NFPA Applications

NFPA 72 Proprietary Fire Alarm Systems

B.4.3 Using an RTM-8 Module

Figure 134 shows typical wiring for an RTM-8 module to a UL-listed Fire•Lite RS-82

Remote Station Receiver. For this application, note the following:

• RTM-8 jumper JP2 must be in position AL/TR REV. POL. for use in alarm and trouble transmission

or

AL ONLY for alarm transmission only.

• For additional information on the RS-82, refer to the Fire•Lite Alarms, Inc. RS-82

Instruction Manual.

• The RTM-8 is not suitable for separate transmission of both alarm and trouble signals to a remote station.

• Cut jumper JP5 on control panel CPU board.

Fire•Lite RS-82 Remote Station Receiver

Polarity Shown is Non-Alarm

JP1

Jumper Settings:

Alarm/Trouble Polarity

Reversal

Remote Station

JP1 must be cut

Alarm only Polarity Reversal

Remote Station

JP1 must be cut

JP2

Polarity Shown is Non-Alarm

RTM-8 Relay Transmitter Module

Figure 134 Remote Station Connections Using an RTM-8 Module

B.5 NFPA 72 Proprietary Fire Alarm Systems

Figure 135 shows typical connections between an AFP-200 control panel and receiving unit (NIB-96 in an AM2020) for a proprietary fire alarm application. Table 51 lists wiring connections for the NIB-96, AM2020, and AFP-200.

• Program the AFP-200 for ACS annunciation mode and set switch (SW2) on the

CPU board for ACS mode. The ACS interface will automatically transmit General

Alarm, General Trouble and General Supervisory signals and will receive

Acknowledge, Silence, and Reset commands automatically from the

AM2020/AFP1010 control panel. Zone alarm and zone trouble information may be transmitted by programming the AFP-200 points to software zones 1 through

88.

• Up to ten AFP-200 Protected Premises Units may be monitored by one

AM2020/AFP1010 Receiving Unit using ten SLC loops and ten NIB-96 modules.

• Disable the ground fault circuit on the AFP-200 by cutting jumper JP9 because the

138

Technical Manuals Online! - http://www.tech-man.com

AFP-200 PN 15511:H2 10/14/2002

NFPA 72 Proprietary Fire Alarm Systems

NFPA Applications

AM2020/AFP1010 performs ground fault protection for the control panel circuits.

• If connecting an RPT-485W isolating repeater module between the

AM2020/AFP1010 and the control panel, a common connection between the two panels is not needed. However—a system common connection must be made from the AFP-200 to RPT-485W,

and

the AFP-200 ground fault jumper JP9 should not be cut.

• For Receiving Unit installation and programming, refer to the AM2020/AFP1010 manual and the NIB-96 manual.

NIB-96

EIA-485 two-wire loop (Style 4), twisted pair

(power-limited and supervised)

TB3

MPS-24A/

MPS=24AE

AM2020/AFP1010 Receiving Unit

System

Common

T

B

1

T

B

2

1 2 3 4 5 6 7 8 T

B

3

1 2 3 4 5 6 7 8

JP 8

JP8

T

B

4

TX REF RX RE F

T

B

5

OU T OU T IN IN

T

B

6

1 2 3 4 5 6

AC POWER

ALARM

ACKNO WLEDGE

STEP

ALARM

SILENCED

SYS TEM RESET

AFP-200 Protected

Premises Unit

JP1

Figure 135

NFPA 72 Proprietary Fire Alarm Systems

EIA-485 (+)

EIA-485 (–)

System Common

NIB-96

P4 Term. 5

P4 Term. 3

AFP-200

TB5 Term. 1

TB5 Term. 2

TB1 Term. 6

MPS-24A

TB3 Term. 6

Table 51 Proprietary Fire Alarm Systems Wiring Connections

AFP-200 PN 15511:H2 10/14/2002

Technical Manuals Online! - http://www.tech-man.com

139

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.