4.3 Mounting Position
When mounting the GOT, the following clearances must be left from the other device.
C D E
Panel thickness: 2 to 4mm
(0.08 to 0.16inch)
A
B
C, D
E
Type
GOT or Bus connection unit is fitted
GT1585
50(1.97) or more
[14(0.55) or more]
GT1575
50(1.97) or more
[31(1.22) or more]
GT1565
50(1.97) or more
[36(1.92) or more]
RS-422 Conversion unit is fitted 51(2.01) or more 68(2.68) or more 73(2.87) or more
Ethernet communication unit,
MELSECNET/10 communication unit (coaxial),
CC-Link communication unit fitted.
50(1.97) or more
[10(0.39) or more]
MELSECNET/10 communication unit (optical) fitted.
50(1.97) or more
[26(1.02) or more]
50(1.97) or more
[10(0.39) or more]
50(1.97) or more
[43(1.69) or more]
80(20) or more
50(20) or more
50(1.97) or more
[10(0.39) or more]
50(1.97) or more
[48(1.89) or more]
100(20) or more
Unit: mm (inch)
The values enclosed in parenthesis apply to the case where no other equipment generating radiated noise (such as a contactor) or heat is installed. However, keep the ambient temperature of the GOT to 55°C or lower even in such a case.
The required lead-in allowance for cables may be larger than the size of
A above depending on the unit or cable used.
For the lead-in allowance for cables at the bottom of the GOT, refer to the following.
Connected manual of GOT1000 series