I.4.7 Set the Pre-Alarm for Alert or Action Level

Set Action/Alert, option

5

, lets you set the Pre-Alarm for Alert or Action. For example, set Alert level=50% and the Action level=70% as follows:

Press

5W

Set % of Alarm: Alert(T) and Action(N) Format: TxxNxx then Enter

Press

t50 n70

W

T50N70

I.4.8 CRT-2 Configuration

The CRT-2 must be set up to communicate with the control panel using the proper protocol. To enter the setup menu on the CRT-2, hold down the CTRL button while pressing the SCROLL LOCK key. There are thirteen groups of parameters that must be set. Each of these thirteen groups is reached by pressing the corresponding function key

(F1 - F13). Use the arrow key to move through each setup group and use the space bar to view the options for each parameter.

176

Technical Manuals Online! - http://www.tech-man.com

AFP-200 PN 15511:H2 10/14/2002

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.

advertisement

Table of contents