SECTION 7
Troubleshooting and Maintenance
This section describes the action to take when NT20 errors occur, and how to carry out maintenance and inspections to prevent the occurrence of errors.
7-1 Hardware Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2 Responding to Displayed Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2-1 Errors Occurring When the Power Is Turned ON . . . . . . . . . . . . . .
7-2-2 Errors Occurring during Operation. . . . . . . . . . . . . . . . . . . . . . . . . .
7-2-3 Errors Occurring on Screen Data Initialization . . . . . . . . . . . . . . . .
7-2-4 Errors Occurring on Resource Transmit Mode. . . . . . . . . . . . . . . . .
7-2-5 Errors Occurring on System Program Transmit Mode . . . . . . . . . . .
7-2-6 Communications Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-3 Maintenance of the NT20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-4 Inspection and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
248
249
249
249
249
250
250
251
253
253
247
Hardware Faults
Section 7-1
7-1 Hardware Faults
When a fault relating to the operation of the NT20 occurs, find the symptoms in the table below and respond by following the corresponding “Remedy” indicated in the table.
Note
1.
Confirm system safety before turning the power ON/OFF or resetting.
2.
Do not disassemble the PT for repair or modification.
NT20 Symptoms
Nothing is displayed on the screen
Communications with the
Support Tool not possible.
Cannot communicate with the PLC/Host.
Buzzer sounds, RUN LED is OFF.
Touch panel does not respond
PLC mode changes to monitor mode.
Cause
Power is not being supplied.
Remedy
Check the connections and make sure that power is supplied correctly.
(Refer to 2-2-3 Power Supply Connection, page 23.)
Contact your OMRON service center. Power supply fuse has blown
Screen #0 has been read at the host. This is not an error. Change the screen number.
(Refer to 4-3 Screen Display, page 140.)
The Transmit Mode has not been established.
Display the system menu and select the Transmit
Mode. (Refer to 3-6 Registering the Screen Data, page 102.)
Not connected to the Support Tool. Check the installation of the connector cable. (Refer
to 2-4 Connecting the NT Support Tool, page 35.)
The PT type/direct connection settings made at the Support Tool do not agree with the NT20.
Make the PT type setting and direct connection setting in the “PT Configuration” of the Support Tool agree with the NT20.
Memory switch settings do not match. Check the communications setting in the “Memory
Switch” menu of the Maintenance Mode, and match the PLC and NT20 settings.
(Refer to 3-5 Setting the Conditions of Communica-
tions with the Host by Using the Memory Switches, page 91.)
NT20 and PLC are not correctly connected.
Check that the type, length and installation of the connector cable match the specifications.
(Refer to 2-4 Connecting the NT Support Tool,
page 35, 2-6 Connecting to the RS-232C Port at the
Host, page 44.)
Set again with no duplication. When NT link (1:N), there is unit number duplication.
Power not supplied to the NT20, PLC, or host
Check the power supply.
Malfunction due to external noise.
Malfunction due to external noise
Touch panel is broken.
The NT20 changes the mode during host link communications.
Distance the communications cable from the source of the noise and insert a noise filter in the power supply line.
Distance the communications cable from the source of the noise and insert a noise filter in the power supply line.
Check the touch panel by performing the touch panel test in the I/O check in the maintenance mode.
This is normal with the NT20 specification. When using a PLC that can also be connected using the NT link, connect it with the NT link (the mode is not changed when using the NT link).
248
Responding to Displayed Error Messages
Section 7-2
7-2 Responding to Displayed Error Messages
When the NT20 displays an error message, find the corresponding symptoms in the appropriate table below and respond by following the “Remedy” indicated in the table.
7-2-1 Errors Occurring When the Power Is Turned ON
The table below shows the errors that can occur when the power supply to the
NT20 is turned ON, and their remedies.
Message
Screen Data
Corrupted
Mark Data
Corrupted
No direct information is set!
Cause
There is an error in the registered screen data.
Remedy
After initializing the screen data memory in the Maintenance Mode, transmit the screen data once more with the
Support Tool.
There is an error in the registered mark data.
After initializing the screen data memory in the Maintenance Mode, transmit the screen data once more using the
Support Tool.
The allocated words for the
PT status control area and
PT status notify area have not been set.
Use the Support Tool to set the head words of the PT status control area and
PT status notify area, and transmit the screen data again.
There is no screen data. Transmit screen data from the Support
Tool.
7-2-2 Errors Occurring during Operation
The table below shows the errors that can occur during operation of the NT20, and their remedies.
Message
Setting Error
QQ command is not available
Cause
Bits or words allocated to the
PLC memory cannot be found in the screen data.
The PLC cannot be connected to the NT20.
Remedy
Check the memory area in the
PLC used and correct the bit and word allocations in the screen data.
Select a type of PLC that can be connected to the NT20.
7-2-3 Errors Occurring on Screen Data Initialization
The table below shows the errors that can occur when data is written to the
NT20 screen data memory, and their remedies.
Message
Initialization Error
Cause
Hardware fault or screen data memory life reached
Remedy
If the same message is displayed even after executing screen data memory initialization or screen data transmission several times, contact your OMRON service center.
249
Responding to Displayed Error Messages
Section 7-2
7-2-4 Errors Occurring on Resource Transmit Mode
The table below shows the errors that can occur when erasing resource, downloading resource or when NT20 is power on, and their remedies.
Message
Erasing failed.
Downloading failed.
Resource Error!
Cause
Hardware fault or resource memory life reached
Noise caused data corruption during communications
Resource is missing or fragmentary. Checksum of
Resource is wrong. There are any two items unmatched among system program, Font
Data and System Information
Data.
Remedy
Push the reset switch and erase again. If the same message is displayed even after executing erase several times, contact your OMRON service center.
Push the reset switch and download again. Use noiseresistant cable if communications occurs in an environment with high levels of noise.
Turn ON the DIP switch 2-5 and push the reset switch to download resource.
7-2-5 Errors Occurring on System Program Transmit Mode
The table below shows the errors that can occur when erasing system program, downloading system program or when NT20 is power on, and their remedies.
Message
Erasing failed.
Communications
Error Time Out
System program error!
Cause
Hardware fault or resource memory life reached
The connectors or the connecting cable have become disconnected.
The power to the NT20 is switched off, or the NT20 is reset, during transfer.
The power to the personal computer that is running the system transfer tool is switched off, or the personal computer is reset, during transfer.
The cable connecting the personal computer running the system transfer tool and the
NT20 becomes disconnected or sustains a wire breakage during transfer.
Transfer is terminated by pressing any two of the function keys on the panel of the
NT20.
Transfer is terminated by pressing the ESC key of the personal computer running the system transfer tool.
Remedy
Push the reset switch and erase again.
Reconnect the cable. Push the reset switch and download again.
Please download system program again.
250
Responding to Displayed Error Messages
Section 7-2
7-2-6 Communications Errors
This section describes the errors relating to communications with the PLC/
Host that can occur during operation, and their remedies.
• Operation When a Communications Error Occurs
When a communications error occurs, the error message is displayed at the NT20, and the buzzer sounds. Error messages are displayed when the
“Automatic Reset” memory switch is not set.
Some error messages are displayed even if the “Automatic Reset” memory switch is set.
• Procedure When a Communications Error Occurs
When an error message is displayed, press the [EXIT] touch switch displayed on the screen. The screen display will return to the RUN mode.
• Display of Communications Errors
As shown below, communications errors are displayed in the center of the screen, together with a classification indicating whether they are receive or send errors.
Screen When an Error Has Occurred while Receiving
RECEIVING ERROR
EXIT
<Error Description>
Parity Error
Overrun Error
Overflow Error
Framing Error
Buffer Overflow
Time Out
NAK Received
Unit No. Error
FCS Error
Screen When an Error Has Occurred while Sending
RECEIVING ERROR
<Type of error>
Time Out
EXIT
Message
(ACIA)
Parity Error
Framing Error
Overflow Error
Overrun
Buffer Overflow
(NT20-ST128 only)
Cause
Communications parameters/ conditions of communications set incorrectly.
Noise caused data corruption during communications.
Remedy
Check whether the parity bit, frame length, baud rate, stop bit length, and flow control settings of the PLC match the settings of the NT20.
Use a noise-resistant cable if communications occurs in an environment with high levels of noise.
Reconnect the cable.
The connectors of the connecting cable are not connected correctly.
The NT20 receive buffer is full.
Lengthen the command transmission intervals. If this error occurs frequently, set flow control for communications.
251
Responding to Displayed Error Messages
Section 7-2
Message
Time Out
NAK Received
(end code simultaneously displayed)
Unit No. Error
FCS Error
Cause
The connectors of the connecting cable have become disconnected.
The PLC is stopped.
Remedy
Reconnect the cable.
During transmission of one command, a time lapse exceeding 5 seconds is detected.
Noise caused data corruption during communications.
Make sure the PLC is able to communicate with the NT20.
Confirm the proper command length.
Reconnect the cable.
Error returned by host.
The unit # does not match that set on the PLC.
The PLC is transmitting incorrect data.
Noise caused data corruption during communications.
Use a noise-resistant cable if communications occurs in an environment with high levels of noise.
Check the end code by referring to the PLC operation manual.
Set the PLC unit # to “0”.
Check PLC operation.
Use a noise-resistant cable if communications occurs in an environment with high levels of noise.
Check PLC operation.
The PLC is transmitting incorrect data.
Noise caused data corruption during communications.
Use a noise-resistant cable if communications occurs in an environment with high levels of noise.
252
Maintenance of the NT20
Section 7-3
7-3 Maintenance of the NT20
Carry out maintenance work in order to ensure that the NT20 is always used in its optimum condition.
Spare PT
Backlight
!WARNING
Do not attempt to take the PLC apart and do not touch any internal parts while the power is being supplied. Doing either of these may result in electrical shock.
It is advisable to have a spare NT20 available to minimize system downtime in the event of an NT20 failure or if the screen display becomes difficult to read due to deterioration of the display unit.
The backlight must be replaced when the brightness of the display backlight dims and the display becomes difficult to see. The backlight cannot be replaced by the user.
Contact your nearest OMRON representative.
7-4 Inspection and Cleaning
Clean and inspect the NT20 regularly to ensure that it is always used in its optimum condition.
Cleaning Method
Inspection Method
Note
If the display is dirty the screen is difficult to see. Clean the screen from time to time as follows.
• In daily cleaning, wipe the display with a soft dry cloth.
• If the soiling cannot be removed with a dry cloth, wet the cloth with water, wring it out well and wipe the display with it.
• If rubber or vinyl products, tape, etc. are left stuck to the display for long periods they will cause staining. If such items are stuck to the display, remove them during cleaning.
Never use volatile solvents such as benzene or thinners, or dusters.
In normal environments, inspect the NT20 at intervals of between 6 months and a year. In environments that are extremely hot and humid, or very dusty environments, shorten the inspection interval.
• Items Required for Inspection
Prepare the following items before starting the inspection.
• The tools supplied with the NT20
• Screwdrivers (Phillips, flat-head)
• Tester (or digital voltmeter)
• Industrial alcohol
• 100% cotton cloth
• Hygrometer (required in some cases)
• Thermometer (required in some cases)
• Synchroscope (required in some cases)
• Pen-writing oscilloscope (required in some cases)
253
Inspection and Cleaning
Section 7-4
• Faulty Display Pixels
Although the LCD panel has been manufactured with extremely high-level technology, there can sometimes be pixels that will not light or that will be lit constantly. These are characteristic of LCD panels and are not an indication of a faulty display. Please understand that, although we are constantly striving to keep these pixels to a minimum, it is not possible with present technology to eliminate them completely.
• Points Inspected
Inspect the following points to determine if there is any divergence from the stated criteria. If there is, either improve the surrounding environment so that the values fall within the stated range, or adjust the NT20.
Point Inspected Inspection Details
Power supply voltage Fluctuation in power supply terminal voltage
Criterion
Permissible voltage fluctuation range (24 VDC
−
15% +15%)
0 to 50
°C
Inspection Instrument
Tester
Ambient environmental conditions
Ambient temperature (temperature in the operation panel)
Thermometer
Ambient humidity
(humidity in the operation panel)
Presence/absence of dust
35% to 85% Hygrometer
Mounting conditions Looseness of mounting brackets etc.
Looseness of screws in external wiring
Conditions of external connecting cables
Dust must not be settled Visual inspection
To be no looseness
Connector connections of connecting cable To be fully inserted and locked, with no looseness
To be no looseness
Faults such as incipient disconnections.
Accessory tools
Phillips screwdriver
Visual inspection
External appearance Peeling of front sheet Front sheet must not show any signs of peeling.
Visual inspection
Note
(1) Do not attempt to disassemble the NT20 for repair or modification.
(2) The disposal of the NT20 may be regulated by national or local authorities. Dispose of them according to the laws and regulations of the relevant country and local authority.
(3) When replacing the NT20 after discovering a fault during inspections, note the following points:
• Be sure to switch the power OFF before replacement.
• After replacement, check that the new NT20 is not subject to the same error.
• If a faulty unit is returned for repairs, write as detailed a description of the fault as possible and send this description together with the unit to the OMRON address indicated on the back cover of this book.