2.9.2 SLC Devices. Notifier AFP-200

Add to My manuals
196 Pages

advertisement

2.9.2 SLC Devices. Notifier AFP-200 | Manualzz

Installation

Refer to the installation drawings supplied with each loop device for rating and specification information.

Wiring a Signaling Line Circuit (SLC)

2.9.2 SLC Devices

Communication with intelligent and addressable initiating, monitor, and control devices takes place through a Signaling Line Circuit (SLC). You can wire an SLC to meet the requirements of NFPA Style 4, Style 6, or Style 7 circuits. Table 10 contains descriptions of devices connected to an SLC:

Type of Device SLC Function

Isolator Modules

(ISO-X)

Addressable

Monitor Modules

Control Modules

Allows a zone of detectors and modules to be electrically isolated from the remainder of the loop, which lets critical loop components function if a circuit fails. ISO-X modules are required for NFPA Style 7 circuits.

Allows the control panel to monitor entire circuits of conventional alarm-initiating devices, such as manual pull stations, detectors, waterflow and supervisory devices.

Allows the control panel to selectively activate Notification Appliance

Circuits (NACs).

Allows the control panel to selectively activate Form-C output relays.

Relay Modules

XP5-M

XP5-C

Allows the control panel to monitor up to five Initiating Device Circuits

(IDCs). Each XP5-M occupies five consecutive addresses on the SLC.

Allows the control panel to control a maximum of five individual notification appliance/telephone circuits or Form-C relays. Each XP5-C occupies five consecutive addresses on the SLC.

Intelligent Detectors Allows the control panel to communicate with intelligent ionization, photoelectric, and thermal detectors on the SLC.

Addressable Pull

Station

The NBG-12LX provides a manual method of creating an alarm activation.

Table 10 SLC Devices

Maximum wiring distance of an SLC:

Style 4.

10,000 ft. (3048 m) (12 AWG)

Style 6, 7.

10,000 ft. (3048 m) (12 AWG) total twisted-pair.

2.9.3 Control Panel Capacity

AFP-200 capacity includes up to 99 intelligent detectors and an additional combination of up to 99 addressable pull stations, and monitor, control and relay modules. In addition, the control panel also supports four Notification Appliance Circuits and up to

99 programmable relays.

JP7

JP6

SW2

SW3

JP2

SLC – Up to 198 intelligent/addressable devices

JP1 JP9

JP3

JP5

42

Afp2incab

Figure 18 AFP-200 Capacity

AFP-200 PN 15511:H2 10/14/2002

Technical Manuals Online! - http://www.tech-man.com

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.

advertisement

Table of contents