5.5 Power Terminal Connection
This section provides an example for connecting power cables and ground cables to the power terminals situated on the back of the GOT.
100/110V AC
AC
In the case of 100V AC
GOT
Fuse
INPUT
100-240VAC
(LG) (FG)
AD
DC
24V DC
GOT
INPUT
24VDC
(LG) (FG)
In the case of 24V DC
Ground cables
Grounding
POINT
1. For 100V AC, 200V AC or 24V DC cable, use the thickest cable as possible (0.75 to 2mm
2
) and start twisting them at the position closest to the connected terminals.
To prevent a short circuit due to loose screws, use the solderless terminal with insulation sleeve.
2. When connection is made between LG and FG terminals, be sure to connect them to the ground.
Otherwise, the system becomes susceptible to noise.
Since the LG terminal has potential equal to a half of the input voltage, touching the terminal may lead to an electric shock.
27