Connecting Link Adapters and RS-422A Converters
Section 2-3
2-3 Connecting Link Adapters and RS-422A Converters
This section describes the installation of the NT-AL001 Link Adapter and
CJ1W-CIF11 RS-422A Converter, including the external dimensions, procedure for mounting and removal, and specifications. Refer to this information when designing the control panel. For further details, refer to the Instruction
Sheet supplied with the NT-AL001 or CJ1W-CIF11.
2-3-1 Connecting an CJ1W-CIF11 RS-422A Converter
The CJ1W-CIF11 RS-422A Converter connects directly to the NT20’s serial port A or B and converts RS-232C communications to RS-422A or RS-485.
The NT20 supplies power to the RS-422A Converter through pin 6 of the RS-
232C connector, so an external power supply is not required.
Note
1.
The RS-232C connector is not insulated from the RS-422A/RS-485 connector within the CJ1W-CIF11 RS-422A Converter. If there are concerns about differences in ground potential or noise, we recommend using the
NT-AL001 Link Adapter.
2.
Always turn OFF the NT20’s power supply before installing/removing a RS-
422A Converter or connecting/disconnecting cables.
3.
Always discharge any static electricity by touching a grounded object before installing the RS-422A Converter or connecting cables.
Specifications
General Specifications
Dimensions
Item
Weight
Ambient operating temperature
Ambient storage temperature
Ambient operating humidity
Rated power supply voltage
Current consumption
Operating atmosphere
Vibration resistance
18.2
× 34.0 × 38.8 mm (W × H × D)
Specification
20 g max.
0 to 55
°C
–20 to 75
°C
10% to 90% (with no condensation)
5 V
40 mA max.
No corrosive gases
Same as NT20 Series.
(Supplied from pin 6 of the RS-232C connector.)
Shock resistance
Isolation method
Same as NT20 Series.
Not isolated
Maximum communications distance 50 m (Use the NT-AL001 if the total communications distance exceeds 50 m.)
RS-232C Connector
Connector Pin Arrangement for
RS-232C Port
Pin number
1
2
3
4
5
6
7, 8
9
Hood
FG
RD
SD
CS
RS
+5V
NC
SG
NC
Signal
24
Connecting Link Adapters and RS-422A Converters
Note
Section 2-3
The hood will have the same electrical potential as the connector on the other end of the cable.
RS-422A/485 Terminal
Block
Signal
RDA–
RDB+
SDA–
SDB+
FG
Block Diagram
SD
RS
CS
SW.6
SW.3
SW.2
SW.1
SDB(+)
SDA( -)
SW.5
RD
RDB(+)
RDA(-)
ER
DR
SV
SG
FG FG
DIP Switch Settings
Pin number
1
Function
Terminating resistance
2
3
4
5
6
ON OFF
With (at both ends of the communications path)
Two-wire method
Without
Four-wire method Two-wire/four-wire method selection (See note 1.)
Two-wire/four-wire method selection (See note 1.)
Not used.
Selection of RS control for RD
(See note 2.)
Selection of RS control for SD
(See note 3.)
Two-wire method
---
With RS control
With RS control
Four-wire method
---
Without RS control (always ready to receive)
Without RS control (always ready to send)
Note
(1) Set pins 2 and 3 to the same setting. (ON for the two-wire method or OFF for the four-wire method.)
(2) To prohibit echoback, set pin 5 to ON (with RS control).
25
Connecting Link Adapters and RS-422A Converters
Section 2-3
(3) When connecting to several devices using the four-wire method in a 1:N connection, set pin 6 to ON (with RS control). When connecting using the two-wire method, set pin 6 to ON (with RS control).
Dimensions
5.8
38.8
18.2
DIP Switch Settings,
Wiring, and Installation
The DIP switch settings must be changed to perform communications according to settings other than the default settings.
1.
Remove the DIP switch cover using a flat-bladed screwdriver in the way shown below.
Wiring the RS-422A/485
Terminal Block
Note
Press the cover gently while removing it to prevent it from popping out suddenly.
2.
Using a fine pair of tweezers or other tool with a fine point, change the settings of the DIP switch pins to match the desired communications conditions.
3.
Be sure to remount the cover after finishing the DIP switch settings.
O
N
3
4
1
2
5
6
O
N
All the pins are factory-set to OFF.
• Use either two-wire or four-wire shielded cable.
Recommended cable: CO-HC-ESV-3P
×7/0.2 (Hirakawa Hewtech)
26
Connecting Link Adapters and RS-422A Converters
Section 2-3
• Connect the shield wire at both ends of the cable carrying RS-422A/485 signals to ground, and ground the ground terminal on the Power Supply
Unit of the CPU or Expansion Rack to 100
Ω max.
1.
Taking care not to damage the shield, strip between 30 and 80 mm of sheath off the end of the cable.
30 to 80 mm
2.
Carefully twist the shield mesh together to form a single wire, and carefully cut off the material surrounding the signal wires and any unnecessary signal wires.
3.
Strip the sheath off the signal wires to a length sufficient to attach crimp terminals. Apply vinyl tape or heat–shrinking tube to the sheathes and stripped parts of communications lines.
4.
Attach stick-type crimp terminals to ends of the signal lines and crimp them using a crimp tool.
• Recommend crimp terminals:
Phoenix Contact
AI Series
AI-0.5-8WH-B (serial number: 3201369)
• Recommended crimp tool:
Phoenix Contact ZA3
With four-wire cables, insert two signal lines into each crimp terminal together before crimping.
• Recommend crimp terminals:
Phoenix Contact
AI Series
AI-TWIN2
×0.5-8WH (serial number: 3200933)
• Recommended crimp tool:
Phoenix Contact
UD6 (serial number: 1204436)
5.
Connect the signal lines and the shield line to the RS-422A/485 terminal block.
27
Connecting Link Adapters and RS-422A Converters
Section 2-3
RS-422A/485 Cable Shield
Connections
When using the CJ1W-CIF11 (with or without the NT-AL001), connect the signal lines, shields, and grounds as shown in the following diagram.
CPU Rack
CPU Unit or Communications
Unit
Power
Supply
Unit
LG
GR
RS-422A/485 shield connected at both ends
Signal line
PT
CJ1W-CIF11
PT
CJ1W-CIF11
PT
CJ1W-CIF11
2-3-2 Connecting an NT-AL001 Link Adapter
The NS-AL001 Link Adapter connects to serial port A or B of the NT20 with an
RS-232C cable and converts the RS-232C communications to RS-422A or
RS-485. (Serial ports A and B cannot be used simultaneously.)
The NT20 supplies +5 V power (150 mA max.) to the Link Adapter through pin
6 of the RS-232C connector, so an external power supply is not required.
Note
1.
The RS-232C connector is insulated from the RS-422A/RS-485 connector within the NT-AL001 Link Adapter.
2.
Always turn OFF the NT20’s power supply before installing/removing a
Link Adapter or connecting/disconnecting cables.
28
Connecting Link Adapters and RS-422A Converters
Dimensions
Section 2-3
The following diagram shows the dimensions of the NT-AL001 Link Adapter.
All dimensions are in mm.
53.5
(2.11)
110 (4.33)
4 (0.16)
74.5 (2.93)
100.2 (3.94)
105 (4.13) max.
NT-AL001-E
(30)
(1.18)
45 (1.77)
30 (1.18)
Installation and Removal
Units: mm (inch)
Dimensions with RS-422A Terminal Block Cover Closed
30
× 114 × 100.2 mm (W × H × D)
Dimensions with RS-422A Terminal Block Cover Open
30
× 114 × 119.5 mm (W × H × D)
The NT-AL001 Link Adapter can be mounted on a DIN Track or in a control panel. The Link Adapter’s RS-422A terminal block can be removed easily.
Mounting to a DIN Track
Latch the hook (a) on the rear of the Link Adapter onto the top edge of the DIN
Track, and pivot the Link Adapter downwards (b) as shown in the diagram below.
Next, fit End Plates at the right and left of the Link Adapter to secure it so that it cannot shift laterally.
(a)
(b)
29
Connecting Link Adapters and RS-422A Converters
Section 2-3
Removal from a DIN Track
Remove the End Plates from the right and left of the Link Adapter, insert a flat blade screwdriver into the catch at the bottom of the Link Adapter, and pull it down to release the catch.
Mounting to a Control Panel
The control panel must be at least 2 mm (5/64 inch) thick. Drill two mounting screw holes in a control panel and secure the Link Adapter with screws.
30
(1.18)
100
(3.94)
110
(4.33)
Specifications
Note
21
(0.83)
2-M4 holes
Units: mm (inch)
The control panel must be at least 2 mm (5/64 inch) thick for a secure and strong mount.
The following tables list the NT-AL001 Link Adapter’s general and communications specifications.
General Specifications
Item Specification
Dimensions
Weight
Ambient temperature
With RS-422A terminal block cover closed:
30
× 114 × 100.2 mm (W × H × D)
With RS-422A terminal block cover open:
30
× 114 × 119.5 mm (W × H × D)
200 g max.
Operating 0 to 55
°C
Storage –20 to 75
°C
Operating ambient humidity 10% to 90% (with no condensation)
Rated power supply voltage +5 V
± 10%
(through pin 6 of the RS-232C connector)
Rated power supply current 150 mA max.
Inrush current
Insulation resistance
0.8 A max.
20 M
Ω min., measured between the RS-422A terminal signal lines and FG terminal (at 500 VDC)
30
Connecting Link Adapters and RS-422A Converters
Section 2-3
Item
Dielectric strength
Operating environment
Vibration resistance
Shock resistance
Specification
1,500 VAC for 1 minute between the RS-422A terminal signal lines and the FG terminal
Leakage current: 10 mA max.
No corrosive gases
Conforms to JIS C0911, 60 minutes each in X, Y, and
Z directions
Conforms to JIS C0912, 147 m/s
2
, 3 times each in X,
Y, and Z directions
Communications Specifications (RS-232C Interface)
Item
Baud rate
Transmission distance
Connector
Specification
115.2k bps max.
2 m max.
9-pin D-SUB connector (female)
Communications Specifications (RS-422A/485 Interface)
Baud rate
Item
500 m max.
Specification
115.2k bps max. (depends on the RS-232C baud rate)
Transmission distance
Terminal block configuration 8-terminal detachable terminal block, M3.0
31
Connecting Link Adapters and RS-422A Converters
DIP Switch Settings
Section 2-3
The NT-AL001 Link Adapter has a 6-pin DIP switch that sets the RS-422A/
RS-485 communications conditions. Set the DIP switch before connecting the communications cable.
Note
ON
1 2 3 4 5 6
(Factory settings)
NT-AL001-E
SW1-1: Not used (always ON)
SW1-2: Built-in terminator setting
- OFF Terminator not set
- ON Terminator set
SW1-3 and SW1-4: 2-wire/4-wire
SW1-3 SW1-4
OFF
2-wire (RS-485)
ON
SW1-3 SW1-4
OFF
ON
4-wire (RS-422A)
SW1-5 and SW1-6: RS-422A send mode
SW1-5 SW1-6
OFF
ON
No RS/CS control
SW1-5 SW1-6
OFF
ON
RS-232C CS control (high)
(Data sent at CS high)
SW1-5 SW1-6
OFF
ON
RS-232C CS control (low)
(Data sent at CS low)
When using Host Link or 1:1 NT Link communications, set the RS-422A send mode to “no RS/CS control” by turn OFF both SW1-5 and SW1-6.
When using 1:N NT Link communications (standard or high-speed), set the communications mode to “RS/CS control” by turning ON either pin SW1-5 or
SW1-6.
1.
Do not turn ON both SW1-5 and SW1-6 at the same time. This may damage internal circuits.
2.
The power supply to the device supplying +5 V must be turned OFF before starting wiring work.
3.
Before connecting the RS-232C cable and turning ON the power to an RS-
232C device such as a PT (i.e., turning ON the power to the Link Adapter), check that the cable is wired correctly and that the DIP switch settings are correct. If the power is turned ON and there is a wiring fault, the internal circuits of the Link Adapter or the RS-232C device may be damaged.
32
Connecting Link Adapters and RS-422A Converters
Terminal Pin Allocation
7
5
3
1
3
4
1
2
5
8
6
4
2
6
7
8
9
Section 2-3
4.
When the Link Adapter is connected to a C200HX/HG/HE (-ZE), CQM1H,
CS1G/H, CS1G/H-H, or CJ1G model of OMRON PLC as an RS-422A device, set pins SW1-5 and SW1-6 as indicated below.
SW1-5
OFF
SW1-6
ON
5 6
The NT-AL001 Link Adapter has a terminal block for an RS-422A/485 interface connection and a connector for an RS-232C interface connection.
The pin allocations for the RS-422A/485 terminal block and the RS-232C connector are as follows.
RS-422A/485 Terminal Block
The CSB and CSA signals are for specialized applications.
8
5
4
7
6
3
2
1
Pin Signal name
Request to send (–)
Request to send (+)
Receive data (–)
Receive data (+)
Send data (–)
Send data (+)
Signal ground
Functional ground
Code
CSA
CSB
RDA
RDB
SDA
SDB
Signal direction
(Link Adapter
⇔ Device)
Link Adapter
→ RS-422A/485 Device
Link Adapter
→ RS-422A/485 Device
Link Adapter
← RS-422A/485 Device
Link Adapter
← RS-422A/485 Device
Link Adapter
→ RS-422A/485 Device
Link Adapter
→ RS-422A/485 Device
SG (GND) ---
---
Compatible Crimp Terminals
Use crimp terminals for M3 screws.
Fork terminal Round terminal
6.2 mm max.
6.2 mm max.
Manufacturer Style
J.S.T. Mfg Co., Ltd.
Fork
Round
Molex Fork
Round
Model Compatible wire
V1.25-N3A
V1.25-MS3
AWG22 to AWG16
(0.25 to 1.65 mm
2
)
VSY1.25-3.5L
AWG22 to AWG16
RAV1.25-3
(0.3 to 1.65 mm
2
)
1
2
3
4
RS-232C Connector
The connector hood is connected to the RS-422A terminal block’s frame ground terminal.
5
6
7
Pin Signal name
Not used
Send data
Receive data
Request to send
(shorted to CS internally)
Clear to send
(shorted to RS internally)
+5 V (150 mA) input for Link
Adapter
Data set ready
(shorted to ER internally)
Code
---
SD
RD
RS
CS
+5 V
DR
Signal direction
(RS-232C Device
⇔ Link Adapter)
---
RS-232C Device
← Link Adapter
RS-232C Device
→ Link Adapter
RS-232C Device
← Link Adapter
RS-232C Device
→ Link Adapter
RS-232C Device
→ Link Adapter
RS-232C Device
→ Link Adapter
33
Connecting Link Adapters and RS-422A Converters
Section 2-3
Block Diagram
RS-232C side
D-SUB 9-pin Case
+5 V
SG
6
Fuse
9
R
Pin Signal name Code
ER
Signal direction
(RS-232C Device
⇔ Link Adapter)
RS-232C Device
← Link Adapter
8 Data terminal ready
(shorted to DR internally)
Signal ground 9 SG ---
The following diagram shows the internal block diagram of the NT-AL001 Link
Adapter. Refer to this diagram only when wiring custom cables or connecting devices with special interfaces.
POWER
Indicator
RS-422A/485 Dr/Rec
DC-DC
Converter
IS_5 V
L L REG
IS_0 V
RS-422A/485 side
8 terminal block
1
FG
2
SG
RD
3
2
SD
RS
4
CS
DR
5
7
8
ER
RS-232C
Dr/Rec
R
Photocoupler
R R R
SW1-6
SW1-5
SW1-3
Terminating resistance
RS-422A Dr
R
SW1-2
3
4
2-wire/
4-wire
SW1-4
SDB
SDA
5
6
RDB
RDA
7
8
CSB
CSA
RS-422A/485 Cable Shield
Connections
When using RS-422A or RS-485 cables for long-distance communications, do not ground the shield at both ends of the communications line because large currents can flow through the shield due to the difference in potential at the two grounding points. We recommend grounding the shield at one end, as shown in the following diagram.
Signal lines
NT-AL001
RS-232C
NT20
Host
RS-422A/485 shield
Connect to the terminal block's
FG terminal.
RS-232C
NT20
RS-232C
NT20
34