5.2 Power Supply Wiring
• Make wiring connections to the power supply, I/O equipment and power equipment separately by system as shown below.
When frequent noise is identified, connect an isolation transformer.
Main power GOT power
Isolation transformer
GOT
T1
I/O power
I/O equipment
Main circuit power
Main circuit equipment
Wiring diagram for power supply
• Twist 100V AC, 200V AC or 24V DC cable as closely as possible and connect the cable between modules at the minimum length.
Also, use the thickest cable as possible (0.75 to 2mm
2
) to minimize the voltage drop.
Use M3 solderless terminals and securely tighten them with a tightening torque of 0.5 to 0.8N
• m so that no problem will result.
• Separate the 100V AC, 200V AC or 24V DC cable from the main circuit lines (high voltage, large current) and/or I/O signal lines.
Keep a distance of 100mm or more.