NFPA Applications

Section Overview

Appendix B NFPA Applications

B.1 Section Overview

B.1.1 Specific Requirements

The control panel is designed for use in commercial, industrial, and institutional applications and meets the requirements for service under the National Fire Protection

Association (NFPA) Standards outlined in this appendix. The minimum system components required for compliance with the appropriate NFPA standard are listed below.

• AFP-200 control panel containing the main circuit board, cabinet (backbox and door), main supply transformer and power supply.

• Batteries (refer to Appendix A for standby power requirements).

• Initiating devices connected to the control panel’s signaling line circuit.

• Notification appliances connected to the control panel’s Notification Appliance

Circuit or via a control module.

B.1.2 Additional Requirements

Table 50 contains additional equipment that is needed for compliance with the NFPA standards listed below:

NFPA Standard

NFPA 72 Central

Station Fire Alarm

Systems

(Protected

Premises Unit)

NFPA 72 Auxiliary

Fire Alarm System

NFPA 72 Remote

Station Fire Alarm

System

NFPA 72

Proprietary Fire

Alarm System

Application

DACT

Universal Digital Alarm

Communicator/Transmitter or Notifier 911AC

DACT for connection to a compatible

UL-listed Central Station DACR or Protected

Premises Receiving Unit.

RTM-8

Relay Transmitter Module or 4XTM

Transmitter Module for connection to a compatible UL-listed Local Energy Municipal

Box.

RTM-8

Relay Transmitter Module or 4XTM

Transmitter Module for connection to the

Fire•Lite RS-82 Remote Station Receiver. or

UDACT

Universal Digital Alarm

Communicator/Transmitter or Notifier 911AC

DACT for connection to a compatible

UL-listed remote station DACR.

NIB-96

Network Interface Board. The

NIB-96 must be installed in the receiving system.

Refer to

“Central Station Fire

Alarm Systems

(Protected Premises)” on page 133

“NFPA 72 Auxiliary Fire

Alarm System” on page

135

“Wiring a Remote Station

Fire Alarm System” on page 136

“Installing a UDACT” on page 134 and “Installing a Notifier 911AC” on page 133.

“NFPA 72 Proprietary

Fire Alarm Systems” on page 138 and the NIB-96

Manual, Document

15666.

Table 50 Additional Equipment for NFPA Applications

132

Technical Manuals Online! - http://www.tech-man.com

AFP-200 PN 15511:H2 10/14/2002

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.