Using the CRT-2 for Alter Status

Example

Disable the NAC at address 1:

Press

b01

W

B01

Terminal Interface Protocol

4. Press <E> to Enable or press <D> to Disable; then press <Enter>:

Press

d or e

W

B01 Now Enabled, Enter E(Enable) / D(Disable) or Esc. to Abort

I.4.4 Change Detector Sensitivity Levels

This option lets you change the Alarm and Pre-Alarm levels of any addressable detector in the system. To do so, follow these steps.

5. From the Alter Status menu, select Sensitivity, option

2

:

Press

2W

Det. Sensitivity Enter point: AA, E

Press

57

W

6. Enter the address of the detector you wish to change. For example, detector 57:

D57 now Low sens. Enter H, M, or L to change, Esc. to Abort

Press

3W

I.4.5 Clear the Verification Counter

Clear Verification, option

3

, lets you clear the verification counter for all the addressable detectors in the system:

Press Enter to Clear Verification Counts or Esc. to Abort

Press

4W

I.4.6 Clear the Entire History Buffer

Clear History, option

4

, lets you clear the entire history buffer:

Press Enter to Clear History or Esc. to Abort

AFP-200 PN 15511:H2 10/14/2002

Technical Manuals Online! - http://www.tech-man.com

175

Terminal Interface Protocol

Using the CRT-2 for Alter Status

I.4.7 Set the Pre-Alarm for Alert or Action Level

Set Action/Alert, option

5

, lets you set the Pre-Alarm for Alert or Action. For example, set Alert level=50% and the Action level=70% as follows:

Press

5W

Set % of Alarm: Alert(T) and Action(N) Format: TxxNxx then Enter

Press

t50 n70

W

T50N70

I.4.8 CRT-2 Configuration

The CRT-2 must be set up to communicate with the control panel using the proper protocol. To enter the setup menu on the CRT-2, hold down the CTRL button while pressing the SCROLL LOCK key. There are thirteen groups of parameters that must be set. Each of these thirteen groups is reached by pressing the corresponding function key

(F1 - F13). Use the arrow key to move through each setup group and use the space bar to view the options for each parameter.

176

Technical Manuals Online! - http://www.tech-man.com

AFP-200 PN 15511:H2 10/14/2002

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.

advertisement

Table of contents