5) Connect the GT15-C BS's FG cable on the PLC side to FG of the
PLC's power supply module.
6) Connect the LG and FG terminals of the terminal block on the PLC and ground them with a cable.
(2) When using GT15-C BS
For the both side GOTs, connect the LG and FG terminals of the terminal block on the GOT unit power and ground them with a cable.
5.4 Grouding
Make sure to carry out the followings for grounding.
• Carry out the independent grounding if possible.
• If the independent grounding is impossible, carry out the shared grounding as shown in fig.2) below.
GOT
Grounding
Other device
GOT
Grounding
Other device
GOT
Other device
(1) Independent ground
...... Best condition
(2) Shared grounding
...... Good condition
(3) Common grounding
...... Not allowed
• Use the cable of 2mm
2
or more for grounding.
Set the grounding point closer to the GOT to make the grounding cable short as possible.
(1) Example of independent grounding
Power equipment
(servo, etc.)
PLC
Connection cable
CN1A CN1B
CN 2C N3
FG
FG
LG
FG
LG
GOT
Ground terminal block
Panel grounding
Ground terminal block
Grounding for power system
Grounding for control system
25
* Ground the control system, especially modules communicating each other, to one end.
(2) Example of shared grounding
Power equipment
(servo, etc.)
PLC
Connection cable
CN1A CN1B
CN2C N3
FG
FG
LG
FG
LG
GOT
Panel grounding
Panel grounding
6.2mm or less
Use a short and thick cable as much as possible.
* Ground the system to one end.
Recommended terminal shape
3.2
Terminal screw
Solderless terminal
3.2
6.2mm or less
Terminal screw
Solderless terminal
When wiring one cable to one terminal
When wiring two cables to one terminal
Applicable solderless terminal RAV1.25- 3, V2- S3.3, V2- N3A, FV2- N3A
26