above selection of communication route applies for communication with groups registered via the RTR-500DC Settings Utility. When communication is carried out with any group which has been registered for “Visitor Entry”, always select [Direct].

* For details about "Visitor Entry", see page 51.

[Period] : Period for Download Settings

[1 hour] to [47 hours] (in units of 1 hour)

[2 days] to [300 days] (in units of 1 day)

[All Data] : All of the data stored in the Remote Unit will be downloaded.

38 Communication Functions

4. Adjust the arrow to [Execute] and press the Operation Dial to search for Remote Unit and start the downloading.

Screen during Downloading

Number of Remote Units for which download is in progress or completed

Total number of Remote Units

The LCD screen as shown above means that recorded data is being (or has been) downloaded from three out of eight Remote Units for which wireless communication is being carried out.

Downloading status icon

If [ ] is blinking a data downloading session is in progress.

List No.

This shows the number assigned automatically in the order that the data was downloaded.

Group Name

This shows the Group Name entered when Remote Unit Registration was carried out.

Remote Unit Name

This shows the Remote Unit Name entered when Remote Unit Registration was carried out.

- Move the arrow to [Cancel] and press the Operation Dial during a download session to cancel the operation.

- Upon completion of 250 downloading sessions, the RTR-500DC will stop downloading and display the judgement result. (See page 40 for details.)

- If there is not enough memory left in the RTR-500DC for the data stored in the

Remote Unit, the RTR-500DC will skip it and go to the next Remote Unit to download data. Only Remote Units whose stored data does not exceed the available memory capacity in the RTR-500DC can be the target of downloading.