B.3 NFPA 72 Auxiliary Fire Alarm System. Notifier AFP-200

Add to My manuals
196 Pages

advertisement

B.3 NFPA 72 Auxiliary Fire Alarm System. Notifier AFP-200 | Manualzz

NFPA 72 Auxiliary Fire Alarm System

NFPA Applications to 2 (refer to the UDACT manual)?

5. Is the ACS/ TERM switch (SW2) on the control panel set to the ACS position?

6. Is the control panel programmed for “ANNUN=UDACT”?

7. Is the control panel configured for proper supervision? Supervise the UDACT via the COMM FAIL output (refer to Monitoring for UDACT Trouble in the UDACT

Manual)?

• For a system without an annunciator – configure the UDACT for

Receive/Transmit

.

• For a system with an annunciator – configure the UDACT for

Receive Only

and the annunciator for

Receive/Transmit

.

Note: If the annunciator does not require remote control capabilities (Reset,

Acknowledge, Silence, etc.), 'COMM FAIL' monitoring is not required if the following conditions are met: the UDACT is configured for “Receive/Transmit”

and

the annunciator is configured for “Receive Only”.

B.3 NFPA 72 Auxiliary Fire Alarm System

Figure 131 and 131 show typical connections (all connections are nonpower-limited and supervised) for wiring the control panel to a municipal box. Maximum loop resistance allowed for wiring from control panel to Municipal Box is 5 ohms. Cut JP5 on control panel circuit board. This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions.

RTM-8 Module

Gamewell Model M34-56

Local Energy Municipal Box

Jumper JP2 must be in the LE MUNCPL BOX position for use in this application

Municipal Box Circuit

Polarities shown in alarm condition

Figure 131 Wiring a Municipal Box Connected to a RTM-8

AFP-200 PN 15511:H2 10/14/2002

Technical Manuals Online! - http://www.tech-man.com

135

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.

advertisement

Table of contents