2.8.4 Keltron Printer. Notifier AFP-200

Add to My manuals
196 Pages

advertisement

2.8.4 Keltron Printer. Notifier AFP-200 | Manualzz

Installation

EIA-232 Devices – Remote Printers and CRTs (TB4)

Plug the DB-9 or DB-25 connector into the EIA-232 port of the printer.

7

Connection between the control panel and the PRN is via an EIA-232 interface. A custom cable must be assembled for connection to the printer's EIA-232 port.

3 2 1

DB-25 Connections:

Connect TX (Pin 3) to TB4 terminal 1

Connect REF (Pin 7) to TB4 terminal 2

Connect RX (Pin 2) to TB4 terminal 3

Note: When using a DB-25 for Upload/Download connect a jumper between pin 6 and pin 20.

DB-9 Connections:

Connect TX (Pin 2) to TB4 terminal 1

Connect REF (Pin 5) to TB4 terminal 2

Connect RX (Pin 3) to TB4 terminal 3

Note: If also using a DB-9 connector for upload/download connect a jumper between pin 4 and pin 6.

1 2 3 4 5 6

TX REF RX REF

TB4

OUT OUT IN IN

TB5

A B B+ A+ B- A-

TB6

The EIA-232 printer interface may also be used with EDP UL-listed equipment, such as personal computers, to monitor the control panel for supplementary purposes.

Figure 14 Remote Printer Connections

2.8.4 Keltron Printer

Figure 15 shows typical connections between the control panel and a Keltron printer.

Keltron Printer

Model number VS4095/5

(see note 3)

Plug this DB-25 connector into the

EIA-232 port of the printer

7 3 2 1

Keltron Remote Printer

DC IN+

DC IN -

24VDC (14 AWG)

38

TB1

TB2 TB3

TB4

TB5

Figure 15 Keltron Printer Connections

TB6

Notes on Figure 15:

1. Outputs are power-limited, but are not supervised.

2. Connections must be made with overall foil/braided-shield twisted paired cable

AFP-200 PN 15511:H2 10/14/2002

Technical Manuals Online! - http://www.tech-man.com

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.

advertisement

Table of contents