3.1 General Specifications
Item
Operating ambient temperature
Display section
Other than display section
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Specifications
0 to 50°C
0 to 55°C
-20 to 60°C
10 to 90% RH, non-condensing
10 to 90% RH, non-condensing
Vibration resistance
Shock resistance
*1
Operating atmosphere
Operating altitude
*2
Installation location
Overvoltage category
*3
Pollution degree
*4
Cooling method
Frequency Acceleration
Halfamplitude
Sweep
Count
Conforms to JIS
B3502 and
IEC61131
-2
Under intermittent vibration
Under continuous vibration
5 to 9Hz
9 to
150Hz
5 to 9Hz
9 to
150Hz
-
9.8m/s
-
4.9m/s
2
2
3.5mm
-
1.75mm
-
10 times each in X,
Y and Z directions
Conforms to JIS B3502, IEC 61131-2 (147 m/s
2
, 3 times each in X, Y and Z directions)
No corrosive gas
2000 m (6562 ft) max.
Inside control panel
II or less
2 or less
Self-cooling
8
*1 When using the MELSECNET/10 communication unit (GT15-
75J71LP23-Z, GT15-75J71BR13-Z) or CC-Link communication unit
(GT15-75J61BT13-Z), refer to the manual of the communication unit you use. (Differs with the specification of GOT.)
*2 Do not use or store the GOT under pressure higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this instruction may cause a malfunction.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the raged voltage of 300
V is 2500 V.
*4 This index indicates the degree to which conductive material is generated in the environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.