1.4.2 Cabinet. Notifier AFP-200

Add to My manuals
196 Pages

advertisement

1.4.2 Cabinet. Notifier AFP-200 | Manualzz

System Overview

Main Assemblies

1.4.2 Cabinet

The CPU board mounts in a compact (16.125" x 14.5" x 5.5") cabinet with a front dress plate. The cabinet provides space for two batteries (up to 12 AH).

1.4.3 LCD Display

The control panel uses an 80-character LCD display (4 rows of 20 characters each). The display includes a long-life LED backlight that remains on unless AC power is lost while the system is not in alarm:

AFP-200

ANALOG@FIRE@PANEL

ALL@SYSTEMS@NORMAL

11:00@MON@5/19/98

Figure 4 LCD Display

1.4.4 Membrane Switch Panel

The membrane switch panel provides LED Status

Indicators, operator keys, and programming keys. The operator keys and LEDs are visible with the cabinet door closed. The programming keys are visible only with the door open. Slide-in labels are provided for switch and

LED descriptions. Refer to “Membrane Switch Panel” on page 15.

1.4.5 Transformer Assembly

The transformer assembly includes two 100 VA transformers and a connector.

1

Q

Z

DET

- / .

#

MOD

ENTER

ALL SYSTEMS NORMAL

09:45A THU 06/18/97

AC POWER

FIRE

ALARM

PRE-ALARM

WARNING

SUPERVISORY

ALARM

SILENCE

SYSTEM

TROUBLE

ACKNOWLEDGE

STEP

DRILL

HOLD 2 SECONDS

SYSTEM

RESET

Membrne

1.4.6 Batteries

The cabinet provides space for 7 AH or 12 AH batteries

(for 18 AH batteries use the BB-17 battery box). Batteries must be ordered separately.

18

Technical Manuals Online! - http://www.tech-man.com

AFP-200 PN 15511:H2 10/14/2002

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.

advertisement