Below you will find brief information for Programmable Terminal NT NT20, Programmable Terminal NT NT20S, Programmable Terminal NT NT20M, Programmable Terminal NT NT20-ST121-E, Programmable Terminal NT NT20-ST128. The OMRON NT20 programmable terminal is a versatile device that can be used to display information, control equipment and communicate with a host system. It features a downsized and waterproof body, making it ideal for use in industrial environments. The NT20 can be connected to a variety of host systems including PLCs, PCs and other devices. It also supports various communications protocols such as Host Link, NT link, RS-232C, and C200H direct communications.
Advertisement
Advertisement
SECTION 1
Functions of the NT20
NT20 is a new programmable terminal (PT) which incorporates a host interface unit and two RS-232C interface units in a programmable terminal body. It can be easily installed and used. This section gives the operation examples and characteristics of the NT20 so that you will understand the applications of the NT20.
1-1-1 Operations of NT20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-2 Principal Functions of NT20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-3 Comparison between NT20S, NT20M, and NT20. . . . . . . . . . . . . .
1-4 Communications with PLC by Direct Connection . . . . . . . . . . . . . . . . . . . . .
1-4-1 Functions of the Allocated Bits and Words . . . . . . . . . . . . . . . . . . .
1-4-2 Connecting to PLC from Other Companies . . . . . . . . . . . . . . . . . . .
1-5 Communications Using RS-232C (NT20-ST128) . . . . . . . . . . . . . . . . . . . . .
1
2
Role and Operation of NT20
Section 1-1
1-1 Role and Operation of NT20
NT20 is a programmable terminal used to display and transmit the information in an FA site. The following gives a general description of the role and operation of the NT20 for those who use a programmable terminal (PT) for the first time.
Production Line Status
Monitoring
The NT20 displays real-time information about the system and equipment operating status, etc.
Production Control
1994/1/25
Product
NT20M/NT20S
560 units
NT600M
441 units
Today's target
Current Production
305 units
275 units
% achieved
54.5 %
63.0 %
Messages
The NT20 warns of system or equipment failures and prompts the appropriate remedial action.
Assembly line B is defective.
Alarm
-
Positioning pin
Panel Switch Functions
Setting touch switches on the NT20 allows workers to use the NT20 as an operating panel. Production data input to the NT20 or the Host can be transmitted to a PLC.
Electroplating Control
Transport
Clamp
UnClamp
Role and Operation of NT20
Section 1-1
1-1-1 Operations of NT20
Displays Screens
The information to be displayed (screen data) can be created on a computer by using the Support Tool and stored in the NT20. The screen data can be displayed on the NT20 in response to the instructions from a Host or touch switch operation.
Host
The screen data designated by instructions from Host or touch switch operation is displayed.
Receives Data from a Host
The NT20 can be connected to the Host using the host link or NT link communications method to enable reception of the required data from the Host.
Host link, NT link, RS-232C,
C200H direct communications
Host
Sends Data to a Host
Data input through a touch panel can be sent to a Host.
Host
Touch panel
ON/OFF information, numeric data, etc.
Screen Data
The screen data to be displayed on the NT20 can be created by a computer by using the Support Tool. Connect the NT20 to a PC/AT with an RS-232C cable so that the screen data are transferred to the NT20.
RS-232C
Create screen data.
PC/AT
(Support Tool)
Screen data
When the host is connected at serial port A, the personal computer is connected only when transferring screen data between the
NT20 and NT Support Tool.
3
Functions of NT20
Section 1-2
1-2 Functions of NT20
The NT20 has the following features which are different from those of existing
NT20M/NT20S;
1-2-1 Features
Downsized Body
• The connectors are located at other than the front.
• The communications cable connectors are housed in the unit so that they do not protrude from the unit.
• The tool connectors and the Host communications connectors are used in common (when the host link/NT link is used).
Construction Best Suited to the FA Environment
• Easy-to-read screen even in direct sunlight.
• Long-lived backlight leads free from maintenance.
• Waterproof structure equivalent to oil-resistant IP65.
256 dots
128 dots
Wide angle of visibility
±35°
A Host Link I/F Unit, Screen Data Memory, and a System ROM Are All Incorporated
• With the NT link communications method, 1:1 connections and 1:N connections are possible.
• There is no complicated installation work except a simple connection to a
Host.
• A flash memory is used for the screen data memory. There is no need of backup battery.
• The following communications methods are standard for each model:
NT20-ST121-E: Host Link (direct) and NT Link
NT20-ST121-E + NT20-IF001 + NT600M-LB122-V1: C200H direct communications
NT20-ST128: RS-232C communications (command control)
• The NT20 can be connected to Mitsubishi FX-series and Mitsubishi Aseries PLCs. (Refer to PLC Connection, Operation Manual (Cat. No.
V042-E1@)).
Touch Switch Operation
The System Menu can be displayed by using the touch switches located in four corners of the screen.
Compatibility with NT20M/
NT20S
Existing screen data, user programs, are compatible.
4
Functions of NT20
1-2-2 Principal Functions of NT20
Functions Related to the Data Display
• Character display
Characters of various sizes can be displayed. Characters can flash or be highlighted.
• Figure display
Straight lines, circles, and other graphic figures can be displayed.
• Memory data display
Contents of the character-string memory table and the numeral memory table can be displayed. The memory table contents can be changed from the PLC/Host.
• Bar graph display
Bar graphs corresponding to the contents of the numeral memory table can be displayed.
• Lamp display
Lamps which turn on or flash as controlled by the Host can be displayed.
Section 1-2
Functions Related to the Data Input
• Input by the touch switch
Data can be input by simply touching the screen.
• Numeric setting function
The touch keys can be assigned with numeric values so that the numeric values can be input at the operation site and sent to the PLC/Host.
Other Functions
• Buzzer
A built-in buzzer can be used.
• Communications with a PLC
By connecting the NT20 with a PLC using the host link, NT link, C200H, or RS-232C communications method, data can be received from the host and touch switch status information can be sent to the host.
• System function
The system setting and maintenance can be executed by using the
System Menu on the screen.
• Screen data creation
The screen data can be created by using support tools on the computer and stored in the unit.
• Unrestricted screen display
When the NT20 is connected to the host via an RS-232C interface, characters and graphics can be displayed independently of the registered screens (terminal function) (only with NT20-ST128).
5
Functions of NT20
Section 1-2
1-2-3 Comparison between NT20S, NT20M, and NT20
The NT20 is a unitary PT which incorporates a system ROM, screen memory, and a host I/F unit (Host link, NT link, RS-232C, and C200H direct communications) as the standard equipment in one body.
The NT20 has the following features which are different from those of existing
NT20/NT20S:
Function
Communications
Communications connector
NT20S
• Host link/NT link incorporated NT20S-ST121-EV3
• C200H direct communications incorporated
NT20S-ST122-V1
• RS-232C incorporated
NT20S-ST128
(other host I/F units cannot be connected)
NT20M-DT121-V2
Host I/F units are required.
NT20
• Host link/NT link
• C200H direct communications
Host I/F unit for C200H communications is required.
• RS-232C incorporated
NT20-ST128 (other host I/F units can not be connected)
• The communications connector (9-pin) for a Host is shared with that for the Support Tool. (NT20S-ST121-
EV3/ST128)
• Connectors for Support Tool
(9-pin) and Host connections on the rear face
(NT20S-ST122-V1).
Not provided
The Support Tool connector
(9-pin) is located on the front.
The Host connector (25-pin) is located on the back.
Provided
• The communications connector (9-pin) for a Host is shared with that for the Support Tool. (Port A)
• The communications connector (9-pin) for a Host
(Port B)
Not provided Host RUN input terminal/
Alarm output terminal
System keys
Contrast control
Waterproof performance
Not provided
Back
Equivalent to oil-resistant
IP65
Not guaranteed
Provided
Front
Conforms to IP54F.
5 ms Allowable momentary power interruption time
System ROM Built in (not replaceable)
Not provided
Back
Equivalent to oil-resistant
IP65
Not guaranteed
Resume function Not provided
History retaining function Not provided
Screen transfer
❍
Screen data compatibility
❍ (Note)
PLC ladder compatibility
❍
Backlight replacement
❍
Screen data memory Built in (flash ROM only)
Screen data memory capacity
Outside dimensions
96KB
190
× 110 × 58 mm
System ROM compatible with host I/F unit is required.
Flash ROM rewriteable
Provided Not provided
Provided
❍ (Only possible if screen data memory is an SRAM)
Not provided
❍
–
–
❍ (Note)
❍
Possible with NT20M-DT131. Do not need
Built in (Flash ROM) Optional (select from
EPROM, SRAM, and
EEPROM)
128 KB max.
512 KB
220
× 110 × 82 mm
190
× 108 × 53.5 mm
Note
If a system key function is required on continuous screens or for numerical setting or buzzer stop, use the Support Tool and set the touch switches which have the system key function in such screens.
For details, refer to 4-7-3 System Key Functions on page 154.
6
Functions of NT20
1-2-4 Displays
Characters
(character string)
Characters (text)
Bar graph
Section 1-2
The NT20 can display various kinds of elements such as characters, lamps, touch switches, and bar graphs on a screen. The screen data displayed on the
NT20 are created by using the Support Tool on a computer.
Touch switches
Line 1 Status
Machine name : NT20
Production qty. : 137 units
Emergency stop
Restart
Numeric value
(Numeral table)
0%
Stage 1
50%
Stage 2
100%
30%
Stage 3
Lamps
Characters (Text)
Characters and marks which do not need to be changed can be written directly to the screen.
Characters (Character-string Memory Table)
Character-strings stored in the character-string memory table are displayed.
The display characters can be changed by changing the data stored in the character-string memory table.
Numeric Values (Numeral Table)
Numbers stored in the numeral table are displayed. The display numbers can be changed by changing the data stored in the numeral table. Hexadecimal values can also be displayed.
Lamps
Touch Switches
Numeric Keys
Bar Graphs
Lamps are displayed as square or round frames and indicate the operating status. They are controlled by the Host and can be lit (reversed) or made flash
(alternates normal with reversed displays).
Touch switches can be set anywhere on the screen. Touching the screen at a touch switch location can switch the display (display switch function) or notify the Host (notification function). The touch switches can be lit or made flash by controlling from the Host in the same way as the lamps.
These are the touch switches used to input numeric values.
Marks
The bar graph extends and contracts in proportion to the data stored in the numeral table. A percentage value can also be displayed simultaneously.
Marks can be designed, created, and handled like characters by the user.
7
Method for Connection to the Host
Section 1-3
1-3 Method for Connection to the Host
This section describes the methods for connection to the host used with the
NT20, and the relationship between the connection method and the communications method.
NT20 Communications Ports and Communications Methods
The NT20 has two communications ports. Their uses are indicated in the table below.
Communications
Port
Serial port A
Usable Communications
Host Link
Methods
1:1 NT Link
1:N NT Link (See note.)
RS-232C (command control) (NT-
20-ST128)
(NT Support Tool connection)
Serial port B Host Link
1:1 NT Link
1:N NT Link (See note.)
RS-232C (command control) (NT-
20-ST128)
Communications
RS-232C
RS-232C
Note
There are two 1:N NT Link communications rates: standard and high-speed.
Converting Communications Type with the RS-232C/RS-422A Link
Adapter and RS-422A Converter
An OMRON NT-AL001 Link Adapter or CJ1W-CIF11 RS-422A Converter can be used convert from RS-232C communications to either RS-422A or RS-
485.
• RS-232C
⇔ RS-422A
•
RS-232C ⇔ RS-485
There are two models of Link Adapter/RS-422A Converter are available. They provide different features:
• NT-AL001 Link Adapter
The RS-232C port is insulated from the RS-422A/485 terminals. An RS-
232C cable (2 m max.) can be connected to either serial port A or B on the NT20.
• CJ1W-CIF11 RS-422A Converter
The RS-232C port is not insulated from the RS-422A/485 terminals. The
CJ1W-CIF11 RS-422A Converter can be connected to either serial port A or B on the NT20.
• Communications Distance
Use the NT-AL001 if the communications distance exceeds 50 m.
8
Method for Connection to the Host
Section 1-3
Communications type at Host
RS-232C
Combinations of Communications Method and Connection Method
The connection methods that can be used depending on the communications method used and the communications type for communications between the
NT20 and the host are indicated in the table below.
Usable Connection Method
Direct 1:1 connection
PT
Host
Usable Communications Method
❍
Host Link 1:1 NT Link 1:N NT Link
❍ ❍
RS-232C
RS-232C (15 m max.)
1:N connection with RS-422A through
Link Adapter and RS-422A Converters
PT
NT-AL001 (See note 1.) or CJ1W-CIF11 RS-
422A Converter NT-AL001
Link Adapter
Host
RS-422A
(total length 500 m,
See note 2.)
RS-232C
(2 m max.)
× × ❍
RS-232C
1:N connection with RS-485 through
Link Adapter and RS-422A Converters
PT
NT-AL001 (See note
1.) or CJ1W-CIF11
RS-422A Converter NT-AL001
Link Adapter
Host
RS-485
(total length 500 m,
See note 2.)
RS-232C
(2 m max.)
× × ❍
Note
❍: Connection possible ×: Connection not possible
(1) An RS-232C Cable (not shown in the diagram) is required when connecting an NT-AL001 Link Adapter to a PT.
(2) If the CJ1W-CIF11 is used, the total communications distance is 50 m.
This also applies if both the NT-AL001 and CJ1W-CIF11 are used in the same communications path.
9
Communications with PLC by Direct Connection
Section 1-4
1-4 Communications with PLC by Direct Connection
1-4-1 Functions of the Allocated Bits and Words
When using an NT20-ST121 @ with the direct connection function (host link or
NT link), the elements displayed on the NT20 and the NT20 status can be allocated to the bits and words of the PLC. By changing the contents of the bits and words, the NT20 can be controlled by the PLC. It is also possible to send data to the PLC by pressing the touch switches on the NT20.
• Controlling the NT20 by a PLC
The following NT20 functions can be controlled by a PLC.
Screens:
Memory tables:
Display of designated screens, confirmation of screen numbers, etc.
Writing to a memory table, copying from a memory table entry to another memory table entry, etc.
Lamps and touch switches: Display instructions, confirmation of display status, etc.
System control:
• Notifying the PLC from the NT20
Data in the NT20 is sent to a PLC when a touch switch is pressed. The following types of data are sent to a PLC.
• NT20 status
Buzzer ON/OFF, backlight ON/OFF, and other NT20 status
• Touch switch status
• Numerical values input with touch switches by using the numeral setting function
• Changes in a memory table after copying between memory table entries
Functions of Display Elements
• Lamps
Allocation destination: Bit
Lamp #1 (Bit 000100)
NT20 PLC
Lit
Unlit
Switch 1: ON (Bit 000100)
Switch 2: OFF (Bit 000101)
Lamp #2 (Bit 000101)
PLC’s bit status is displayed by the “Lamp” on the NT20.
The lamp comes on (flashes) when the PLC’s bit status (lamp bit) is ON
(1), and goes off when it is OFF (0).
10
Communications with PLC by Direct Connection
• Touch Switches
Allocation Destination: Bit
Touch switch
12 Bit 009012
NT20 PLC
Section 1-4
Bit 009012: ON
The lamp comes on (flashes) when the PLC’s control bit is ON (1) and goes off when it is OFF (0). When the touch switch is pressed, the PLC’s notification bit comes ON (1) or goes OFF (0).
• Numeral Memory Table
Allocation destination: Word
Numeral memory table entry 1 (TIM003)
NT20
PLC
Numeral memory table entry 150 (word 0005)
Allocate the numeral memory table entries to arbitrary words in the PLC. If word contents change when corresponding numeral memory table entry is displayed on the screen, the value on the screen will also change. Monitoring of words can also be made easily.
Reading and writing are executed so that the contents of allocated words and contents of numeral memory table entries are always the same during display.
• Character-string Memory Table
Allocation destination: Word
NT20 PLC
("a", "b")
("c", "d")
("e", "f")
Character-string memory table entry 1
Allocated word number: 3
First word: DM0100
Allocate character-string memory table entries to arbitrary words in the
PLC. If word contents change when corresponding character-string memory table entry is displayed on the screen, the value on the screen will also change. Messages can be displayed easily.
Reading and writing are executed so that the contents of allocated words and contents of character string memory table entries are always the same during display.
11
Communications with PLC by Direct Connection
Section 1-4
Functions of the PT Status Control Area (PLC to NT20)
The “PT status control area” is used to control the NT20 status. When data is written to this area in the PLC, the NT20 reads the contents and operates according to the contents.
Example of the PT Status Control Area Application
When data is written to the PT status control area, the NT20 will operate as given below.
Screen 3 display
NT20 PLC
Continuous buzzer sound
PT status control area
Screen switch setting
Memory table entry
Copy setting
PT status control bits
Numeral memory table entry 50
Copy
Numeral memory table entry 7
Functions of the PT Status Notify Area (NT20 to PLC)
The “PT status notify area” is used to notify the PLC of changes of the NT20 status. When a change is made in the NT20 status, the change is written to this area in the PLC. By reading the data from the area, the NT20 status can be checked.
Example of the PT Status Notify Area Application
When a change is made in the NT20 status, such change will be indicated in the PT status notify area as described below.
NT20 PLC
12345678
Numeral memory table entry 13
12345678
PT status notify area
Currently display screen
Updated memory table entry
PT status
Allocated word (numeral table entry 13)
12345678 Start
Start + 1
1-4-2 Connecting to PLC from Other Companies
The NT20 can be connected to PLCs from other companies using the computer link method.
Connectable PLCs
The NT20 can be connected to the following PLCs.
• Mitsubishi A-series Sequencers (via Computer Link Unit)
• Mitsubishi FX-series Sequencers
Refer to the PLC Connection Manual (Cat. No. V042) for connection methods.
NT Series Support
Software
The following Support Software is required when connecting PLCs from other companies.
Support Software: NT-ZJCAT1-EV4(S) (NT Series Support Software for
Windows, Version 4.
@)
12
Communications Using RS-232C (NT20-ST128)
Section 1-5
1-5 Communications Using RS-232C (NT20-ST128)
This section gives a brief description of the NT20 control commands sent from the host through the RS-232C interface when the NT20-ST128 is used.
For details on each of the commands sent through the RS-232C interface,
refer toSECTION 6 Using RS-232C Communications.
Control of the NT20 by a Host is executed by two kinds of commands supported by the RS-232C interface that is built into the NT20.
Operation Commands
Terminal Commands
Operation commands are used to control the display and status of the running
NT20 as well as to provide notification.
They are used for purposes such as screen display, data writing, and enquiries.
Notification of the NT20 operation contents can be provided to the Host.
Terminal commands are used to use the NT20 as a display terminal of the
Host.
When the NT20 is used as a display terminal, it can display characters and figures according to instructions given by the Host, independently of the screens registered to the NT20.
These commands are also used if unexpected problems occur.
13
Before Operating
Section 1-6
1-6 Before Operating
Follow the procedure given below to start the system of the NT20.
Host
Set the host settings.
• For the Host Link, refer
uals for the Host Link
Unit and Programming
Device.
• For a 1:1 NT Link, refer
• For 1:N NT Links, refer to
• For high-speed 1:N NT
• When using C200H direct communications, no settings are required.
• For RS-232C, refer to
als for the Host.
NT20
Set the DIP switch pins.
Install the PT in the operation panel.
NT Support Tool
Install the NT Support
Tool in the computer.
(Refer to the NT Support Tool
Operation Manual.)
Connect the power supply and peripheral device.
Install the system program.
(See note.)
Support Tool operation manual.)
Transmit the screen data.
Create the screens.
(Refer to the NT Support Tool
Operation Manual.)
Connect to the NT20.
Set the memory switches.
Connect to the host.
Create the host program.
Confirm the settings and check communications.
Note
Start operation.
System program installation is only done in special circumstances, for example when changing the system program, or when recovering the original status of the installed program. This operation is not normally necessary.
14
Before Operating
Section 1-6
Refer to the following manuals for the equipment and software.
Device or Software
NT20 User’s Manual
System Installer
NT Support Tool
PLC
Manual Title
NT-series Support Tool for Windows (Ver. 4.8) Operation Manual
NT-series Support Tool for Windows (Ver. 4.8) Operation Manual
SYSMAC CPM1 Operation Manual
SYSMAC CPM1A Operation Manual
SYSMAC CPM2A Operation Manual
SYSMAC CPM2C Operation Manual
SYSMAC C200H Operation Manual (for CPU01/03/11) (Programming)
SYSMAC C200H Operation Manual (for CPU21/23/31) (Programming)
CompoBus Master
Control Unit
Programming Tools SYSMAC Support Software Operation Manual: C-series PLCs
Host Link Unit/
Serial Communications Board
SYSMAC C200HS Installation Guide
SYSMAC C200HS Operation Manual (Programming)
SYSMAC C200HX/HG/HE (-Z) Installation Guide
SYSMAC C200HX/HG/HE Operation Manual
SYSMAC C200HX/HG/HE-Z Operation Manual
SYSMAC CQM1/CPM1/CPM1A/SRM1 Programming Manual
SYSMAC CQM1H Operation Manual
SYSMAC CVM1/CV500/CV1000/CV2000/CVM1 Operation Manual: Ladder Diagrams
CS Series Programmable Controllers Operation Manual
CJ Series CJ1G-CPU @@-E Programmable Controllers Operation Manual
CS/CJ Series Programming Manual
CS/CJ Series Serial Communications Boards/Units Operation Manual
SYSMAC CQM1H Series Serial Communications Board Operation Manual
SRM1 (-V2) Operation Manual
SYSMAC Support Software Operation Manual: CVM1 PLCs
SYSMAC CPT User Manual and Quick Start Guide
CX-Programmer Ver. 4 User Manual
SYSMAC C Series Host Link Unit System Manual
SYSMAC CVM1/CV Series Host Link Operation Manual
SYSMAC C200HW-COM01 C200HW-COM02-V1 to C200HW-COM06-EV1 Communications Board Operation Manual
W339-E1-
@
W393-E1@
W394-E1@
W336-E1@
W365-E1-
@
W318-E1@
W248-E1@
W249-E1@
W332-E1-
@
W333-E1-
@
W425-E1@
W143-E1@
W205-E1@
W304-E1-
@
Cat. No.
V091-E1@
V061-E1-
@
V061-E1@
W262-E1@
W317-E1@
W352-E1-
@
W356-E1@
W130-E1@
W217-E1@
W236-E1-
@
W235-E1@
W302-E1@
W303-E1@
W322-E1-
@
W228-E1@
W363-E1@
W202-E1@
15
Before Operating
Section 1-6
16
Download
Advertisement
Key features
Downsized body
Waterproof structure equivalent to oil-resistant IP65
Host Link I/F Unit, Screen Data Memory, and a System ROM are all incorporated
Touch switch operation
Compatibility with NT20M/NT20S
Character display
Figure display
Memory data display
Bar graph display
Lamp display
Frequently asked questions
The NT20 supports the following communications methods: Host Link, NT Link, RS-232C, and C200H direct communications.
The NT20 can be connected to OMRON PLCs and Mitsubishi FX-series and Mitsubishi A-series PLCs.
The NT20 can be used to display data, receive data from a host system, send data to a host system, control equipment and provide alarm notifications.
The screen data is created using support tools on a computer and then stored in the NT20.
The NT20 is connected to a PC/AT using an RS-232C cable for transferring screen data.