Appendix L U.S. Coast Guard & Lloyd’s Register. Notifier AFP-200
Add to My manuals196 Pages
Notifier AFP-200's advanced technology provides early detection of fire, helping protect lives and property. By utilizing smoke, heat, and flame detectors, it promptly identifies threats. Additionally, manual pull stations enable occupants to raise an alarm manually. The system's audible and visual warning devices, including bells and strobes, effectively alert individuals to danger. Remote notification capabilities ensure timely alerts to emergency responders, facilitating a swift response.
advertisement
![Appendix L U.S. Coast Guard & Lloyd’s Register. Notifier AFP-200 | Manualzz Appendix L U.S. Coast Guard & Lloyd’s Register. Notifier AFP-200 | Manualzz](http://s3.manualzz.com/store/data/054722654_1-e71ff1e80a23798f93e27b72338a5e46-360x466.png)
Typical Circuit with Nonpower-limited and Power-limited Wiring
U.S. Coast Guard & Lloyd’s Register
Appendix L U.S. Coast Guard & Lloyd’s Register
USCG.
Table 70 contains a list of equipment suitable for use in marine and shipyard applications as compatible with the AFP-200.
Notifier Equipment
29085 Ferrite Bead for I/O Lines
29146 Ferrite Bead for AC input
ABM-16AT Annunciator Blank Module
ABM-32A Annunciator Blank Module
ACM-16AT Annunciator Control Module
ACM-32A Annunciator Control Module
ACM-8R Annunciator Control Module (Relay)
AEM-16AT Annunciator Expander Module
AEM-32A Annunciator Expander Module
AFM-16A Annunciator Fixed Module
AFM-16AT Annunciator Fixed Module
AFM-32A Annunciator Fixed Module
AVPS-24 Audio/Visual Power Supply
B224BI Intelligent isolator base
B224RB Intelligent Relay base
B401B Detector Base
B402B Four-Wire Detector Base
B501 Flangeless Base for Intelligent Detectors
B501BH Sounder base with B501 base
B501BH Sounder Base
B501BHT Same as B501BH, but includes
Temporal sounder
B710LP Standard US Low-Profile base
BGX-101L Addressable Manual Pull Station
BX-501 Base for all Intelligent
Detectors/Sensors
CAB-AM Cabinet for Marine Applications
CMX-1 Addressable Control Module
CMX-2 Addressable Control Module
CP-651 Ionization Detector
CPX-551 Intelligent Ionization Smoke Detector
CPX-751 Intelligent Ionization Smoke Detector
CRT-2 Video Display Monitor with Keyboard
DHX-501 Duct Housing
DHX-502 Duct Housing
Drip Shield Kit Alternate to CAB-AM
FCM-1 Addressable Control Module
FDX-551 Intelligent Thermal Sensor
FMM-1 Addressable Monitor Module
FMM-101 Addressable Mini Monitor Module
FRM-1 Addressable Relay Module
FSI-751 Addressable Low Profile Ion Detector
FSP-751 Addressable Low Profile Photoelectric
Detector
FSP-751T Addressable Low Profile
Photoelectric with Fixed thermal Detector
FST-751R Addressable Low Profile Heat with
Rate of Rise Sensor
FZM-1 Addressable Zone Monitor Module
HPX-751 Addressable Hostile-environment smoke detector
ISO-X Loop Fault Isolator Module
LCD-80 Liquid Crystal Display Module
LDM-32 Lamp Driver Module
LDM-E32 Lamp Driver Module
LDM-R32 Lamp Driver Module
LP-610 Smoke Detector Base
MMX-1 Addressable Monitor Module
MMX-101 Addressable Mini Monitor Module
MMX-2 Addressable Monitor Module
N-ARA-10 Agent Release Pull Station
NBG-12 Dull Action Manual Pull Station with
Hex lock
NBG-12L Dull Action Manual Pull Station with key lock
NBG-12LX Addressable Pull Station
NBG-12S Single Action Manual Pull Station with pigtail connections and hex lock
NBG-12SP Same as NBG-12L with English and Spanish Labeling
N-ELR Assortment Pack with Mounting Plate
NIB-96 Network Interface Board
NR45-24 Notifier Remote Battery Charger
PRN-4 80-Column Printer
R-120 120 ohm End-of-Line Resistor
R-2.2K 2.2K End-of-Line Resistor
R-27K 27K End-of-Line Resistor
R-470K 470K End-of-Line Resistor
R-47K 47K End-of-Line Resistor
RTM-8 Relay Module
SB-10 Surface Backbox
SD-651 Photoelectric Detector
SDX-551 Intelligent Photoelectric Detector
SDX-751 Intelligent Photoelectric Detector
SMB-500 Surface Mount Box
WP-10 Weatherproof Backbox
System Sensor
1400 Smoke Detector
1451 Smoke Detector
2400TH Smoke Detector with Thermal
2451 Smoke Detector
A2143-00 End-of-Line Resistor Assembly
A77-716B End-of-Line Power Supervision
Relay
H24 (W) 24VDC Horn Red (White)
H24K 24VDC Horn weather proof Red only
MA-24 Electronic Sounder, 24 VDC
MA-24D Sounder, 24 VDC
MASS24110ADA 24 VDC Sounder/Strobe 110
CD
MASS241575ADA 24 VDC Sounder/Strobe
15/75 CD
MASS2415ADA 24 VDC Sounder/Strobe 15
CD
MASS2475ADA 24 VDC Sounder/Strobe 15/75
CD
MASS24LO 24V Red Sounder/Strobe
MASS24LOC 24V Sounder/Strobe Ceiling
P24110 w) 24VDC 110cd Horn / Strobe Red
(White)
P24110K 24VDC 110cd Horn / Strobe weather proof Red only
P2415 (W) 24VDC 15cd Horn / Strobe Red
(White)
P241575 (W) 24VDC 15 / 75cd Horn / Strobe
Red (White)
P241575AG 24VDC 15 / 75cd Horn / Strobe agent Red only
P241575EV 24VDC 15 / 75cd Horn / Strobe evacuation Red only
P241575K 24VDC 15 / 75cd Horn / Strobe weather proof Red only
P241575P (W) 24VDC 15 / 75cd Horn / Strobe no lettering Red (White)
P2430 (W) 24VDC 30cd Horn / Strobe Red
(White)
P2475 (W) 24VDC 75cd Horn / Strobe Red
(White)
P2475K 24VDC 75cd Horn / Strobe weather proof Red only
PS24LO 24V Red Sounder Strobe
RA-400/RA400Z Remote LED Assembly
S24110 w) 24VDC 110cd Strobe Red (White)
S24110K 24VDC 110cd Strobe weather proof
Red only
S2415 (W) 24VDC 15cd Strobe Red (White)
S241575 (W) 24VDC 15 / 75cd Strobe Red
(White)
S241575AG 24VDC 15 / 75cd Strobe agent
Red only
S241575EV 24VDC 15 / 75cd Strobe evacuation Red only
S241575K 24VDC 15 / 75cd Strobe weather proof Red only
S241575P (W) 24VDC 15 / 75cd Strobe no lettering Red (White)
S2430 (W) 24VDC 30cd Strobe Red (White)
S2475 (W) 24VDC 75cd Strobe Red (White)
S2475K 24VDC 75cd Strobe weather proof
Red only
SS-24 Strobe 24 VDC
SS24110ADA 24 VDC Sounder/Strobe 110 CD
SS241575ADA 24 VDC Sounder/Strobe 15/75
CD
SS2415ADA 24 VDC Sounder/Strobe 15 CD
SS2475ADA 24 VDC Sounder/Sounder 75 CD
SS24LO 24 V Red Sounder Strobe
SS24LOC 24V Sounder/Strobe Ceiling
WBB Weatherproof Backbox
Hochiki
HSC-200 Detector Base
HSC-4R Four-Wire Detector Base
SIH-24F Smoke Detector
SLK-24F Smoke Detector
Wheelock
7002T-24 Horn with Strobe, 24 VDC
MB-G10-24-R Bell 10" Gong 24 VDC Red
MB-G6-24-R Bell 6" Gong 24 VDC Red
Fenwal
27121-0 140 Degree F. Thermal Detector
27121-0 190 Degree F. Thermal Detector
27121-0 225 Degree F. Thermal Detector
Table 70 Equipment Suitable for Marine Applications: US Coast Guard
AFP-200 PN 15511:H2 10/14/2002
Technical Manuals Online! - http://www.tech-man.com
187
U.S. Coast Guard & Lloyd’s Register
Typical Circuit with Nonpower-limited and Power-limited Wiring
Table 71 contains a list of equipment listed with Lloyd’s Register as compatible with the AFP-200.
Notifier Equipment
29085 Ferrite Bead for I/O Lines
29146 Ferrite Bead for AC input
ABM-16AT Annunciator Blank Module
ABM-32A Annunciator Module Blank
ACM-16AT Annunciator Control Module
ACM-32A Annunciator Control Module
ADP-4 Annunciator Dress Panel
AEM-16AT Annunciator Expander Module
AEM-32A Annunciator Expander Module
AVPS-24 Audio/Visual Power Supply
B224BI Intelligent isolator base
B224RB Intelligent Relay base
B501 Flangeless Base
B501BH Sounder base with B501 base
B501BHT Same as B501BH, but includes
Temporal sounder
B710LP Standard US Low-Profile base
BGX-101L Addressable Manual Pull Station
BP-3 Battery Dress Panel
CAB-AM Cabinet for Marine Applications
CMX-1 Addressable Control Module
CMX-2 Addressable Control Module
CPX-551 Intelligent Ionization Smoke Detector
CPX-751 Intelligent Ionization Smoke Detector
FCM-1 Addressable Control Module
FDX-551 Intelligent Thermal Sensor
FMM-1 Addressable Monitor Module
FMM-101 Addressable Mini Monitor Module
FRM-1 Addressable Relay Module
FSI-751 Addressable Low Profile Ion Detector
FSP-751 Addressable Low Profile Photoelectric
Detector
FSP-751T Addressable Low Profile
Photoelectric with Fixed thermal Detector
FST-751R Addressable Low Profile Heat with
Rate of Rise Sensor
FZM-1 Addressable Zone Monitor Module
HPX-751 Addressable Hostile-environment smoke detector
ISO-X Loop Fault Isolator Module
LCD-80 Liquid Crystal Display Module
MMX-1 Addressable Monitor Module
MMX-2 Addressable Monitor Module
NBG-12 Dull Action Manual Pull Station with
Hex lock
NBG-12L Dull Action Manual Pull Station with key lock
NBG-12LX Addressable Pull Station
NBG-12S Single Action Manual Pull Station with pigtail connections and hex lock
NBG-12SP Same as NBG-12L with English and Spanish Labeling
NIB-96 Network Interface Board
PS-12250 Battery 12-volt, 25 amp-hour
R-120 120 Ohm End-of-Line Resistor
R-2.2K 2.2K End-of-Line Resistor
R-27K 27K End-of-Line Resistor
R-470K 470K End-of-Line Resistor
R-47K 47K End-of-Line Resistor
SB-10 Surface Backbox
SDX-551 Intelligent Photoelectric Detector
SDX-751 Intelligent Photoelectric Detector
SMB-500 Surface Mount Box
WP-10 Weatherproof Backbox
System Sensor
H24 (W) 24VDC Horn Red (White)
H24K 24VDC Horn weather proof Red only
MA/SS-24D Electronic Sounder/Strobe, 24
VDC
P24110 w) 24VDC 110cd Horn / Strobe Red
(White)
P24110K 24VDC 110cd Horn / Strobe weather proof Red only
P2415 (W) 24VDC 15cd Horn / Strobe Red
(White)
P241575 (W) 24VDC 15 / 75cd Horn / Strobe
Red (White)
P241575AG 24VDC 15 / 75cd Horn / Strobe agent Red only
P241575EV 24VDC 15 / 75cd Horn / Strobe evacuation Red only
P241575K 24VDC 15 / 75cd Horn / Strobe weather proof Red only
P241575P (W) 24VDC 15 / 75cd Horn / Strobe no lettering Red (White)
P2430 (W) 24VDC 30cd Horn / Strobe Red
(White)
P2475 (W) 24VDC 75cd Horn / Strobe Red
(White)
P2475K 24VDC 75cd Horn / Strobe weather proof Red only
S24110 w) 24VDC 110cd Strobe Red (White)
S24110K 24VDC 110cd Strobe weather proof
Red only
S2415 (W) 24VDC 15cd Strobe Red (White)
S241575 (W) 24VDC 15 / 75cd Strobe Red
(White)
S241575AG 24VDC 15 / 75cd Strobe agent
Red only
S241575EV 24VDC 15 / 75cd Strobe evacuation Red only
S241575K 24VDC 15 / 75cd Strobe weather proof Red only
S241575P (W) 24VDC 15 / 75cd Strobe no lettering Red (White)
S2430 (W) 24VDC 30cd Strobe Red (White)
S2475 (W) 24VDC 75cd Strobe Red (White)
S2475K 24VDC 75cd Strobe weather proof
Red only
WBB Weatherproof Backbox
Table 71 Equipment Suitable for Marine Applications: Lloyd’s Register
188
Technical Manuals Online! - http://www.tech-man.com
AFP-200 PN 15511:H2 10/14/2002
advertisement
Key Features
- Early fire detection through smoke, heat, and flame detectors
- Manual pull stations for immediate alarm activation
- Audible and visual warning devices for effective alerting
- Remote notification capabilities for rapid emergency response
- Complies with industry standards such as NFPA 72
Related manuals
Frequently Answers and Questions
What types of detectors does the AFP-200 support?
How does the system alert individuals to danger?
What is the purpose of remote notification capabilities?
advertisement
Table of contents
- 10 About This Manual
- 14 Section 1 System Overview
- 14 1.1 General Description
- 14 1.2 Features
- 15 1.3 Components
- 15 1.3.1 Membrane Switch Panel
- 16 1.3.2 Panel Sounder
- 16 1.3.3 Output Circuits (TB2)
- 16 1.3.4 Relays (TB3)
- 17 1.4 Main Assemblies
- 17 1.4.1 CPU Board
- 18 1.4.2 Cabinet
- 18 1.4.3 LCD Display
- 18 1.4.4 Membrane Switch Panel
- 18 1.4.5 Transformer Assembly
- 18 1.4.6 Batteries
- 19 1.5 Optional Devices & Option Modules
- 19 1.5.1 Digital Communicator
- 19 1.5.2 UDACT
- 19 1.5.3 Network Interface Board - NIB
- 20 1.5.4 Field Charger/Power Supply - FCPS
- 20 1.5.5 Battery Charger - CHG
- 20 1.5.6 Liquid Crystal Display - LCD
- 20 1.5.7 Option Module: Transmitter Module - 4XTM
- 20 1.5.8 Option Module: Relay/Transmitter Module - RTM
- 20 1.5.9 Meter Module
- 21 1.5.10 Trim Ring
- 21 1.5.11 Battery Box
- 21 1.5.12 Dress Panel
- 21 1.5.13 Expansion Power Supplies (AVPS-24 and APS-6R)
- 21 1.5.14 Marine Cabinet
- 21 1.6 Intelligent Detectors
- 22 1.7 Addressable Modules
- 22 1.7.1 Overview
- 22 1.7.2 Module Descriptions
- 24 1.8 End-of-Line Devices
- 24 1.8.1 Overview
- 24 1.9 Annunciation Modules
- 24 1.9.1 Overview
- 24 1.9.2 Annunciator Control Module-8R (ACM-8R)
- 24 1.9.3 LDM Series Lamp Driver Modules
- 25 1.9.4 Annunciator Control System (ACS)
- 25 1.9.5 Annunciator Fixed Modules
- 26 1.10 EIA-232 Peripheral Devices (TB4)
- 26 1.10.1 Overview
- 26 1.10.2 PRN Remote Printer
- 26 1.10.3 Keltron Remote Printer (Model VS4095)
- 26 1.10.4 CRT-2 Display Terminal
- 27 1.11 Specifications
- 27 1.11.1 Primary AC Power (TB7)
- 27 1.11.2 Battery (lead-acid only)
- 27 1.11.3 Signaling Line Circuit (TB6)
- 27 1.11.4 Notification Appliance and Releasing Circuits (TB2)
- 28 1.11.5 Relays (TB3)
- 28 1.11.6 24 VDC Power (TB1)
- 28 1.12 Cabinet Dimensions
- 28 1.12.1 Surface Mount with a BB-17 Battery Box
- 27 AFP-200 PN 15511:H
- 29 1.12.2 Semi-flush Mount
- 30 Section 2 Installation
- 30 2.1 Preparing for Installation
- 30 2.1.1 Unpacking the System
- 30 2.1.2 Installation Notes
- 30 2.1.3 Standards and Codes
- 31 2.2 Installation Checklist
- 32 2.3 Backbox Mounting
- 33 2.4 AC and DC Power Connections
- 33 2.4.1 AC Power Connections (TB7)
- 34 2.4.2 Battery Power Connection (J3)
- 34 2.4.3 Expansion Power Supplies – AVPS-24 or APS-6R (Optional)
- 35 2.5 DC Output Power Connections (TB1)
- 35 2.6 Output Circuits (TB2)
- 35 2.6.1 Notification Appliance Circuits
- 36 2.7 Standard Relays (TB3)
- 37 2.8 EIA-232 Devices – Remote Printers and CRTs (TB4)
- 37 2.8.1 Overview
- 37 2.8.2 Printer Configuration
- 37 2.8.3 Installation
- 38 2.8.4 Keltron Printer
- 39 2.8.5 CRT Connections
- 41 2.9 Wiring a Signaling Line Circuit (SLC)
- 41 2.9.1 Overview of SLC Wiring
- 42 2.9.2 SLC Devices
- 42 2.9.3 Control Panel Capacity
- 43 2.9.4 SLC Performance
- 43 2.9.5 SLC Shield Termination
- 44 2.9.6 Setting an SLC Address for a Module
- 45 2.9.7 Wire Requirements for a Two-wire SLC
- 46 2.9.8 Wire Requirements for a Four-wire SLC
- 49 2.9.9 Wiring an Isolator Module (ISO-X)
- 50 2.9.10 Wiring an IDC with Monitor Modules
- 56 2.9.11 Wiring a Notification Appliance Circuit (NAC) or Control Circuit
- 57 2.9.12 SLC Wiring with Control Modules
- 59 2.9.13 SLC Wiring with an Intelligent Detector
- 60 2.9.14 SLC Wiring with an NBG-12LX Addressable Manual Pull Station
- 61 2.10 Option Module Installation
- 61 2.10.1 Overview
- 62 2.10.2 Installing a 4XTM Module
- 63 2.10.3 Installing an RTM-8 Module
- 65 Section 3 Programming
- 65 3.1 Overview
- 65 3.1.1 Programming Methods
- 65 3.1.2 In This Section
- 66 3.2 Getting Started
- 66 3.2.1 How to Access Programming Options
- 66 3.2.2 Programming Passwords
- 67 3.2.3 How to Use the Programming Keypad
- 68 3.2.4 Programming Shortcuts
- 68 3.2.5 Upload and Download
- 68 3.2.6 Key Programming Terms
- 69 3.2.7 How to Avoid Programming Errors
- 70 3.3 Program Change Options
- 70 3.3.1 Overview
- 71 3.4 How to Enter Program Change
- 72 3.4.1 Program Change Map
- 69 AFP-200 PN 15511:H
- 73 3.4.2 How to Clear a Program from Memory (0=clr)
- 73 3.4.3 How to Autoprogram the Control Panel (1=auto)
- 78 3.4.4 How to Edit or Delete a Point (2=point)
- 85 3.4.5 How to Change a Programming Password (3=passwd)
- 86 3.4.6 How to Change a System Message (4=message)
- 86 3.4.7 How to Change a Zone Label (5=zones)
- 87 3.4.8 How to Edit a Special Zone (6=spl zones)
- 89 3.4.9 How to Edit System Functions (7=sys)
- 92 3.4.10 How to Check the Program (8=check)
- 92 3.5 Status Change Options
- 92 3.5.1 Overview
- 93 3.5.2 Entering Status Change
- 94 3.5.3 Status Change Programming Map
- 95 3.5.4 How to Disable or Enable a Point (1=disable)
- 96 3.5.5 How to Set Detector Selections (2=sens/comp)
- 97 3.5.6 How to Clear Alarm Verification Counters (3=clr ver)
- 98 3.5.7 How to Clear the History Buffer (4=clr hist)
- 98 3.5.8 How to Set the System Time and Date (5=time)
- 99 3.5.9 How to do a Walk Test (6=walk test)
- 101 Section 4 Operation
- 101 4.1 Overview
- 102 4.2 The Membrane Panel
- 102 4.2.1 Overview
- 102 4.2.2 How to Use the Programming Keypad
- 103 4.2.3 How to Use the Enter Key and Cursor Keys
- 103 4.2.4 How to Use the Operator Keys
- 105 4.2.5 How to Read System Status LED Indicators
- 106 4.3 How to Operate the Control Panel
- 107 4.3.1 How to Operate the Panel in Normal Operation
- 107 4.3.2 How to Operate a Panel with a Trouble Condition
- 109 4.3.3 How to Operate a Panel with a Trouble Monitor Point
- 109 4.3.4 How to Operate a Panel with a Fire Alarm
- 110 4.3.5 How to Operate a Panel with a Supervisory Condition
- 111 4.3.6 How to Operate a Panel with a Non-Alarm Condition
- 111 4.3.7 How to Operate the Panel with an Output Circuit Trouble
- 112 4.3.8 How the Control Panel Indicates a Panel Circuit Trouble
- 112 4.4 Control-By-Event Operation
- 113 4.5 Releasing Functions
- 113 4.5.1 Overview
- 113 4.5.2 How to Select Cross Zone Options
- 114 4.6 Releasing Functions
- 115 4.7 Intelligent Detector Functions
- 115 4.7.1 Summary of Detector Functions
- 115 4.7.2 Pre-Alarm Operation/Advanced Warning Addressable Combustion Sensing (AWACS™)
- 116 4.8 Time Functions
- 116 4.8.1 Overview
- 117 4.8.2 Coding Operation (NAC only)
- 117 4.8.3 Presignal/PAS Operation
- 118 4.8.4 Special System Timers
- 118 4.8.5 Waterflow Circuits Operation
- 118 4.8.6 Disable/Enable Operation
- 118 4.8.7 Style 6 Operation
- 118 4.9 Read Status
- 118 4.9.1 Overview
- 119 4.9.2 How to Enter Read Status
- 119 4.9.3 Read Status Options
- 119 4.9.4 Read Point
- 124 4.9.5 Using the History Buffer
- 118 AFP-200 PN 15511:H
- 126 Appendix A Power Supply Calculations
- 126 A.1 Overview
- 126 A.2 Calculating the AC Branch Circuit
- 127 A.3 The Main Power Supply
- 127 Current Limitations in Standby
- 127 Current Limitations in Alarm – System Operation on Primary Power
- 128 A.4 Calculating the System Current Draw
- 128 Overview
- 128 How to Use Table 47 to Calculate System Current Draws
- 130 A.5 Calculating the Battery Size
- 131 A.6 Selecting and Locating Batteries
- 131 A.7 NFPA Battery Requirements
- 132 Appendix B NFPA Applications
- 132 B.1 Section Overview
- 132 Specific Requirements
- 132 Additional Requirements
- 133 B.2 Central Station Fire Alarm Systems (Protected Premises)
- 133 Installing a Notifier 911AC
- 134 Installing a UDACT
- 135 B.3 NFPA 72 Auxiliary Fire Alarm System
- 136 B.4 Wiring a Remote Station Fire Alarm System
- 136 Overview
- 137 Using a 4XTM Module
- 138 Using an RTM-8 Module
- 138 B.5 NFPA 72 Proprietary Fire Alarm Systems
- 140 Appendix C Annunciators
- 140 C.1 LCD-80 Display
- 140 ACS Mode
- 140 Terminal Mode
- 140 C.2 Terminal Mode (LCD-80) Annunciation Interface (TB5 on CPU)
- 141 C.3 ACS Annunciation Interface (TB5 on CPU)
- 141 Supported Modules
- 141 C.4 Annunciator Capacity
- 141 Data Formats for Annunciator Address
- 141 Data Formats at Annunciator Address
- 144 C.5 Terminal Mode EIA-485 Connections (TB5)
- 145 C.6 LCD-80 ACS Mode EIA-485 Connections
- 146 C.7 Power Connections for LCD and ACS Series Annunciators
- 147 C.8 ACS and LDM Series EIA-485 Connections
- 148 Appendix D Releasing Applications
- 148 D.1 NFPA Standards
- 148 D.2 Programming Releasing Zones
- 149 Releasing Zone Functions
- 149 Delay Timer
- 149 Cross Zoning
- 150 Soak Timer (NFPA 16 Applications Only)
- 151 Abort Timer
- 151 Special Module Type Codes
- 151 Abort Switch
- 151 Man. Release
- 152 Rel Ckt ULC
- 152 Release Ckt
- 152 Initiating Devices
- 152 Warning Sounders
- 153 Auxiliary Control Relay Functions
- 153 ACS Annunciation
- 153 Deluge/Pre-Action Release
- 153 D.3 Connecting Releasing Devices
- 152 AFP-200 PN 15511:H
- 154 Connecting a Releasing Device to a Control Panel through an SLC Control or Relay Module
- 154 Connecting an NBG-12LRA Agent Releasing Abort Station
- 157 Appendix E Combination Fire/Burglary Applications
- 157 E.1 Overview
- 157 E.2 Installation
- 157 Installation Overview
- 157 Installing a Tamper Switch
- 158 Wiring for Proprietary Security Alarm Applications
- 159 Connecting to an AM2020/AFP1010 Receiving Unit
- 159 E.3 Programming
- 160 E.4 Operation
- 160 Overview
- 160 Configuring the Keypad for a Security LED Indicator
- 160 Control Panel Operation in a Security Condition
- 161 Appendix F Wire Requirements
- 162 Appendix G Pre-Alarm (AWACS™) Applications
- 162 G.1 Overview
- 162 G.2 Pre-Alarm Applications
- 162 Pre-Alarm Alert Level
- 163 Action Level Pre-Alarm Function
- 163 G.3 Pre-Alarm Programming
- 163 Pre-Alarm Programming Screen
- 164 Selecting Pre-Alarm Application Levels
- 165 Self-Optimizing Pre-Alarm Function
- 166 Audible Warning Applications for AWACS
- 167 Appendix H Special Zones
- 167 H.1 Overview
- 167 H.2 Presignal and Positive Alarm Sequence (PAS)
- 167 Presignal
- 167 Positive Alarm Sequence (PAS)
- 168 H.3 Time Control
- 168 H.4 NAC Code Types
- 169 Appendix I Terminal Interface Protocol
- 169 I.1 General Description
- 169 I.2 Operating Modes
- 169 Local Terminal Mode (LocT)
- 170 Local Monitor Mode (LocM)
- 170 Remote Terminal Mode (RemT)
- 171 I.3 Using the CRT-2 for Read Status
- 171 Overview
- 171 Accessing Read Status Options
- 172 Read Point
- 172 Display Devices in Alarm or Trouble
- 172 Display the Status of all Programmed Points
- 173 View the History Buffer
- 173 Send the History Buffer to the CRT
- 173 I.4 Using the CRT-2 for Alter Status
- 173 Overview
- 174 Accessing Alter Status Options
- 174 Enable or Disable Detectors, Modules, or Bell Circuits
- 175 Change Detector Sensitivity Levels
- 175 Clear the Verification Counter
- 175 Clear the Entire History Buffer
- 176 Set the Pre-Alarm for Alert or Action Level
- 176 CRT-2 Configuration
- 177 Appendix J Expansion Power Supplies
- 177 J.1 Overview
- 175 AFP-200 PN 15511:H
- 177 AVPS-24 Audio/Visual Power Supply
- 177 APS-6R Auxiliary Power Supply
- 179 J.2 Programming
- 179 J.3 Supply Calculations
- 179 AVPS-24/AVPS-24E Calculations
- 180 APS-6R Calculations
- 180 J.4 Installation
- 180 Installing the AVPS-24/AVPS-24E
- 183 Installing the APS-6R
- 186 Appendix K UL Power-limited Wiring Requirements
- 186 K.1 Overview
- 186 K.2 Typical Circuit with Nonpower-limited and Power-limited Wiring
- 187 Appendix L U.S. Coast Guard & Lloyd’s Register
- 189 Appendix M CBE Programming
- 189 M.1 Purpose
- 189 M.2 Software Zones
- 189 M.3 How to Program CBE
- 189 CBE Example
- 191 Appendix N External Battery Charger
- 191 N.1 Overview
- 191 N.2 Installation Requirements
- 191 N.3 Mounting the CHG
- 191 Mounting the Charger into a CAB-X3 Series Cabinet
- 192 Mounting the Charger into a Battery Box
- 194 N.4 Connecting the CHG
- 194 Connecting a CHG-120 to the AFP
- 191 AFP-200 PN 15511:H
- - 3:17A Fri
- - ALARM: SMOKE(PHOTO) DETECTOR ADDRESS 29 ZONE 01 3:15A
- - ACKNOWLEDGE 3:16A Fri
- - SYSTEM RESET 3:17A Fri
- 191 AFP-200 PN 15511:H