Transferring the System Program
Section 3-10
3-10 Transferring the System Program
The system program of the NT20 can be changed by the System Transfer
Tool.
The system transfer tool is automatically installed in the personal computer when the NT20 support tool is installed.
For details on how to start up the System Transfer Tool, and the system transfer tool operation, refer to the NT-series Support Tool Operation Manual
(V061-E1@).
Transferring the System
Program from the System
Transfer Tool
Operation
Note
An NT20 which has no system program registered in it will be able to execute only the installation function.
For details on System Transfer Tool operations, refer to the NT-series Support
Tool Operation Manual (V061-E1@).
In order to transfer the system program from the System Transfer Tool, first connect the NT20 to a personal computer running the System Transfer Tool using the appropriate cable, then proceed as follows.
Reference
The NT20 uses the same connector (Port A) for connection to the Support
Tool and connection to the host. If this connector is currently connected to the host, disconnect the cable from the host and connect it to the Support Tool
(personal computer) before attempting to transfer the system program.
1.
Connect the NT20 to the personal computer running the System Transfer
Tool, then turn ON the power to the NT20.
2.
Turn ON the power to the personal computer and start up the System
Transfer Tool.
3.
When the power to the NT20 is turned ON, the screen shown below will be displayed.
[System Installer V1.00]
-Download System Program-
Ready for downloading.
Yes
4.
Press the Yes button to enter the system transfer mode, as shown below.
[System Installer V1.00]
-Download System Program-
Downloading…
Abort
5.
The NT20 is now on standby for reception. Start transfer of the program by using the System Transfer Tool.
When the NT20 starts reception, the screen shown below will be displayed.
126
Transferring the System Program
[System Installer V1.00]
-Download System Program-
Downloading…
Section 3-10
Abort
6.
When transfer of the system program has been completed, the NT20 will display the screen shown below.
[System Installer V1.00]
-Download System Program-
Downloading is completed
Points to Observe during
Transfer of the System
Program
Method for Erasing the
System Program
Operation
Run System
7.
Press the Run system Button when using the system transfer tool to return to run mode.
If any of the following events or a system error occurs during transfer of the system program, the program will not be installed in the NT20 correctly.
• The power to the NT20 is turned OFF, or the NT20 is reset during transfer.
• The power to the personal computer that is running the System Transfer
Tool is turned OFF, or the personal computer is reset, during transfer.
• The cable connecting the personal computer running the System Transfer
Tool and the NT20 becomes disconnected or sustains a wire breakage during transfer.
• Transfer is terminated by pressing the Abort Button on the NT20.
• Transfer is terminated by pressing the ESC key of the personal computer running the System Transfer Tool.
In the event of any of the above, there is a possibility that the NT20 will not operate or that unpredictable malfunctions will occur.
To prevent this, turn ON DIP switch SW2-6 to erase the system program after the problem has occurred. For details on erasing the system program with the
DIP switch, refer to Method for Erasing the System Program (page 127).
In order to erase the system program, the system program area must be cleared.
If a system program already exists, it must be erased before the new one can be transferred.
Use the following procedure to erase the system program.
1.
Set DIP SW2-6 to the ON position and turn ON the power or reset. The following screen will be displayed.
127
Transferring the System Program
Section 3-10
Exit
-Download System Program-
Erase system program.
Are you sure?
Yes
2.
Press the Exit key if you want to quit without erasing the program. If you do want to erase the program, press Yes Button. This will start erasure of the program.
During erasure, the screen shown below will be displayed:
[System Installer V1.00]
-Download System Program-
Erasing…
3.
On completion of erasure, the screen shown below will be displayed. At this point, set DIP SW2-6 to the OFF position and reset the NT20.
-Download System Program-
Erasing is completed.
Set DIP-SW2-6 to OFF, and
Power OFF/ON.
128