ACS Annunciation Interface (TB5 on CPU)

Annunciators

C.3 ACS Annunciation Interface (TB5 on CPU)

In ACS mode, the control panel annunciates its 99 software zones. The use of software zones lets you map any number of modules or detectors to a single LED. The ACS connection uses a standard EIA-485 interface, capable of two-way, high speed communications with multiple annunciators located up to 6,000 ft. from the control panel.

Canadian Requirement: The ACM Series annunciator modules must be used to annunciate the fire alarm input points/zones only. For Canadian applications, the following LED colors must be employed:

• Red must be used to indicate active alarm inputs

• Yellow must be used to indicate supervisory, burglary or trouble signals

• Green must be used to indicate the presence of power or an activated output

C.3.1 Supported Modules

When programmed for ACS mode, the control panel will support the following

ACS-compatible modules:

• Point annunciators

ACM-16AT, AEM-16AT

AFM-16A, AFM-32A, AFM-16AT

ACM-32A, AEM-32A

LDM-32, LDM-E32, LDM-R32

ACM-8R

– This module may be used to increase the relay capacity of the control panel by providing mappable dry contact relays. The control panel can support 99 detectors, 99 modules, four Notification Appliance Circuits, eight internal relays, and 99 external relays, for a total of over 300 points. The ACM-8R may be powered by the regulated/high-ripple notification appliance power from the control panel. For detailed information, refer to ACM-8R manual.

Note: Similar point capacity extension is possible using the LDM-R32, but the LDM-32 series must use filtered, regulated power and is therefore more limited than the ACM-8R.

LCD-80

– The LCD-80 must be set to ACS mode (refer to the LCD-80 manual).

C.4 Annunciator Capacity

ACS annunciation displays the 99 software zones of the control panel plus 8 system points, for a total of 107. Information is transmitted using annunciator addresses 1 and

2. The EIA-485 interface will allow up to 32 annunciators (all but two must be in receive-only mode), over distances of up to 6,000 feet (1828.8 m) subject to system power limitations.

C.4.1 Data Formats for Annunciator Address 1

Table 52 contains the data formats available at annunciator address 1. Note the following:

1. The use of a UDACT Universal Digital Alarm Communicator/Transmitter and an

ACM, AFM or LDM Series Annunciator on the same control panel alters the assignments of the yellow LEDs on ACS Points 3, 4, 5, 6, 7 and 8.

2. Assignments with the UDACT are Point 3=Program Mode, Point 4=Supervisory,

Point 5=Bell Trouble, Point 6=Prealarm/Maintenance Alert, Point 7=Low Battery and Point 8=AC Fail.

C.4.2 Data Formats at Annunciator Address 2

Table 53 contains the data formats for annunciator address 2. Note the following:

1. The National Standard of Canada (CAN/ULC-5527) requires a dedicated display to use yellow visual indicators to show the status of supervisory inputs. Notifier annunciators intended for Canadian Supervisory Service are: ACM-16ATCS4,

ACM-16ATCS, ACM-16ATY, ACM-32ACS8, ACM-32ACS, and ACM-32AY.

2. On address 2, LED number = point number – 56

AFP-200 PN 15511:H2 10/14/2002

Technical Manuals Online! - http://www.tech-man.com

141

Annunciators

Annunciator Capacity

142

ACS Point no.

1

I/O

Input

Red LED

System Alarm

30

31

32

33

26

27

28

29

22

23

24

25

18

19

20

21

14

15

16

17

10

11

12

13

8

9

6

7

4

5

2

3

46

47

48

49

42

43

44

45

38

39

40

41

34

35

36

37

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

54

55

56

57

50

51

52

53

Input

Input

Input

Input

Input

Input

Input

Input

Z42 Active

Z43 Active

Z44 Active

Z45 Active

Z46 Active

Z47 Active

Z48 Active

Z49 Active

58

59

60

61

Input

Input

Input

Input

Z50 Active

Z51 Active

Z52 Active

Z53 Active

62

63

Input

Input

Z54 Active

Z55 Active

64 Input Z56 Active

Note: 1 System Trouble excludes AC Power Fail.

Z26 Active

Z27 Active

Z28 Active

Z29 Active

Z30 Active

Z31 Active

Z32 Active

Z33 Active

Z34 Active

Z35 Active

Z36 Active

Z37 Active

Z38 Active

Z39 Active

Z40 Active

Z41 Active

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Output

Output

Output

Input

Input

Input

Input

Input

Z10 Active

Z11 Active

Z12 Active

Z13 Active

Z14 Active

Z15 Active

Z16 Active

Z17 Active

Z18 Active

Z19 Active

Z20 Active

Z21 Active

Z22 Active

Z23 Active

Z24 Active

Z25 Active

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Z1 Active

Z2 Active

Z3 Active

Z4 Active

Z5 Active

Z6 Active

Z7 Active

Z8 Active

Z9 Active

Yellow LED with UDACT

System Trouble

1

Signals Silenced

Program Mode

Supervisory

Bell Trouble

Pre-Alarm/Maint. Alert

Low Battery

AC Fail

Table 52 Data Formats at Annunciator Address 1

Z38 Trouble

Z39 Trouble

Z40 Trouble

Z41 Trouble

Z42 Trouble

Z43 Trouble

Z44 Trouble

Z45 Trouble

Z46 Trouble

Z47 Trouble

Z48 Trouble

Z49 Trouble

Z50 Trouble

Z51 Trouble

Z52 Trouble

Z53 Trouble

Z54 Trouble

Z55 Trouble

Z56 Trouble

Z22 Trouble

Z23 Trouble

Z24 Trouble

Z25 Trouble

Z26 Trouble

Z27 Trouble

Z28 Trouble

Z29 Trouble

Z30 Trouble

Z31 Trouble

Z32 Trouble

Z33 Trouble

Z34 Trouble

Z35 Trouble

Z36 Trouble

Z37 Trouble

Z6 Trouble

Z7 Trouble

Z8 Trouble

Z9 Trouble

Z10 Trouble

Z11 Trouble

Z12 Trouble

Z13 Trouble

Z14 Trouble

Z15 Trouble

Z16 Trouble

Z17 Trouble

Z18 Trouble

Z19 Trouble

Z20 Trouble

Z21 Trouble

Yellow LED

System Trouble

1

Signals Silenced

Not used

Not used

Supervisory

Pre-Alarm

Panel trouble

AC Fail

Z1 Trouble

Z2 Trouble

Z3 Trouble

Z4 Trouble

Z5 Trouble

Switch

Acknowledge

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Signal Silence

System Reset

Drill

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Comments

See Note 1

Panel Supervisory LED on

Trouble

Trouble

Battery/Earth Trouble

AFP-200 PN 15511:H2 10/14/2002

Technical Manuals Online! - http://www.tech-man.com

Annunciator Capacity

Annunciators

60

61

62

63

64

56

57

58

59

52

53

54

55

48

49

50

51

44

45

46

47

40

41

42

43

36

37

38

39

32

33

34

35

28

29

30

31

24

25

26

27

20

21

22

23

16

17

18

19

12

13

14

15

8

9

10

11

6

7

4

5

2

3

ACS Point #

1

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Z88 Active

Z89 Active

Z90 Active

Z91 Active

Z92 Active

Z93 Active

Z94 Active

Z95 Active

Z96 Active

Z97 Active

Z98 Active

Z99 Active

Not used

Not used

Not used

Not used

Z72 Active

Z73 Active

Z74 Active

Z75 Active

Z76 Active

Z77 Active

Z78 Active

Z79 Active

Z80 Active

Z81 Active

Z82 Active

Z83 Active

Z84 Active

Z85 Active

Z86 Active

Z87 Active

Red LED

Z57 Active

Z58 Active

Z59 Active

Z60 Active

Z61 Active

Z62 Active

Z63 Active

Z64 Active

Z65 Active

Z66 Active

Z67 Active

Z68 Active

Z69 Active

Z70 Active

Z71 Active

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Z88 Trouble

Z89 Trouble

Z90 Trouble

Z91 Trouble

Z92 Trouble

Z93 Trouble

Z94 Trouble

Z95 Trouble

Z96 Trouble

Z97 Trouble

Z98 Trouble

Z99 Trouble

Not used

Not used

Not used

Not used

Z72 Trouble

Z73 Trouble

Z74 Trouble

Z75 Trouble

Z76 Trouble

Z77 Trouble

Z78 Trouble

Z79 Trouble

Z80 Trouble

Z81 Trouble

Z82 Trouble

Z83 Trouble

Z84 Trouble

Z85 Trouble

Z86 Trouble

Z87 Trouble

Yellow LED

Z57 Trouble

Z58 Trouble

Z59 Trouble

Z60 Trouble

Z61 Trouble

Z62 Trouble

Z63 Trouble

Z64 Trouble

Z65 Trouble

Z66 Trouble

Z67 Trouble

Z68 Trouble

Z69 Trouble

Z70 Trouble

Z71 Trouble

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

Input

I/O

Input

Input

Input

Input

Input

Input

Input

Comments

Presignal Time Run Time

Started/Release Time

Started/Release Time

Started/Release Time

Started/Release Time

Time Control Active

Time Control Active

Holiday Active

Tornado Active

Pre-Alarm Active

Table 53 Data Formats at Annunciator Address 2

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Switch

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

Not used

AFP-200 PN 15511:H2 10/14/2002

Technical Manuals Online! - http://www.tech-man.com

143

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.

advertisement

Table of contents