Using a Memory Unit
Section 2-5
2-5 Using a Memory Unit
This section explains how to use a Memory Unit with the NT20. By installing a
Memory Unit (NT-MF261) on the NT20, the system program or the screen data in the NT20 can be recorded (backed up) in the Memory Unit.
In addition, the system program or the screen data in the Memory Unit can be automatically read into the NT20 when it starts up. This means that system program and screen data can be changed easily at the operation site without connecting to the NT Support Tool.
The data in the Memory Unit is retained without backup by a battery or other means.
In systems where there are frequent setup changes, by preparing a number of
Memory Units in advance and recording screen data in them according to the control performed in each case, the NT20 screen data can be changed simply by installing the Memory Unit, without connecting to the NT Support Tool.
Even if NT20 is replaced, the previous status can be maintained simply by installing the Memory Unit that retains the system program and screen data of the previous NT20.
By using the following combinations, data can be stored (backed up) to a
Memory Unit.
• Screen data for two PTs.
• System program for two PTs.
• System program and screen data for one PT.
One Memory Unit can store the screen data for two PTs.
Note
(1) Make sure that the power supply to the PT is OFF before connecting or disconnecting a Memory Unit. After mounting a Memory Unit, be sure to tighten its two screws. Otherwise the product may malfunction.
(2) During data transmission, do not turn OFF the power supply to the NT20.
(3) Do not touch the PCB (printed circuit board) with bare hands. Also, discharge any static electricity by touching a grounded object before connecting or disconnecting a Memory Unit. Static electricity may cause the components to malfunction.
(4) Be sure that the combination of the system program and screen data is correct in the NT20 before transferring data from the Memory Unit to the
NT20. If the system program and screen data are not combined correctly, unexpected operation may result.
Reference:
• When a Memory Unit is mounted, the NT20 cannot be set to the operating status. On completion of data transmission with a Memory Unit, always disconnect the Memory Unit from the NT20 before starting NT20 operation.
• One Memory Unit can store a system program for up to two PTs of different models. In order to transmit a system program from the Memory Unit to the NT20, the system program must be compatible to the target PT model.
• The status of memory switch settings can be recorded to the Memory Unit besides screen data. When the data in the Memory Unit is written into the
NT20, make sure that these settings can be adapted to the NT20 used before transmission.
36
Using a Memory Unit
Section 2-5
2-5-1 Installation Method
Install the Memory Unit (NT-MF261) at the expansion interface connector at the rear of the NT20 as shown in the figure below.
Mounting screws
Screw hole
2-5-2 Method of Use
As shown in the figure below, a Memory Unit has 2 four-pin DIP switches, and the operation is determined by the DIP switch settings at startup.
1 2 3 4 1 2 3 4
DIP Switch Functions
Note
Factory setting is turned all to OFF .
OFF
SW1
OFF
SW2
Always confirm that the power to the NT20 is OFF before setting the DIP switches.
The functions of the DIP switches on the Memory Unit are indicated in the table below.
SW1
Pin Function
SW1-1 Automatic transmission (writing from the Memory Unit to the PT)
SW1-2 Automatic transmission (writing from the PT to the Memory Unit)
SW1-3 Manual transmission (Direction of transmission and bank used selected at the PT touch panel)
SW1-4 Data type to transfer
OFF: Not executed
ON: Executed
OFF: Not executed
ON: Executed
OFF: Not executed
ON: Executed
OFF: Screen data
ON: System program
SW2
Pin
SW2-1
SW2-2
Disable/enable writing to PT
Function
SW2-3 Area (bank) selection of automatic transmission
(See note.)
SW2-4
Disable/enable writing to the Memory Unit
System/Screen simultaneous transmission
OFF: Disable
ON: Enable
OFF: Disable
ON: Enabled
OFF: Bank 0
ON: Bank 1
OFF: Disable
ON: Enable
37
Using a Memory Unit
Section 2-5
Writing Screen Data to a
Memory Unit Using
Automatic Transmission
(PT to Memory Unit)
Note
The Memory Unit stores system program or screen data for one PT in each of Areas (bank 0, bank 1). (The total data storage is for two
PTs.) SW2-3 sets which of these two banks is used for automatic transmission.
Reference:
• In the following cases, a mode setting error occurs.
• More than one of the SW1-1 to SW1-3 switches are set to ON.
• None of the SW1-1 to SW1-3 switches are set to ON.
• In the following case, a protect setting error occurs.
Transmitting to the write destination has been disabled by the setting for
SW2-1 or SW2-2.
• In the following cases, a data transmission error occurs.
• An attempt is made to transmit data other than the system program to
PT System Program Area.
• An attempt is made to transmit the system program to PT Screen Data
Area.
• For details on mode setting errors and protect setting errors, refer to
Errors When Using a Memory Unit (page 42).
In this mode, system program or the screen data in the NT20 is forcibly written to the Memory Unit irrespective of the setting status of the NT20.
This mode is convenient if the touch panel is broken and touch switch operation is not possible, or if someone unfamiliar with touch switch operation at the operation site is using the system.
Reference:
When screen data is written to the Memory Unit, the data that has been stored in the specified Area up until that point is lost (if the data is written into only one Bank, the other Bank will not be affected).
■
Method of Execution
Use the following procedure to write the system program or screen data in the
NT20 to the Memory Unit by automatic transmission.
1,2,3...
1.
Check that the power supply to the NT20 is OFF, then set the DIP switches of the Memory Unit as follows after installing Memory Unit to NT20.
ON
ON
1 2 3 4
1 2 3 4
SW1
SW2
SW2-4 ON: System/Screen transmitted simultaneously
OFF: System/Screen not transmitted simultaneously
SW1-4 ON: System program
OFF: Screen data
SW2-3 ON: Bank 1
OFF: Bank 0
It is not strictly necessary to set SW2-1 to OFF (to disable writing to the
PT), but it is recommended to do so to avoid loss of data in the event of operating errors.
Reference:
• Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW1-4.
• Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW2-3, writes the system program into bank 0, and the screen data into bank 1 at all times.
38
Using a Memory Unit
Section 2-5
2.
Turn the NT20 power ON.
The screen data is automatically written into the Memory Unit. The screen data in the NT20 is preserved.
The messages Preparing, Transmitting, Verifying, and Finished are displayed on the screen according to the progress of data writing.
At the same time, the progress of the data writing status is displayed by the means of the number of bytes and blocks (1 bank = 16 block = 1024k byte).
RUN Indicator operates as follows according to the processing status.
Preparing: flashes at intervals of 1 second
Transmitting: flashes at intervals of 0.5 second
Verifying: flashes at intervals of 0.5 second
Finished: lights up
3.
Turn the NT20 power OFF, remove the Memory Unit.
To operate NT20 continuously, turn the NT20 power back ON.
Writing Screen Data to the
PT Using Automatic
Transmission (Memory
Unit to PT)
In this mode, the system program or screen data in the Memory Unit is forcibly written to NT20 irrespective of the setting status of the NT20.
Since data transmission by this method is faster than when the NT Support
Tool or system installer is used, it can save a lot of time. When transmitting the same system program or screen data to multiple NT20, this mode becomes convenient.
Reference:
When data is written to the NT20, the data that has been stored up until that point is lost. When the system program is changed, the operation of NT20 also changes.
■
Method of Execution
Use the following procedure to write the screen data in Memory Unit to the
NT20 by automatic transmission.
1,2,3...
1.
Check that the NT20 power is OFF, then set the DIP switches on the Memory Unit as follows after installing Memory Unit to NT20.
ON
ON
1 2 3 4
1 2 3 4
SW1
SW2
SW2-4 ON: System/Screen transmitted simultaneously
OFF: System/Screen not transmitted simultaneously
SW1-4 ON: System program
OFF: Screen data
SW2-3 ON: Bank 1
OFF: Bank 0
It is not strictly necessary to set SW2-2 to OFF (to disable writing to the
Memory Unit), but it is recommended to do so to avoid loss of data in the event of operating errors.
39
Using a Memory Unit
Section 2-5
Reference:
• Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW1-4.
• Setting SW2-4 to ON (System/Screen transmitted simultaneously) disables the setting of SW2-3. In this case, the data transmission becomes possible only if the data inside Memory Unit is in either of following combinations.
Bank 0: system program, Bank 1: other than system program
Bank 0: other than system program, Bank 1: system program
If the combination is not as listed above, a data transmitting error occurs.
• When writing the system program into the NT20, the type of system program inside Memory Unit and the PT model must correspond.
2.
Turn the NT20 power ON.
The screen data is automatically written into the PT.
The messages Preparing, Transmitting, Verifying and Finished are displayed on the screen according to the progress of data writing.
At the same time, the progress of data writing status is displayed by the means of the number of bytes and blocks (1 bank = 16 block = 1024k byte).
The RUN Indicator operates as follows according to the processing status.
Preparing: flashes at intervals of 1 second
Transmitting: flashes at intervals of 0.5 second
Verifying: flashes at intervals of 0.5 second
Finished: lights up
3.
Turn the NT20 power OFF, remove the Memory Unit.
To operate NT20 continuously, turn the NT20 power back ON.
Reading and Writing Data by Manual Transmission
In this method, the direction of transmission and Area of the Memory Unit used are set by touch switch operations at the NT20. Transmission can be executed while checking the settings.
Reference:
When data is written to the NT20 or Memory Unit, the data that has been stored up until that point is lost.
■
Method of Execution
Use the following procedure to write screen data using manual transmission.
1,2,3...
1.
Check that the NT20 power is OFF, then set the DIP switches on the Memory Unit as follows.
ON
ON
1 2
SW1
3 4
1
SW2
2 3 4
Setting of SW2-4 not relevant
Setting of SW1-4 not relevant Setting of SW2-3 not relevant
In order to avoid loss of data in the event of operating errors, it is advisable to set SW2-1 and SW2-2 so as to disable writing to the Unit from which the data is to be read.
2.
Turn the NT20 power ON.
Display language select screen appears.
40
Using a Memory Unit
Section 2-5
3.
Press the Japanese or English touch switches to select the display language.
The screen shown below is displayed.
Current PT Screen Data, System
The first line: System program name and version for the system program inside the PT.
The second line: Resource name and version for the resource inside the
PT.
Current PT Screen Data, Screen
The comment for the screen data in the NT20 is displayed here.
Current Memory Unit Screen Data
• System Program:
The first line: System program name and version for the system program inside the Memory Unit.
The second line: Resource name and version for the resource inside the
Memory Unit.
• Screen Data:
The comment for the screen data in the NT20 is displayed here.
The available transmitting destinations are altered depending on the settings of the source of transmitting as described in the table below
Source
[PT]screen
[PT]system
Description
[Memory Unit] Bank 0
[Memory Unit] Bank 1
[PT]system/screen
[Memory Unit] Bank 0
[Memory Unit] Bank 1
[Memory Unit] Bank 0/1 (fixed)
• If system program is selected
[PT]system (fixed)
• If screen data is selected
[PT]screen (fixed)
[Memory Unit] Bank 0/1 [PT]system/screen (fixed)
Reference:
• When transmitting the system program and screen data simultaneously from the PT to the Memory Unit, the setting of banks is Bank 0: system program, Bank 1: screen data, and when transmitting them from the
Memory Unit to the PT, either of the following combinations must be used.
Bank 0: system program, Bank 1: other than system program
Bank 0: other than system program, Bank 1: system program
• When writing the system program into the NT20, the type of system program inside Memory Unit and the PT model must correspond.
41
Using a Memory Unit
Errors When Using a
Memory Unit
Section 2-5
4.
Press Execute.
The messages Preparing, Transmitting, Verifying, and Finished are displayed according to the progress of data transmission. At the same time, the progress of data transmitting status is displayed by the means of the number of bytes and blocks (1 bank = 16 block = 1024k byte).
When the data transmission is operated manually, RUN Indicator remains
OFF.
5.
Turn the NT20 power OFF, remove the Memory Unit, then turn the NT20 power back ON.
If an error occurs when using the Memory Unit, the NT20 operates as follows
• Details on the error and remedial action are displayed on the screen.
Each screen has touch switches to change the display language from one to the other. When the manual data transmission is operating, the content of error and remedial action are shown with selected language. When the automatic transmission is operating, it is displayed in Japanese.
• The continuous buzzer sounds.
• The RUN Indicator flashes.
If a protect setting error occurs when executing manual transmission, it is possible to return to the Memory Unit manual transmission screen by pressing the OK touch switch, but in the case of other errors, the status described above remains in effect until the NT20 power is turned OFF or reset.
When an error occurs, take remedial action by referring to the table below.
Error
Mode setting error
Protect setting error
(automatic transmission)
Protect setting error
(manual transmission)
Probable Cause
DIP Switch pins SW1-1 to
SW1-3 are all OFF, or more than one is ON.
Writing to the data write destination has been prohibited by the setting of SW2-1 or SW2-
2.
Writing to the data write destination has been prohibited by the setting of SW2-1 or SW2-
2.
Remedial Action
Turn the NT20 power OFF, set the Memory Unit DIP switches correctly, then turn the NT20 power back ON.
Turn the NT20 power OFF, set the Memory Unit DIP switches correctly, then turn the NT20 power back ON.
Perform either of the following procedures.
• Press the OK touch switch to return to the Memory Unit manual transmission screen, make the correct settings, then try again.
• Turn the NT20 power OFF, correct the DIP switches settings of the Memory Unit, then turn the power back
ON.
Flash memory error An error occurred during initialization of the NT20 or
Memory Unit flash memory, or during write processing.
Turn the NT20 power OFF, then back ON. If the error recurs, the flash memory at the write destination may be faulty. In this case, replace the
Unit.
42
Using a Memory Unit
Section 2-5
Error
Verify error
Transmitting data error (The automatic transmission only)
Probable Cause
An error occurred during verification processing at the flash memory of the NT20 or the
Memory Unit.
An attempt is made to transmit data other than a system program or the system program of a different PT model into the NT20 as the system program.An attempt is made to write a system program into the NT20 as screen data.
Remedial Action
Turn the NT20 power OFF, then back ON. If the error recurs, the flash memory at the write destination may be faulty. In this case, replace the
Unit.
Perform either of the following procedures.
• Turn the NT20 power OFF, correct the DIP switch settings of the Memory Unit, and then turn the power back ON.
• Turn the NT20 power OFF, set the DIP switch settings to the manual transmission, and then check the data inside the Memory Unit.
43