Installation Checklist

2.2 Installation Checklist

Installation

!

!

!

CAUTION: Make sure to install system components in the precise order in the checklist. Failure to do so can damage the control panel and other system components

Table 6 contains an installation checklist for installing, wiring, and testing an AFP-200 system:

Task Refer to

Mount the cabinet backbox to the wall.

If using expansion power supplies, mount the expansion power supply to the backbox.

CAUTION: Connect the AC power cable and DC battery cables.

CAUTION: Do not connect power at this time!

Mount an optional module (RTM-8 or 4XTM).

Install optional peripheral devices, such as a printer, personal computer, or CRT-2 terminal.

Wire the Signaling Line Circuits.

Connect AC power to control panel — but do not connect batteries.

Check AC power—but do not connect batteries.

Program the control panel.

Connect the batteries.

Walk test the system.

“Backbox Mounting” on page 32

Appendix J “Expansion Power

Supplies”

“AC and DC Power Connections” on page 33

“Option Module Installation” on page 61

“EIA-232 Devices – Remote

Printers and CRTs (TB4)” on page 37

“Wiring a Signaling Line Circuit

(SLC)” on page 41

“AC Power Connections (TB7)” on page 33

Table 7

Section 3 “Programming”

“Battery Power Connection (J3)” on page 34

“How to do a Walk Test (6=walk test)” on page 99

Table 6 Installation Checklist

Table 7 contains a checklist for checking the system with AC power applied:

CAUTION: While checking AC power, make sure batteries are not connected.

Component Status

The CPU option module

AVPS-24/AVPS-24E or APS-6R

The green AC Power indicator on; the system Trouble indicator on because of no battery power.

The yellow Trouble indicator may come on for approximately 10 seconds after applying AC power. (This only applies to an unconfigured system.)

The yellow Trouble indicator comes on because batteries are not connected.

Table 7 AC Power Checklist

AFP-200 PN 15511:H2 10/14/2002

Technical Manuals Online! - http://www.tech-man.com

31

advertisement

Key Features

  • Early fire detection through smoke, heat, and flame detectors
  • Manual pull stations for immediate alarm activation
  • Audible and visual warning devices for effective alerting
  • Remote notification capabilities for rapid emergency response
  • Complies with industry standards such as NFPA 72

Related manuals

Frequently Answers and Questions

What types of detectors does the AFP-200 support?
It supports smoke, heat, and flame detectors for comprehensive fire detection.
How does the system alert individuals to danger?
It utilizes audible alarms (bells) and visual indicators (strobes) for effective alerting.
What is the purpose of remote notification capabilities?
Remote notification capabilities enable the system to send alerts to emergency responders, ensuring a swift response.

advertisement

Table of contents