Appendix D Releasing Applications. Notifier AFP-200

Add to My manuals
196 Pages

advertisement

Appendix D  Releasing Applications. Notifier AFP-200 | Manualzz

Releasing Applications

Appendix D Releasing Applications

NFPA Standards

D.1 NFPA Standards

The control panel can be used for agent release or preaction/deluge control applications. When used with compatible, UL-listed actuating and initiating devices, the control panel meets the requirements of the NFPA standards listed in Table 54:

!

WARNING: When used for CO

2

releasing applications, observe proper precautions as stated in NFPA12. Do not enter the protected space unless physical lockout and other safety procedures are fully completed. Do not use software disable functions in the panel as lockout.

!

WARNING: Use only SLC control module outputs for agent releasing applications.

NFPA 12

NFPA 12A

NFPA 12B

NFPA 13

NFPA 15

NFPA 16

NFPA 17

NFPA 17A

NFPA 2001

CO

2

Extinguishing Systems (high pressure only)

Halon 1301 Extinguishing Systems

Halon 1211 Extinguishing Systems

Sprinkler Systems

Water Spray Systems

Foam-water Deluge and Foam-water Spray Systems

Dry Chemical Extinguishing systems

Wet Chemical Extinguishing systems

Clean Agent Extinguishing systems

Table 54 NFPA Standards for Releasing Applications

D.2 Programming Releasing Zones

The control panel includes four software releasing zones (zones 91, 92, 93 and 94) used to control releasing functions. Each releasing zone operates independently, and is fully programmable. Program releasing zones from the Releasing Zone screen (Figure 141).

To display the Release Control screen, select 91-94 from the Special Zone Program

Change screen.

Status banner

Delay timer selection

Abort timer selection

(see Table 57)

PRG@SOFTWARE@ZONE

RELEASE@CONTROL

DELAY=XX@ABORT=XXX

CROSS=N@SOAK=XX@Z91

Cross Zoning selection

(see Table 55)

Releasing zone

Soak timer selection

Figure 141 Release Control Screen

148

Technical Manuals Online! - http://www.tech-man.com

AFP-200 PN 15511:H2 10/14/2002

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.

advertisement

Table of contents