Table 62 below summarizes the functions available with the Local Terminal mode:

Function

Read Status

Alter Status

Control

Functions

Lets you...

• Display the status of an individual point (detector, module, panel circuit, or zone)

• Display a list of all the points in alarm or trouble

• Display a list of all programmed points in the system

• Step through the history buffer event by event

• Display the entire history buffer

• Disable/Enable an individual point

• Change the sensitivity of a detector

• Clear the verification counter of all detectors

• Clear the entire history buffer

• Set the AWACS™ alert and action levels

• Acknowledge

• Alarm Silence

• System Reset

• Drill

Table 62 LocT Functions

I.2.2 Local Monitor Mode (LocM)

Functions, passwords, and special requirements of Local Monitor Mode (LocM) are:

Functions:

Read Status, Alter Status, and Control Functions.

Passwords:

User-defined password for Alter Status and Control functions.

Requirements:

Password security feature for Control Functions eliminates the need for mounting the CRT-2 in an enclosure.

Table 63 summarizes the functions available with the Local Monitor mode:

Function Lets you...

Read Status • Display the status of an individual point (detector, module, panel circuit, or zone)

• Display a list of all the points in alarm or trouble.

• Display a list of all programmed points in the system

• Step through the history buffer event by event

• Display the entire history buffer

Alter Status*

Control

Functions*

• Disable/Enable an individual point

• Change the sensitivity of a detector

• Clear the verification counter of all detectors

• Clear the entire history buffer

• Set the AWACS™ alert and action levels

• Acknowledge

• Alarm Silence

• System Reset

• Drill

*Requires the user defined password for access.

Table 63 LocM Functions

I.2.3 Remote Terminal Mode (RemT)

Functions, passwords, and special requirements of Remote Terminal Mode (RemT) are:

Functions:

Read Status only. See Table 64.

170

Technical Manuals Online! - http://www.tech-man.com

AFP-200 PN 15511:H2 10/14/2002

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.

advertisement

Table of contents