Appendix A
Specifications
General Specifications
Item
Power supply voltage
Allowable power supply voltage range
Allowable momentary power interruption time
Power consumption
Ambient operating temperature
Storage temperature
Ambient operating humidity
Ambient storage humidity
Operating environment
Noise immunity
Vibration resistance (during operation)
Shock resistance (during operation)
Dimensions (mm)
Panel cutout dimensions
Weight
Degree of protection
Applicable standards
Specification
24 VDC
20.4 VDC to 27.6 VDC (24 VDC –15% +15%)
Not specified.
10 W max.
0 to 50
°C (with no freezing)
–20 to 70
°C
35% to 85% at 0 to 40
°C (with no condensation)
35% to 50% at 40 to 50
°C (with no condensation)
35% to 85% at
−20 to 40°C (with no condensation)
35% to 50% at 40 to 50
°C (with no condensation)
35% to 45% at 50 to 70
°C (with no condensation)
No corrosive gases.
Based on IEC 61000-4-4: 2 kV (power line)
5 to 9 Hz with 3.5-mm single amplitude, 9 to 150 Hz with 9.8-m/s
2
acceleration for 10 times (1 octave/min) in each of X, Y and Z directions
147 m/s
2
, 3 times in each of X, Y and Z directions
190 x 108 x 53.5 mm (W x H x D)
178.5
+0.5
/
0
x 98.5
+0.5
/
0
mm (H x V), Panel thickness: 1.6 to 4.8 mm
0.7 kg max.
Front panel operating section: Equivalent to oil-resistant IP65 and equivalent to NEMA4 (See note 2.)
UL 1604 Class 1 Division 2 and EC Directives
Note
(1) The display quality (e.g., the contrast) will deteriorate at temperatures above 40
°C. Also, response will be slower due to the characteristics of liquid crystals at low temperatures.
(2) Do not use the PT in locations subject to long-term exposure to oil.
255
Specifications
Appendix A
Performance Specifications
Display Specifications
Item
Display panel
(See note 1.)
Backlight
(white cold cathode tube)
Front-panel indicator
Specification
Display device
Number of dots
(resolution)
Monochrome STN LCD (with backlight)
140 (128) vertical
× 260 (256) horizontal, dot size: 0.42 mm
Values in parentheses are the numbers of dots that can be used by the NT20 system program.
Effective display area 66 (57.6) mm vertical
× 120 (115.2) mm horizontal
Values in parentheses are effective display area that can be used by the NT20 system program.
Display mode
View angle
Life expectancy
Blue mode
Up: 40
°, Down: 50°, Left: 35°, Right: 35°
50,000 hours minimum
Contrast adjustment The contrast can be adjusted with the contrast adjustment on the back of NT20.
Life expectancy
Replacement
50,000 hours minimum (See note 2.)
User must not replace the backlight.
Brightness adjustment Not provided.
Automatic turn-off Can be set to turn off in 10 minutes, 1 hour, or to remain ON.
RUN Lit green: Running normally and Memory Unit automatic transmission completed.
Flashing green: Memory Unit automatic transmission being executed or Memory
Unit automatic transmission error.
Note
(1) There are sometimes faulty pixels in the touch panel but this does not indicate an error as long as the number of bright or dark pixels does not exceed the following limits.
4 total defects max. of the following size with no more than one per 20-mm square:
0.2 mm < (short dia. + long dia.)/2
≤ 0.55 mm
(2) Time taken for brightness to reduce to half at room temperature and humidity. This is a reference value only. The life expectancy will be radically reduced at low temperatures. For example, the life expectancy at 0
°C or lower will be 10,000 hours (reference value).
Panel Specifications
Item
Touch panel
Specification
Number of switches: 72 (6 vertically
× 12 horizontally)
Switch size: 9.14 mm horizontal
× 9.18 mm vertical
Input: Pressure-sensitive type
Life expectancy: 1 million operations min.
256
Specifications
Appendix A
Display Capacity
Display elements
Item
Character displays
Character string displays
Specification
Host Link/NT Link
C200H direct communications
RS-232C (NT20-ST128)
Fixed character data (character strings registered for each screen)
32 positions per screen 128 strings per file, 32 positions per screen
Screen types
Screen attributes
Numeral displays
(See note.)
Graph displays
(See note.)
Graphic displays
Lamps
Continuous screens
50 positions per screen, 8-digit display
50 per screen
Can be displayed wherever required.
128 per screen 256 strings per file max.
Touch switches
Numeral settings
(See note.)
Normal screen
72 per screen 256 strings per file max.
Display of set numerical values 50 per screen, 8 digits each
Displays screens registered as normal.
Overlapping screens A maximum of 8 registered screens can be displayed overlapped with each other.
A maximum of 8 screens can be displayed sequentially by scrolling.
(The screen can be changed by pressing the and touch switches)
Buzzer, numeral setting, backlight Buzzer, numeral setting, backlight, bit input
Max. number of registered screens
Screen registration method
Screen saving method
(screen data memory)
495
Transfer screen data created using the Support Tool to the PT.
Saved to flash memory (recording format unique to NT20)
Note Number of numeral memory table entries that can be set (number used for numeral display + number used for graphs + number used for numeral settings)
≤ 128
Display Element Specifications
Display characters
Item
Enlargement function
Smoothing processing
Character display attributes
Graphics
Specification
Half-size characters (8
× 8 dots): Alphanumerics and symbols
Normal characters (8
× 16 dots): Alphanumerics and symbols
Marks (16
× 16 dots): User-defined pictographs
Horizontal and vertical magnifications of double width, double height, 4x, 9x, and 16x
Enlarged characters up to 4x
Normal, inverse, flashing, inverse flashing
Continuous straight lines, circles
Data Quantities
Item
Strings
Numeral data
Marks
Touch switches
Lamps
Specification
Host Link/NT Link
C200H direct communications
128 strings comprising 32 characters each
RS-232C (NT20-ST128)
128 max. (8 digits each)
64 marks
No maximum restriction
No maximum restriction
256 strings per file max.
256 strings per file max.
257
Specifications
Appendix A
Special Features
Buzzer
Item
Maintenance functions
Key input sound setting
Two types:
Setting:
Specification
Continuous sound and intermittent sound
Set “Buzzer Sound” in the “Memory Switch” menu of the
Maintenance Mode ON.
ON:
If “ERR ON” is set the buzzer only sounds when an error occurs.
The buzzer sounds on designation from the PLC, when a screen with a buzzer-ON specification is called, or on display of an error screen such as for a receive error.
OFF: The buzzer is turned off on designation from the PLC, by touch switch input, or when a screen without a buzzer-ON specification is displayed.
Sound pressure: Min. 80 dB, average 87 dB (measured 10 cm from front face)
• Self-test for memory, switches, etc.
• Status setting confirmation for communications and other conditions.
• Simple communications confirmation.
0.2 second input sound when a touch switch is pressed
Setting: Set “Key Sound” of the “Memory Switch” menu in the Maintenance mode ON.
Note The NT20 system program does not provide a battery backup function.
258
Specifications
Appendix A
Communications Specifications
Host Link
Item
Communications standard
Communications settings
Specification
EIA RS-232C
Start-stop synchronization
Baud rate: 9,600, 19,200, 38,400, 57,600, 115,200 bps
Data length: 7 bits
Stop bits:
Parity:
2 bits
Even
9-pin, D-SUB connector (female)
1 to 1
15 m max.
Connector
Number of units connected
Transmission distance
NT Link (1:1)
Item
Communications standard
Connector
Number of units connected
Transmission distance
NT Link (1:N)
Item
Communications standard
Connector
Number of units connected
Transmission distance
EIA RS-232C
9-pin D-SUB connector (female)
1 to 1
15 m max.
Specification
Specification
EIA RS-232C
9-pin D-SUB connector (female)
1:1 to 8
RS-232C cable: 2 m max. (*)
RS-422A/485 cable: Total length 500 m (*)
(*) When NT-AL001 used
RS-232C (NT20-ST128)
Item
Communications standard
Communications settings
Connector
Number of units connected
Transmission distance
Specification
EIA RS-232C
Start-stop synchronization
Baud rate: 2,400, 4,800, 9,600, 19,200 bps
Data length:
Stop bits:
7, 8 bits
1, 2 bits
Parity:
Flow control:
Even, Odd, None
RS/CS control
XON/XOFF control
None
9-pin D-SUB connector (female)
1 to 1
15 m max.
259
Specifications
Appendix A
260