Bar Graphs
Section 4-5
4-5 Bar Graphs
The contents of the numeral memory table entries of the NT20 can be displayed as bar graphs as well as numeral data.
This section describes the bar graphs which can be displayed.
In order to change the data displayed in a bar graph, the contents of its numeral memory table entries have to be changed.
For details on how to update the data of a currently displayed bar graph, refer
to 5-2-5 Upgrading Bar Graphs (Changing the Contents of Allocated Words)
on page 189, and Four-digit Write Numeral Memory Table on page 219.
4-5-1 Bar Graph Functions
The bar graph function displays a value in a bar graph form as a percentage to the specified value according to the contents of a numeral memory table entry. Up to 50 bar graphs can be registered in one screen.
• Reference Table Entries
The numeral memory table entries used as the reference for the bar graph display can be set.
The Support Tool has the “direct” and “indirect” options for the reference method of the numeral memory table. However, the NT20 recognizes the
“direct” method only.
The bar graph display cannot use hexadecimal numbers. If hexadecimal numbers are set in the reference numeral memory table entries, the bar graph cannot be displayed. Use caution not to write hexadecimal numbers except the minus sign “F” to the reference numeral memory table entries.
Bar Graph Attributes
The following attributes can be set with the NT20 for the bar graph display:
• Position and Size
The display position and size (length) of a bar graph can be set.
The width of the bar graph can be set in the range of 2 to 255 dots.
• Orientation and Incremental Direction
The orientation and incremental direction of the bar graph can be selected from those described below.
↑ (up): The bar graph increments upward in the vertical orientation.
↓ (down): The bar graph increments downward in the vertical orientation.
← (left): The bar graph increments to the left in the horizontal orientation.
→ (right): The bar graph increments to the right in the horizontal orientation.
Direction:
↑
Direction:
→
• Graph Frame
Select whether or not the graph frame (boundary line of a graph display area) which indicates the effective display range is displayed.
← This frame is not displayed if
"Graph frame: No" has been set.
• Setting the 100 % Value and % Display
147
Bar Graphs
Section 4-5
Set a value which corresponds to 100 % for the “100 % value”. The available value range is “0 to 99999999” (eight digits max.). For the “% display”, whether or not the proportion (percentage) of the reference numeral memory table value to the “100 % value” is displayed in a numeral can be selected. The display value is calculated as follows:
“% display” value = Numeral memory table value
÷ “100 % value” x 100
For the font and attributes used for the numeral display, refer to Numerals
Which Can Be Displayed on page 145.
• Sign Display and Display Method
Select whether or not the bar graph which indicates a value below 0 % is displayed.
To Display Values Below 0 %: Sign Display “Yes”
The bar graph is displayed in the range of –100% to 100%. The middle of the bar graph indicates 0%.
% display
−60 %
−100 %
0 % 100 %
To Not Display Values Below 0 %: Sign Display “No”
The bar graph is displayed in the range of 0% to 100%. The end of the bar graph indicates 0%. Values below 0% are indicated as 0%.
% display
60 %
0 % 100 %
• Differences in the Bar Graph Display Method According to the % Values
The bar graph display method varies according to the % value range.
1.
When the % value is in the minus range
The display varies as follows according to the sign display setting:
Sign display “No”: Displayed as 0%.
Sign display “Yes”: Displayed in the minus range.
2.
When the absolute value of the % value is in the range of 100% to 999%
The % value is displayed as it is.
Sign display “No”: The display will be as shown below according to the graph frame setting.
When the frame is displayed:
% display
999 %
0 %
↔
100 %
Graph width: 8 dots
148
Bar Graphs
Section 4-5
When the frame is not displayed:
% display
1-dot-wide space
999 %
↔
100 %
Graph width: 8 dots
0 %
Sign display “Yes”: A value below –100% will be displayed in the minus direction as shown above.
3.
When the absolute value of the % value is above 1000%
The bar graph will be displayed the same as (2) above.
The % value is displayed as follows according to the sign display setting:
Sign display “No”:
***
%
Sign display “Yes”:
****
%
149