6.2 Periodic Inspection. Mitsubishi Electric GT15
Tangazo
Tangazo
6.2 Periodic Inspection
Yearly or half-yearly inspection items
The following inspection should also be performed when equipment has been moved or modified or the wiring changed.
No.
1
2
3
4
Inspection Item
Surroun ding environ ment
Ambient temperature
Ambient humidity
Atmosphere
Power supply voltage check
Inspection
Method
100 to 240VAC
Measure voltage across terminals.
Criterion
Make measurement with thermometer or hygrometer
Measure corrosive gas
Display section
Other portions
10 to 90%RH
0 to 40
°
C
0 to 55
°
C
No corrosive gas
85AC to 242V
Move module
Visual check
Should be mounted firmly
No dirt, foreign matter sticking
Looseness
Mountin g status
Connecti on status
Dirt, foreign matter
Loose terminal screws
Proximate solderless terminals
Loose connectors
Retighten screws with screwdriver
Not loose
Visual check
Visual check
Proper intervals
Not loose
5 Battery
Check "GOT internal battery voltage status" in
"Time setting & display" of the
Utility. (Refer to the GT15 User's
Manual.)
No alarm appears
Action
For use in control panel, temperature inside control panel is ambient temperature
Change supply power
Retighten screws
Remove, clean
Retighten terminal screws
Correct
Retighten connector fixing screws
Replace with new battery when the current battery has reached the specified life span, even if battery voltage low is not displayed.