Registering the Screen Data
Section 3-6
3-6 Registering the Screen Data
The screen data is created by using the Support Tool and registered to the
NT20 screen data memory. This section describes the procedure to register the screen data to the NT20. For the screen data creation and the Support
Tool operation, refer to the NT-series Support Tool Operation Manual (Cat. No.
V061).
Note
The screen data transmission speed can be increased by setting “Hi speed” for “Communications Mode” on the Tool Settings screen of the Support Tool.
Unit of Screen Transmission – Transmission in File Units
The NT20 uses several screens which are switched on its display. The screen data of one NT20 unit corresponds to the files created by using the Support
Tool. Select a file which contains the screen data to be transmitted when selecting the screen data to be transmitted to the NT20 so that the required screen data can be transmitted to the NT20.
Screen data file
Screen 1
Screen 2
:
NT20
Screen 1
Screen 2
:
Screen N
All screen data is transmitted by one operation.
Screen N
Memory tables Memory tables
Mark data Mark data
System memory System memory
(Direct information) (Direct information)
When the screen data is transmitted from the Support Tool to the NT20, the screen data already existing in the NT20 will be erased.
If an error message and the System Menu are displayed immediately after the
NT20 has been started, the screen data memory needs to be initialized.
Data Transmission in Screen Units
The NT20 allows the transmission of data for specified screens. By selecting the screen number of the screen to be transmitted using the Support Tool, it is possible to transmit the required screen only to the NT20 (it is also possible to transmit multiple screens in a batch).
When changes have also been made to the memory table entries or direct connection information, transmit the changed data to the NT20 too, for example by using transmission in screen units.
Support Tool NT20
Screen 2
Screen 1
Screen 2
:
Only the required screen data is transmitted.
Screen N
Memory tables
(Direct information)
!Caution When screen data transmission is in screen units, if there is data other than screen data, for example memory table or direct access changes, transmit this data also.
102
Registering the Screen Data
Section 3-6
Note
Transmitting the Screen Data from the Support Tool
To transmit the screen data from the Support Tool to the NT20, connect the
NT20 to the computer on which the Support Tool is being used, and follow the procedure below.
Note
When screen data is transmitted to an NT20, it is written into a free area of the memory without overwriting the existing data. This means that if data transmission in screen units is performed frequently, there will come a time when there is no more free area in the memory and further transmission is impossible. If this happens, transmit the data in file units to reorganize the contents of the NT20 memory.
When the screen data transmission is attempted, the screen data memory in the NT20 is automatically initialized before new screen data is transmitted. It is not necessary to initialize the screen data memory by using the menu before the screen data transmission.
The NT20-ST121-E/ST128 uses the same connector for screen data transmission and connection to the Host. If this connector is currently connected to the host, disconnect the cable from it and connect it to the Support Tool (personal computer) before attempting screen data transmission.
1,2,3...
1.
Connect the NT20 to a PLC in which the Support Tool has been installed and turn on the power to the NT20.
2.
Turn ON the computer and start up the Support Tool.
3.
Enter the “Transmit Mode” by operating the menu of the NT20 as described below.
Select “Transmit Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ TRANSMIT MODE ]
The transmit mode is established. When using an NT20, the “Support Tool mode” setting will be displayed on the bottom line of the screen, as shown in the figure to the left.
ABORT
Tool Mode NT20S
4.
Select a screen data to be transmitted to the NT20 in the File Selection screen of the Support Tool, and press the Send key.
5.
The NT20 will display the following screen when the screen data is being transmitted.
103
Registering the Screen Data
Section 3-6
[ TRANSMIT MODE ]
Tool
→ PT
Screen Data
0 KB
ABORT
Tool Mode NT20S
6.
When the screen data transmission is completed, the Support Tool will display the following screen.
Note
7.
Press any key on the Support Tool to return to the File Selection screen.
8.
Pressing the ABORT touch switch in the Transmit Mode screen of the
NT20 will exit the Transmit Mode and enter the RUN Mode.
Press the “Abort” touch switch on the NT20 when the screen data transmission is completed. Unless this touch switch is pressed, the screen data will not be correctly registered. If the “Abort” touch switch is pressed during transmission, the screen data will not be correctly registered.
If screen data cannot be transmitted from the Support Tool, confirm normal communications between the NT20 and the Support Tool (Personal computer). Use the tool communications check function in the Maintenance Mode
of the NT20 to check communications with the Support Tool. Refer to Check-
ing the Communications with the Support Tool on page 116.
Precautions to Be Observed during Screen Data Transmission
When any of the following or a system error occurs during the screen data transmission, the transmitted screen data will not be registered correctly to the NT20. If an error message is displayed in the System Menu and the RUN
Mode cannot be selected, the screen data memory needs to be initialized.
• The power to the NT20 is interrupted or reset.
• The power to the computer on which the Support Tool is running is interrupted or reset.
• The cable connecting the NT20 to the computer on which the Support
Tool is running is interrupted or reset.
• The “Abort” touch switch on the NT20 screen is pressed to end the transmission.
• The ESC key on the Support Tool is pressed to end the transmission.
When the power to the NT20 is turned ON or reset, the screen data is checked. However, if any of the above occurs during the screen data transmission, the screen may disappear and other unexpected problems may occur.
In the case of such problems, set DIP SW2-1 to ON to initialize the memory.
For the memory initialization by using the DIP switch, refer to the 3-4-2 Initial-
ization by Using the DIP Switch (Forced Initialization) on page 90.
104