5. Wiring. Mitsubishi Electric GT15
Advertisement
Advertisement
5. Wiring
5.1 Wiring Precautions
DANGER
z Before starting wiring, always switch off the GOT power externally in all phases.
Not doing so may cause an electric shock, product damage or malfunction.
CAUTION
z Please make sure to ground FG terminal and LG terminal of the GOT power supply section by applying Class D Grounding (Class 3 Grounding Method) or higher which is used exclusively for the GOT.
Not doing so may cause an electric shock or malfunction.
z Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product.
Not doing so can cause a fire or failure.
z
Tighten the terminal screws of the GOT power supply section in the specified torque range. Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT.
z Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT. Not doing so can cause a fire, failure or malfunction.
This section describes wiring to the GOT power supply section.
For the connection with PLC CPU or others, refer to the following.
GOT1000 Series Connection Manual
Remarks
General preventive measures against noise
There are two kinds of noises: Radiated noise that is transmitted into the air and conductive noise that is directly transmitted through connected lines. In noise countermeasures, the both two types of noise should be taken into account. As the noise countermeasures, there are the following three methods.
21
(1) Protecting against noise
(a) Keep signal lines away from possible noise sources such as power cables or high-power driving circuits.
(b) Shield signal lines.
(2) Reducing generated noise
(a) Use a noise filter, etc. to reduce the noise generated from high-power motor drive circuits.
(3) Releasing noise to the ground
(a) Make sure to connect the ground cable to the ground.
(b) Use a ground cable as short and thick as possible to lower its impedance.
(c) Separate the grounding between power and control systems.
22