Communicating with the PLC Using C200H Direct Communications
Section 2-7
2-7 Communicating with the PLC Using C200H Direct
Communications
Connect an NT20-ST121-E and PLC made by OMRON with an I/O cable.
2-7-1 Applicable PLC Units
Before making the connection, check the series and model of the PLC to which the connection is to be made. A list of the PLCs that can be connected to an NT20 using C200H direct communications is presented below.
CPU Unit
C20H/C28HC40H/C60H C @@H
C200H-CPU01-E C200H
C200H-CPU03-E
Model Name
C200H-CPU11-E
C200H-CPU21-E
C200H-CPU23-E
C200H-CPU31-E
C200HS-CPU01-E
C200HS-CPU03-E
C200HS-CPU21-E
C200HS-CPU23-E
C200HS
C200HS-CPU31-E
C200HS-CPU33-E
C200HE-CPU11-E
C200HE-CPU32-E
C200HE-CPU42-E
C200HG-CPU33-E
C200HG-CPU43-E
C200HG-CPU53-E
C200HG-CPU63-E
C200HX-CPU34-E
C200HX-CPU44-E
C200HX-CPU54-E
C200HX-CPU64-E
C200HE
C200HG
C200HX
!Caution With systems in which the user program operates according to the PLC cycle time, since there is some fluctuation in the PLC cycle time, the system operation may not be consistent, and this should be born in mind when designing the system.
2-7-2 Connection Method
The NT20 PT is connected to the PLC using the NT20-IF001 and NT600M-
LB122-V1.
The connection conditions are different for C200H/HS, C200HX/HG/HE and
C @@H.
73
Communicating with the PLC Using C200H Direct Communications
Mounting the NT20-IF001
Section 2-7
1.
As shown in the following diagram, connect the NT20 connector on the back of the NT20-IF001 to the expansion interface connector on the NT20
PT.
2.
After connecting the connector, secure the NT20-IF001 with the two screws. The tightening torque is 0.6 N
• m.
3.
As shown in the following diagram, hold the Interface Unit with the notch on the left and press the Interface Unit into the NT20-IF001 until it clicks into place.
Notch
4.
Connect the ground screw on the NT20-IF001 to the NT20 using a short wire (100 mm max.), and connect the ground through the NC terminal.
Reference:
The NC terminal on the NT20 also serves as a functional ground. Do not connect this terminal when using only the NT20 (grounding is not required).
!Caution Always turn off the power at the PLC and PT before connecting the C200H interface cable. Otherwise the system may operate unpredictably.
!Caution Make sure that the power supply to the PT is OFF before connecting or disconnecting the Interface Unit. After mounting an NT20-IF001, be sure to tighten its two screws. Do not touch the PCB (printed circuit board) with bare hands.
!Caution After connecting the communications cable, always secure it with the screws.
Otherwise the cable may disconnect, causing operation to fail.
74
Communicating with the PLC Using C200H Direct Communications
Section 2-7
Connection to C200H/
C200HS and C200HX/HG/
HE
I/O Connecting Cable
Use the following models of I/O Connecting Cable.
For connecting C200H/HS/HE/HG/HX
For connecting C @@H
Model
C200H-CN311
NT20M-CNP711
C200H-CN711
NT20M-CNP221
C200H-CN221
NT20M-CNP521
C200H-CN521
NT20M-CNP131
C200H-CN131
C20H-CN312
NT20M-CNP712
C20H-CN712
NT20M-CNP222
C20H-CN222
Cable Length (L)
30 cm
70 cm
2 m
5 m
10 m
30 cm
70 cm
2 m
Note
The C200H interface connector of NT20M-CNP @@@ has been downsized.
!Caution Keep the total length of I/O cables used within 12 m (6 m for C
@@H).
!Caution The cable's tensile load is 30 N. Do not subject it to loads greater than this.
Otherwise a discontinuity may occur, causing operation to fail.
Reference:
If a C200H-CN
@@@
or C20H-CN
@@@
is used as the I/O Connecting Cable, the connector will project beyond the bottom face of the NT20.
If the I/O cable is passed through a hole or other opening, the diameter of the hole or opening must be at least 53 mm
φ. Removing the top cover reduces this requirement to 33 mm
φ or larger. During installation, this cover must be replaced before securing the PT.
Connect the CPU Rack or Expansion I/O Rack with an I/O cable. The following restrictions apply when making this connection.
• A maximum of one CPU Rack and one Expansion I/O Rack can be connected. Connection to two Expansion I/O Racks is not possible.
• Connection to a Remote Rack is not possible.
75
Communicating with the PLC Using C200H Direct Communications
Section 2-7
• There is only one C200H interface unit interface connector. This means that it is not possible to connect an NT20 between a CPU Rack and an
Expansion I/O Rack. It must be the final connection in the system.
CPU Rack
Expansion I/O Rack
Expansion I/O Cable
(C200H-CN @@1)
1 Rack max.
(Rear face of NT20)
Connection to C
@@
H
Expansion I/O Cable
(NT20M-CNP
@@1/
C200H-CN @@1)
Host interface connector
Connect the CPU Unit with an I/O Connecting Cable. The following restrictions apply when making this connection.
• A maximum of one CPU Unit can be connected.
• Up to two I/O Units can be connected for the one CPU unit, but Expansion
I/O Units cannot be connected.
76
Communicating with the PLC Using C200H Direct Communications
Section 2-7
• It is not possible to connect a C @@H I/O Unit after the NT20. It must be the final connection in the system.
CPU Unit
I/O Connecting Cable
(C20H-CN @@2)
I/O Unit
I/O Connecting Cable
(C20H-CN
@@2)
I/O Unit
2 Units max.
(Rear face of NT20)
I/O Connecting Cable
(NT20M-CNP @@2
/C20H-CN
Host interface connector
Note
When connecting a C
@@H, always install a noise filter.
1.
Insert the noise filter in the power supply line of the C @@H.
2.
Make the distance between the noise filter and the C @@H as short as possible and separate it from the power supply line.
3.
Install the noise filter case on the FG face.
4.
Use a ZGB2202-01U (manufactured by TDK) or equivalent as the noise filter.
Noise filter
1 4
+
+24 V IN OUT 24 V
2 3
–
2-7-3 Turning the Power ON/OFF When Using C200H Direct
Communications
The NT20-ST121-E functions as an expansion I/O unit of the PLC. Use the following procedure to turn the power ON and OFF.
Power ON
!Caution Depending on the method used to turn the power ON and OFF, the entire system may stop. Follow the procedure described below to turn the power ON and OFF.
Turn the power ON as follows:
Turn ON the power to the NT20.
“Connecting to Host” is displayed on the NT20 screen.
77
Communicating with the PLC Using C200H Direct Communications
Power OFF
Note
Note
Section 2-7
↓
Turn ON the power to the PLC.
After “Connecting to Host” has been displayed for approximately 1 second, normal operation starts.
(1) If the power to the PLC is turned ON first, the CPU Unit of the PLC is subjected to a system reset, making operations such as programming console impossible. Then, when the power to the NT20 is turned ON,
“Connecting to Host” is displayed on the NT20 screen for approximately
1 second, after which normal operation starts.
(2) If the I/O Connecting Cable is disconnected during system operation, an
I/O bus error occurs at the PLC and operation stops. If this happens, connect the I/O Connecting Cable and cancel the error.
Turn the power OFF as follows:
Turn OFF the power supplies to the PLC and NT20 simultaneously.
The next time the power is turned ON, the NT20 displays the screen that was displayed when the power was turned OFF.
If the power to the NT20 is turned OFF first, the CPU Unit of the PLC is subjected to a system reset, making operations such as programming console impossible.
Turn OFF the system temporarily before replacing the NT20 (when a fault occurs, for example). If the power to the NT20 only is turned OFF, the system stops immediately and this could cause an accident or damage machinery.
78