5.3 Wiring of Connection Cables. Mitsubishi Electric GT15
विज्ञापन
विज्ञापन
• As measures against surge due to lightning, connect a lightning surge absorber as shown below.
Lightning surge absorber connection
AC
GOT
I/O equipment
E2
E1
Lightning surge absorber
POINT
1. Separate the grounding of the lightning surge absorber (E1) from the grounding of the GOT (E2).
2. Select an appropriate lightning surge absorber so that the supply voltage does not exceed the maximum allowable circuit voltage of the surge absorber even when it rises to the maximum.
5.3 Wiring of Connection Cables
Keep the connection cables away from the main circuit lines (high voltage, large current) or I/O signal lines.
When using GT15-C EXSS-1 or GT15C BS, perform the grounding in the following steps.
(1) When using GT15-C EXSS-1
Not connected
PLC
GOT
3)
(GT15-C BS)
OUT IN
FG
LG
N
L
(GT15-EXCNB)
L N LG FG
5)
2SQ cables to
FG terminals,
28cm or less
6)
4)
1)
2)
1) Connect the LG and FG terminals of the terminal block on the GOT unit power and ground them with a cable.
2) Use the GT15-C BS's FG cable of 28cm or less.
3) Do not connect the GT15-EXCNB's FG ground cable.
4) Connect the GT15-C BS's FG cable on the GOT side to FG of the
GOT unit power's terminal block.
24